Notice! The site will be taken down tonight at 7pm Pacific Time and will be unavailable for an hour while we perform site maintenance.
We apologize for any inconvenience.
JA2.2 - California Design Location Data

The data contained in the following table was obtained through a joint effort by the Southern California Chapter and the Golden Gate Chapter of ASHRAE. It is reprinted here with the written permission of Southern California Chapter ASHRAE, Inc. The values for 1.0 percent drybulb and 1.0 percent mean coincident wetbulb (MCWB) are interpolated.

The data in Table 2-3 is developed from Aa full listing of design location data for California is contained in the ASHRAE publication SPCDX, Climate Data for Region X, Arizona, California, Hawaii, and Nevada (ISBN 200021, May 1982) and Supplement to Climatic Data for Region X, Arizona, California, Hawaii, Nevada (ISBN 20002956, November 1994). The publication may be ordered from:

Order Desk
Building News
10801 National Blvd.
Los Angeles, CA 90064
(888) 264-7483 or (310) 474-7771
http://www.bnibooks.com

Please click on the link below to view Table 2-3

Table 2-3 – Design Day Data for California Cities
City
Latitude
Elevation (ft)
Longitude
Cooling
Heating
0.10%
0.50%
1.00%
2.00%
Design Wetbulb 0.1%
Design Wetbulb 0.5%
Outdoor Daily Range
Winter Median of Extremes
Design Drybulb (0.2%)
Design Drybulb (0.6%)
HDD*
DB
MCWB
DB
MCWB
DB
MCWB
DB
MCWB

Adelanto

34.6

2865

117.4

105

67

101

65

100

64

97

62

70

68

39

14

24

27

1654

din RS

41.2

4195

121

96

61

92

60

91

60

88

59

65

63

43

-7

-2

4

-

Agoura Hills

34.2

700

118.8

103

70

96

68

94

68

90

66

73

71

29

27

31

34

-

Alameda NAS

37.8

15

122.3

88

65

82

64

80

64

76

62

66

64

21

35

38

40

2507

Alamo

37.9

410

122.9

102

69

97

68

96

68

92

66

72

70

30

23

28

31

-

Albany

37.9

40

122.3

88

65

83

64

81

64

77

62

66

64

16

30

35

38

-

Alderpoint

40.2

460

123.6

100

69

95

67

94

67

90

65

70

68

39

21

27

30

3424

Alhambra

34

483

118.1

100

71

96

70

94

70

90

68

73

71

25

30

35

37

-

Aliso Viejo

33.6

50

117.7

91

69

83

68

81

68

76

66

71

69

18

30

33

36

-

Almaden AFS

37.2

3470

121.9

95

62

90

60

89

60

85

59

64

62

20

20

25

29

4468

Alondra Park

33.9

50

118.3

91

69

86

68

85

68

81

66

71

69

17

35

40

42

-

Alpine

32.8

1735

116.8

99

69

95

68

94

68

91

67

72

70

35

27

32

35

-

Alta Sierra

35.7

6500

118.6

87

62

84

61

83

61

80

59

65

63

32

-4

1

8

2428

Altadena

34.2

1200

118.1

99

68

94

67

92

67

88

66

72

70

31

32

37

39

1920

Alturas RS

41.5

4400

120.6

99

62

96

61

95

61

91

59

65

63

43

-10

-4

0

6895

Alum Rock

37.4

70

121.8

95

68

90

66

88

66

84

64

70

68

22

28

33

36

-

American Canyon

37.6

85

122.3

93

67

90

66

88

66

84

64

70

68

23

28

33

36

-

Anaheim

33.8

158

117.9

99

69

92

68

90

68

85

67

73

71

26

32

37

39

-

Anderson

40.5

430

122.3

107

71

103

70

101

70

97

68

72

70

30

26

31

34

-

Angwin

38.6

1815

122.4

98

66

93

64

92

64

88

62

69

66

33

25

30

33

-

Antioch

38

60

121.8

102

70

97

68

95

68

91

66

70

69

34

22

28

31

2627

Apple Valley

34.5

2935

117.2

105

66

101

65

100

65

97

64

70

68

38

14

21

25

-

Aptos

37

500

121.9

94

67

88

66

87

65

83

63

69

67

30

27

32

35

-

Arcadia

34.2

475

118

100

69

96

68

95

68

91

67

73

71

30

31

36

38

-

Arcata

41

218

124.1

75

61

69

59

68

59

65

58

61

60

11

28

31

33

5029

Arden

38.5

80

121.4

104

70

100

69

98

69

94

67

73

71

35

28

33

35

-

Arroyo Grande

35.1

105

120.6

92

66

86

64

84

64

79

62

67

65

18

28

32

35

-

Artesia

33.8

50

118.1

99

71

91

70

89

70

85

68

73

71

23

33

37

40

-

Arvin

35.2

445

118.8

106

71

102

69

101

69

98

68

74

72

30

26

29

32

-

Ash Mtn

36.5

1708

118.8

105

69

101

68

100

68

97

66

72

70

30

25

31

33

2703

Ashland

37.7

45

122.1

92

66

86

65

85

64

81

62

68

66

24

26

31

34

977

Atascadero

35.5

837

120.7

94

66

89

67

88

67

84

65

70

68

42

25

29

32

-

Atherton

37.5

50

122.2

90

66

84

64

82

64

78

62

68

66

27

23

29

33

-

Atwater

37.3

150

120.6

102

72

99

70

98

69

94

67

74

72

38

24

30

34

-

Auberry

37.1

2140

119.5

102

69

98

67

97

66

95

64

71

69

36

21

27

30

3313

Auburn

38.9

1292

121.1

103

69

100

67

99

67

95

66

72

69

33

25

30

33

3089

Avalon

33.4

25

118.3

83

64

75

62

73

62

69

60

68

66

11

37

41

44

2204

Avenal

36

550

120.1

103

70

98

70

97

70

93

69

73

72

34

23

28

31

-

Avocado Heights

34.2

550

118

101

69

97

68

95

68

91

68

74

72

30

28

32

35

741

Azusa

34.1

605

118.2

101

70

97

69

95

69

91

68

74

72

36

31

36

38

-

Baker

35.3

940

116.1

115

73

112

72

111

72

108

70

77

75

29

23

28

31

-

Bakersfield AP

35.4

475

119.1

106

71

102

70

101

70

98

68

74

72

34

26

31

35

2185

Balch PH

36.9

1720

116.0

100

67

97

66

96

66

93

64

71

69

26

26

31

34

-

Baldwin Park

34

394

118

100

69

96

69

94

69

90

68

73

72

32

31

36

38

-

Banning

33.9

2349

116.9

104

69

100

68

99

68

96

67

73

71

34

20

26

30

-

Barrett Dam

32.7

1623

116.7

103

69

97

68

96

68

92

67

73

71

35

22

26

28

2656

Barstow

34.9

2162

117

107

69

104

69

103

69

100

67

74

72

35

16

23

27

2580

Baywood-Los Osos

35.3

100

-

88

65

82

64

80

64

76

62

67

65

14

31

36

38

-

Beale AFB

39.1

113

121.4

105

71

102

70

101

70

97

68

74

72

34

25

28

30

2835

Beaumont

33.9

2605

117

103

68

99

67

98

67

95

66

72

70

38

22

27

30

2628

Bell

33.9

143

118.2

97

70

91

69

89

69

85

67

72

70

22

33

38

41

-

Bell Gardens

33.9

160

118.2

97

70

91

69

87

67

85

67

72

70

22

32

37

40

-

Bellflower

33.8

73

118.1

98

70

91

69

89

69

85

67

72

70

21

32

37

40

-

Belmont

37.5

33

122.3

90

66

84

64

82

64

78

62

68

66

24

29

34

36

-

Ben Lomond

37.1

450

122.1

92

67

85

66

83

65

79

63

69

67

30

25

30

33

-

Benicia

38.1

55

122.1

99

69

93

67

91

67

87

65

70

68

30

28

33

36

Berkeley

37.9

345

122.3

90

64

83

63

81

63

76

61

66

64

16

33

37

40

2950

Berryessa Lake

38.6

480

122.1

102

70

98

69

96

69

92

67

72

70

35

26

31

34

-

Beverly Hills

34.1

268

118.2

94

69

88

68

87

68

83

66

71

69

20

39

43

46

-

Big Bar RS

40.8

1260

121.8

102

68

98

67

97

67

93

65

70

68

46

19

25

28

-

Big Bear Lake

34.2

6745

116.9

87

59

83

58

82

58

79

56

64

62

32

-3

3

7

6850

Bishop AP

37.4

4108

118.4

103

61

100

60

99

60

97

58

65

63

40

5

12

16

4313

Blackhawk

37.7

10

121.9

88

65

82

64

80

64

76

62

66

64

21

35

38

40

977

Blackwells Corner

35.6

644

119.9

99

68

94

66

93

66

89

65

71

69

31

23

28

32

-

Bloomington

34

980

117.4

106

71

102

70

101

70

98

69

75

73

34

30

35

38

-

Blue Canyon AP

39.3

5280

120.7

88

60

85

59

84

59

81

57

64

62

20

13

20

24

5704

Blythe AP

33.6

395

114.7

115

74

112

73

111

73

108

71

80

78

27

28

33

36

1219

Blythe CO

33.6

268

114.6

115

74

112

73

111

73

108

71

80

78

27

24

29

32

1312

Boca

39.4

5575

120.1

92

58

89

57

88

57

84

55

62

60

46

-18

-13

-10

8340

Bodie

38.2

8370

119

83

50

80

49

79

49

76

48

55

53

42

-21

-16

-13

-

Bonadella Ranchos – Madera Rancho

36.8

270

119.9

105

72

101

70

100

70

96

68

74

72

40

29

32

1273

Bonita

32.7

105

117

91

69

82

67

81

66

78

64

70

68

20

28

32

44

1864

Boron AFS

35.1

3015

117.6

106

70

103

69

102

69

98

68

73

71

35

18

23

26

3000

Borrego Desert PK

33.2

805

116.4

112

76

107

74

105

74

101

72

79

77

36

25

30

33

-

Bostonia

32.8

600

116.9

96

70

91

69

88

69

81

67

72

70

30

29

34

36

-

Boulder Creek

37.2

493

122.1

92

67

85

65

83

65

79

63

69

67

30

25

30

33

1120

Bowman Dam

39.4

5347

120.7

89

59

86

57

85

57

82

55

63

60

26

9

17

22

5964

Boyes Hot Sprgs

38.2

300

122.5

100

70

95

69

93

69

89

67

72

70

40

22

28

31

1289

Brannan Island

38.1

30

121.7

100

69

95

68

93

68

89

67

72

70

10

24

28

31

-

Brawley 2 SW

33

-100

115.6

113

74

110

73

109

73

105

73

81

79

32

25

30

33

1204

Brea Dam

33.9

275

117.9

100

69

94

68

92

68

86

66

73

71

29

30

34

37

-

Brentwood

37.9

71

121.7

102

70

97

68

95

67

89

65

71

68

34

27

32

35

-

Bridgeport

38.2

6470

119.2

89

56

86

54

85

54

82

53

60

57

41

-20

-15

-12

-

Broderick-Bryte

38.6

20

121.5

104

71

100

69

98

69

94

67

72

71

36

25

31

35

-

Brooks Ranch

38.8

294

122.2

104

71

99

70

97

70

93

68

73

71

35

19

25

28

2968

Buena Park

33.9

75

118

98

69

92

68

90

68

85

67

72

70

25

31

35

38

-

Burbank AP

34.2

699

118.4

101

70

96

68

94

68

90

67

72

70

28

29

34

36

1701

Burbank Vly Pump

34.2

655

118.4

101

69

96

68

94

68

90

66

72

70

28

29

34

36

1678

Burlingame

37.6

10

122.4

88

67

82

64

80

64

76

63

68

65

20

30

35

37

-

Burney

40.9

3127

121.7

95

64

92

63

91

63

88

61

67

65

42

0

5

12

6404

Butler Valley (Korbel)

40.7

420

123.9

91

66

86

64

85

64

81

62

67

65

22

20

26

29

-

Buttonwillow

35.4

269

119.5

103

71

99

70

98

70

95

68

74

72

36

20

26

29

2621

Cabrillo NM

32.7

410

117.2

89

69

84

68

83

68

80

67

71

69

12

39

43

45

-

Cachuma Lake

34.6

781

120

97

69

92

67

91

67

87

65

70

68

19

26

31

34

-

Calabasas

34.2

1100

118.6

102

71

98

70

97

70

93

69

73

71

26

26

30

33

2348

Calaveras Big Trees

38.3

4696

120.3

92

61

88

60

87

60

84

58

64

62

33

11

18

23

5848

Calexico

32.7

12

115.5

114

74

110

73

109

73

106

71

81

79

28

26

31

34

-

California City

35.1

2400

118

107

69

104

68

103

68

99

66

72

70

33

10

17

22

2572

Callahan

41.3

3185

122.8

97

63

93

62

92

62

88

60

66

64

35

7

15

20

-

Calwa

36.8

330

119.8

105

73

101

71

100

70

97

68

75

73

34

23

27

29

-

Camarillo

34.2

147

119.2

91

69

84

68

82

68

78

67

71

69

22

28

32

35

Cambria AFS

35.5

690

121.1

78

62

72

61

70

61

66

59

64

62

16

30

35

38

3646

Cameron Park

38.6

1800

121

101

67

98

66

97

66

93

65

70

68

42

20

26

29

2235

Camp Pardee

38.2

658

120.9

106

71

103

70

102

70

98

69

74

72

36

27

32

35

2812

Camp Pendleton

33.4

50

117.4

88

69

85

68

84

68

80

67

71

69

12

34

38

40

-

Camp Roberts

35.8

765

120.8

106

72

101

71

99

71

95

69

74

72

45

16

24

27

2890

Campbell

37.3

195

121.8

93

69

88

66

87

66

83

65

71

68

30

28

33

36

-

Campo

32.6

2630

116.5

101

67

95

66

94

66

90

66

71

69

41

16

23

27

3303

Canoga Park

34.2

790

118.6

104

71

99

70

97

70

93

69

74

72

38

25

30

33

1884

Cantil

35.3

2010

118

111

71

107

71

106

71

103

70

74

73

32

12

19

24

-

Canyon Dam

40.1

4555

121.1

93

60

90

59

89

59

85

57

64

62

39

1

6

13

6834

Canyon Lake

33.8

1500

117.3

105

70

101

69

100

69

97

68

74

72

39

22

27

30

-

Capitola

37

64

122

94

67

88

66

86

65

81

63

69

67

24

27

32

35

-

Cardiff-by-the-Sea

33

80

117.3

87

68

83

67

81

67

77

65

70

68

12

35

39

41

-

Carlsbad

33.2

44

117.4

87

68

83

67

81

67

77

65

70

68

10

34

38

40

-

Carmel Valley

36.5

425

121.7

94

68

88

66

86

66

80

65

69

67

20

25

30

33

-

Carmel-by-the-Sea

36.5

20

121.9

87

65

78

62

76

62

71

61

66

63

20

30

35

38

968

Carmichael

38.6

100

121.5

104

70

100

69

98

69

94

68

73

71

35

25

35

37

1290

Carpinteria

34.4

385

119.5

90

69

83

67

81

67

77

65

70

68

15

30

34

37

-

Carson

33.8

60

118.3

96

69

88

68

86

68

82

66

71

69

19

33

38

40

-

Casa de Oro-Mount Helix

32.7

530

117.0

96

71

88

69

87

69

84

67

72

70

19

34

38

41

404

Castle AFB

37.4

188

120.6

105

71

101

70

100

70

96

69

73

71

33

24

28

31

2590

Castro Valley

37.6

177

122.2

93

67

87

67

85

67

80

65

69

68

25

24

29

32

-

Castroville

36.8

20

121.8

86

66

77

63

75

63

70

61

67

64

18

32

37

40

1151

Cathedral City

33.8

400

116.5

117

74

113

73

112

73

109

72

79

78

33

26

31

34

374

Catheys Valley

37.4

1000

120.1

102

69

99

68

98

68

94

67

72

70

38

21

27

30

-

Cecilville

41.1

3000

123.1

95

63

89

62

88

61

84

59

65

63

44

13

20

24

-

Cedarville

41.5

4670

120.2

97

61

94

60

93

60

89

58

65

63

35

1

6

13

6304

Centerville PH

39.8

522

121.7

105

70

100

68

99

68

96

67

72

70

40

25

30

33

2895

Ceres

37.6

90

121

101

72

96

70

94

69

90

67

74

72

36

24

30

34

-

Cerritos

33.9

34

118.1

99

71

92

69

90

69

85

68

73

71

23

33

38

40

-

Charter Oak

34.1

600

117.9

101

70

97

69

95

69

91

68

74

72

34

29

34

36

-

Chatsworth

34.2

964

118.6

98

69

93

68

91

68

87

66

72

70

38

26

31

34

664

Cherry Valley Dam

38

4765

119.9

96

62

92

61

91

61

88

59

65

63

32

9

16

21

-

Cherryland

37.5

100

122.1

93

67

86

66

84

66

79

64

69

67

24

26

31

37

-

Chester

40.3

4525

121.2

94

62

91

61

90

61

86

59

65

63

33

-3

2

8

-

Chico Exp Sta

39.7

205

121.8

105

70

102

69

100

69

96

68

72

71

37

22

27

30

2878

China Lake

35.7

2220

117.7

112

70

108

68

107

68

104

68

74

72

33

15

22

25

2560

Chino

34

714

117.7

104

70

100

69

98

69

94

68

74

72

35

27

32

35

-

Chino Hills

34.1

800

117.7

104

70

100

69

98

69

94

68

74

72

35

27

32

35

800

Chowchilla

37

200

120.3

104

72

101

70

100

70

96

68

74

72

38

22

28

31

1250

Chula Vista

32.6

9

117.1

90

70

84

68

83

68

79

66

71

69

9

33

38

40

2072

Citrus Heights

38.7

138

121.5

104

71

100

70

98

70

94

68

74

72

36

24

26

29

-

Claremont

34.1

1201

117.8

101

69

97

68

95

68

91

66

73

71

34

29

34

36

2049

Clarksburg

38.4

14

121.5

102

70

97

69

95

69

91

67

72

70

35

24

29

32

2971

Clayton

38

60

121.9

102

70

97

68

95

67

89

65

71

68

34

27

32

35

-

Clearlake Highlands

39

1360

122.7

101

69

97

68

95

67

89

65

71

69

36

15

22

26

-

Cloverdale

38.8

320

123

102

70

97

69

95

68

89

66

72

70

37

26

31

34

2763

Clovis

36.8

404

119.7

105

72

102

70

101

70

98

68

74

72

36

22

28

32

-

Coachella

33.7

-76

116.2

114

74

110

73

109

73

106

73

80

79

28

25

30

34

-

Coalinga

36.2

671

120.4

103

70

98

70

97

70

93

69

73

72

34

23

28

31

2592

Colfax

39.1

2418

121

100

66

97

65

96

65

92

63

69

67

29

22

28

31

3424

Colton

34.1

978

117.3

105

70

102

68

101

68

97

67

74

72

35

28

33

36

-

Colusa

39.2

60

122

103

72

100

70

98

70

94

68

74

71

36

23

29

31

2793

Commerce

33.9

175

118.2

98

69

92

68

90

68

86

67

72

70

23

33

37

39

-

Compton

33.9

71

118.2

97

69

90

68

88

68

83

67

72

70

21

33

37

39

1606

Concord

38

195

112

102

70

97

68

95

67

89

65

71

68

34

27

32

35

3035

Corcoran

36.1

200

119.7

106

72

102

71

101

71

98

70

74

73

36

22

28

31

2666

Corning

39.9

487

122.2

106

71

103

70

102

69

98

67

73

71

33

23

28

31

1330

Corona

33.9

710

117.6

104

70

100

69

98

69

92

67

74

72

35

26

31

34

1794

Coronado

32.7

20

117.2

89

69

82

67

80

67

76

65

70

68

10

36

39

41

1500

Corte Madera

37.9

55

122.5

97

68

91

66

89

66

84

64

69

68

34

28

33

35

-

Costa Mesa

33.7

100

117.9

88

68

81

66

79

66

73

65

70

68

16

31

36

38

1482

Cotati

38.3

100

122.7

99

69

94

68

93

68

89

66

71

69

32

24

28

30

1205

Country Club

37.8

600

121.3

102

69

97

68

96

68

92

66

72

70

30

68

28

31

977

Covelo

39.8

1385

123.3

99

67

93

65

91

65

87

63

69

67

43

15

22

26

4179

Covina

34.1

575

117.9

101

70

97

69

95

69

91

68

74

72

34

29

34

36

-

Crescent City

41.8

40

124.2

75

61

69

59

68

59

65

58

61

60

18

28

33

36

4445

Crestline

34.2

4900

117.3

90

62

86

61

85

61

81

59

66

64

26

13

20

24

3200

Crockett

38

9

122.2

96

68

90

66

89

66

85

64

70

67

23

28

33

36

-

Crows Landing

37.4

140

121.1

101

70

96

68

94

68

89

66

72

70

33

23

28

31

2767

Cucamonga

34.1

1450

117.6

103

69

99

68

97

67

93

65

73

71

31

29

34

36

-

Cudahy

33.9

130

118.2

98

70

91

69

89

69

85

67

72

70

21

33

37

39

-

Culver City

34

106

118.4

96

70

88

69

87

69

83

67

72

70

18

35

40

42

1515

Cupertino

37.3

70

122

96

68

88

67

86

66

80

64

70

68

30

28

33

36

-

Cuyama

34.9

2255

116.6

99

68

96

67

94

67

89

66

72

70

42

13

20

24

-

Cuyamaca

33

4650

116.6

92

64

85

62

84

61

81

59

67

65

29

11

18

23

4848

Cypress

33.8

75

118

98

70

92

69

90

69

85

67

72

70

24

31

35

38

Daggett AP

34.9

1915

116.8

109

68

106

68

105

68

102

66

73

72

33

21

26

29

2203

Daly City

37.6

410

122.5

84

65

78

62

77

62

73

61

66

63

16

34

37

39

-

Dana Point

33.5

100

117.7

91

69

84

68

82

68

78

66

71

69

13

30

33

36

600

Danville

37.8

368

122

102

69

97

68

96

68

92

66

72

70

30

23

28

31

977

Davis

38.5

60

121.8

103

72

99

70

97

70

93

68

74

71

41

24

30

34

2844

De Sabla

39.9

2713

121.6

97

66

94

64

92

64

88

62

68

66

35

18

24

27

4237

Death Valley

36.5

-194

116.9

121

77

118

76

117

76

114

74

81

79

28

27

33

37

1147

Deep Springs Clg

37.5

5225

118

98

60

95

59

94

59

92

58

64

62

35

-3

2

8

Deer Creek PH

39.3

4455

120.9

93

61

91

60

90

60

87

58

65

63

39

10

17

22

5863

Del Aire

34

100

118.4

91

69

84

67

83

67

79

66

71

69

15

37

40

42

383

Delano

35.8

323

119.3

106

71

102

70

101

70

98

69

74

72

36

22

25

28

-

Denair

37.6

137

120.8

100

70

95

69

93

69

89

67

72

70

38

22

28

31

2974

Desert Hot Springs

34

1060

116.5

115

73

111

72

110

72

107

71

78

77

35

24

29

32

400

Diamond Bar

34

880

117.8

101

69

97

68

96

68

92

66

73

71

33

28

33

35

-

Dinuba

36.5

340

119.4

104

73

101

70

100

70

96

69

75

73

36

24

30

34

-

Discovery Bay

38.1

10

121.6

102

70

97

68

95

67

89

65

71

68

34

27

32

35

-

Dixon

38.4

100

121.9

104

72

99

70

97

70

93

68

74

71

36

24

30

33

2826

Dobbins

39.4

1640

121.2

104

70

101

68

100

68

96

67

72

70

31

24

29

32

-

Donner Mem Stt Pk

39.3

5937

120.3

85

56

82

56

81

56

77

54

60

58

40

-3

3

6

-

Donner Summit

39.4

7239

120.3

80

53

77

53

76

52

72

50

57

55

40

-8

-1

3

8290

Downey

33.9

110

118

98

71

90

70

88

70

84

68

73

71

21

32

37

39

-

Downieville RS

39.6

2895

120.8

98

64

95

63

94

63

90

61

68

66

42

13

20

24

-

Doyle

40

4390

120.1

96

63

93

62

92

61

88

59

66

64

42

0

5

12

-

Dry Canyon Res

34.5

1455

118.5

105

71

100

69

99

69

96

68

74

72

32

24

29

32

-

Duarte

34.1

500

118

100

69

96

68

94

68

90

67

73

71

33

31

36

38

-

Dublin

37.7

200

121.5

99

69

93

67

91

67

86

65

70

68

35

24

29

32

-

Dudleys

37.7

3000

120.1

97

65

94

64

93

64

90

62

68

66

44

10

17

22

4959

Duttons Landing

38.2

20

122.3

96

68

91

66

89

66

84

64

70

68

31

26

31

34

-

Eagle Mtn

33.8

973

115.5

113

72

110

71

109

71

105

69

77

75

24

32

37

39

1138

Earlimart

35.8

283

119.3

106

71

102

70

101

70

98

69

74

72

36

23

26

29

1100

East Compton

34

71

118.2

97

69

90

68

88

68

83

67

72

70

21

33

37

39

436

East Hemet

33.7

1655

116.9

109

70

104

69

103

69

101

67

74

72

40

20

25

28

-

East La Mirada

33.9

115

118.0

99

70

91

69

89

69

85

68

73

71

26

31

36

38

-

East Los Angeles

34

250

118.3

99

69

92

68

90

68

86

67

72

70

21

38

41

43

-

East Palo Alto

37.5

25

122.1

93

66

85

64

83

64

77

62

68

66

25

26

31

34

1103

East Park Res

39.4

1205

122.5

101

69

97

68

96

68

92

66

71

69

38

19

25

28

3455

East Pasadena

34.2

864

118.1

99

69

94

68

92

68

88

67

73

71

30

32

37

40

452

East Porterville

36.1

393

119.0

106

71

102

70

101

70

97

69

74

72

36

25

30

33

1129

East San Gabriel

34.1

450

118.1

99

70

94

69

92

69

88

68

73

71

30

30

35

37

431

Edwards AFB

34.9

2316

117.9

107

69

104

68

103

68

99

66

72

70

35

10

17

22

3123

El Cajon

32.7

525

117

96

70

91

69

90

69

87

67

72

70

30

29

34

36

-

El Capitan Dam

32.9

600

116.8

105

71

98

70

97

70

93

68

74

72

35

29

34

36

1533

El Centro

32.8

-30

115.6

115

74

111

73

110

73

107

73

81

79

34

26

35

38

1212

El Cerrito

37.8

70

122.3

91

66

84

64

81

64

75

62

68

65

17

30

35

38

-

El Dorado Hills

38.6

673

121.1

103

70

100

69

98

69

94

67

72

71

36

24

30

34

-

El Mirage

34.6

2910

117.6

105

69

101

68

100

68

97

66

72

70

31

9

16

21

-

El Monte

34.1

271

118

101

71

97

70

95

70

91

68

73

71

30

31

36

39

-

El Paso de Robles

35.6

721

120.7

102

65

95

65

94

65

90

65

69

67

44

16

20

23

1768

El Rio

34.3

50

119.2

95

69

88

68

86

68

82

66

71

69

20

30

34

37

-

El Segundo

33.9

105

118.4

91

69

84

68

83

68

79

66

71

69

14

37

40

42

-

El Sobrante

37.9

55

122.3

91

66

87

65

86

65

82

64

69

67

25

30

35

38

823

El Toro MCAS

33.7

380

117.7

96

69

89

69

87

69

82

68

73

71

26

34

38

41

1591

El Toro Station

33.7

380

117.7

96

69

89

69

87

69

82

68

73

71

26

34

38

41

560

Electra PH

38.3

715

120.7

106

70

102

69

101

69

98

68

73

71

41

23

28

31

2858

Elk Grove

38.4

50

121.4

104

71

100

69

98

69

94

68

73

71

35

29

34

36

1150

Elk Valley

42

1705

123.7

96

65

90

63

88

63

84

61

67

65

39

16

23

27

5404

Elsinore

33.7

1285

117.3

105

71

101

70

100

70

98

69

74

72

39

22

26

29

2128

Encinitas

33

50

117.3

87

68

83

67

81

67

77

65

70

68

10

35

39

41

-

Encino

34.2

750

118.5

103

71

98

69

96

69

92

67

74

71

27

28

33

36

664

Enterprise

40.6

470

122.3

107

69

103

68

101

68

97

67

72

70

29

26

31

34

-

Escondido

33.1

660

117.1

97

69

90

68

88

68

84

67

72

70

29

26

31

34

2005

Eureka

40.8

43

124.2

75

61

69

59

68

59

65

58

61

60

11

30

35

38

4679

Exeter

36.3

350

119.1

104

72

101

71

100

71

97

69

74

72

39

24

29

32

1236

Fair Oaks

38.7

50

121.3

104

70

100

69

98

69

94

69

72

71

36

23

29

33

-

Fairfax

38

110

122.6

96

68

90

66

88

65

83

63

71

68

34

26

31

34

-

Fairfield FS

38.3

38

122

103

69

98

68

96

68

91

66

73

71

34

24

30

33

2686

Fairmont

34.7

3060

118.4

100

67

96

66

95

66

92

65

71

69

22

22

28

31

3330

Fairview

35.9

3519

118.5

97

67

94

66

93

66

90

64

70

68

43

11

18

23

-

Fallbrook

33.6

660

117.3

94

68

89

67

88

67

85

66

71

69

29

26

31

34

2077

Farmersville

36.3

350

119.2

104

72

101

72

100

71

97

69

74

72

39

24

29

32

1236

Felton

37

100

122.1

94

68

88

66

86

66

81

64

69

67

28

27

32

35

1097

Ferndale

40.5

1445

124.3

76

57

66

56

65

56

62

54

59

57

12

28

33

35

-

Fillmore

34.4

435

118.9

100

70

94

69

92

69

87

67

73

71

30

28

32

35

-

Five Points

36.4

285

120.2

103

71

99

70

97

70

93

68

73

71

36

21

27

30

-

Fleming Fish & Game

40.4

4000

120.3

96

62

93

61

92

61

88

59

66

64

40

-3

2

8

-

Florence-Graham

34

175

118.3

98

69

90

68

88

68

84

67

72

70

19

35

40

43

-

Florin

38.5

100

121.4

104

71

100

69

98

69

94

68

73

71

35

29

34

36

-

Folsom Dam

38.7

350

121.2

104

70

101

69

99

69

95

67

72

71

36

25

31

35

-

Fontana

34.1

1090

117.4

105

70

101

69

100

69

97

67

74

72

33

30

35

38

1530

Foothill Farms

38.6

90

121.3

104

71

100

70

98

70

94

68

73

71

36

24

30

34

-

Forest Glen

40.4

2340

123.3

96

65

92

64

91

64

88

62

67

65

42

12

19

24

-

Fort Baker

37.8

15

122.5

87

66

81

65

79

65

73

65

67

65

12

33

38

40

3080

Fort Bidwell

41.9

4498

120.1

93

60

90

59

89

59

85

57

64

62

38

-2

3

10

6381

Fort Bragg

39.5

80

123.8

75

60

67

59

66

59

62

58

62

61

15

29

34

37

4424

Fort Jones RS

41.6

2725

122.9

98

64

93

63

92

63

88

61

67

65

44

5

13

18

5590

Fort MacArthur

33.7

200

118.3

92

69

84

68

82

68

78

66

71

69

13

35

40

42

1819

Fort Ord

36.7

134

121.8

86

65

77

63

75

62

70

60

67

64

18

24

29

32

3818

Fort Ross

38.5

116

123.3

79

63

74

62

71

61

65

59

64

62

19

30

35

37

4127

Fortuna

40.6

100

124.2

75

61

69

59

68

59

65

58

61

60

11

30

35

38

2000

Foster City

37.5

20

122.7

92

67

84

65

82

65

76

63

68

66

22

29

34

36

-

Fountain Valley

33.7

60

118

97

70

90

68

88

68

84

67

72

70

18

33

38

40

-

Freedom

37

1495

121.8

89

67

85

64

83

64

79

62

68

65

22

27

32

34

-

Fremont

37.5

56

122

94

67

88

65

86

65

81

63

69

67

24

25

30

33

-

Fresno AP

36.8

328

119.7

104

73

101

71

100

70

97

68

75

73

34

24

28

30

2650

Friant Gov Camp

37

410

119.7

106

72

103

70

102

70

100

68

74

72

40

23

28

31

2768

Fullerton

33.9

340

117.9

100

70

94

69

92

69

87

68

73

71

26

30

35

37

-

Galt

38.2

40

121.3

101

70

97

68

95

68

91

67

72

70

38

23

28

31

1240

Garden Acres

38

20

121.3

103

71

98

69

97

69

93

67

73

71

35

24

28

30

1334

Garden Grove

33.6

85

117.9

98

70

91

68

89

68

84

67

72

70

23

31

36

38

-

Gardena

33.9

40

118.3

92

69

85

68

84

68

80

66

71

69

18

32

37

39

-

George AFB

34.6

2875

117.4

105

67

102

65

101

64

98

62

70

68

31

19

23

26

2887

Georgetown RS

38.9

3001

120.8

98

64

95

63

94

63

90

61

68

66

31

18

24

27

-

Giant Forest

36.6

6412

118.8

84

56

81

55

80

55

77

53

60

58

26

5

13

18

-

Gillespie Field

32.8

385

117.0

98

71

91

70

89

70

85

68

73

71

30

24

29

32

-

Gilroy

37

194

121.6

101

70

93

68

91

67

86

65

72

69

25

23

28

31

-

Glen Avon

34

827

117.5

105

70

101

69

99

69

95

67

74

72

35

28

33

35

-

Glendale

34.2

563

118.3

101

70

96

68

94

68

90

67

73

71

28

30

35

37

-

Glendora

34.1

822

117.9

102

69

98

68

96

68

92

67

73

71

35

30

35

37

-

Glennville

35.7

3140

118.7

97

67

94

66

93

66

90

64

70

68

43

11

18

23

4423

Gold Rock Rch

32.9

485

114.8

113

73

110

72

109

72

106

70

79

77

28

31

36

38

-

Golden Hills

35.1

4000

118.5

97

66

93

65

92

65

89

64

69

67

33

13

20

24

-

Granada Hills

34.4

1032

118.5

100

70

95

68

93

68

89

66

73

70

37

28

31

34

664

Grand Terrace

34.1

1000

117.3

105

70

102

68

101

68

97

67

74

72

35

28

33

36

611

Grant Grove

36.7

6600

119

82

56

78

55

77

54

74

52

59

57

26

6

14

19

7044

Grass Valley

39.2

2400

121.1

99

67

96

65

95

65

91

63

69

67

29

19

25

28

-

Graton

38.4

200

122.9

95

68

91

67

88

66

82

64

70

68

34

22

28

31

3409

Greenacres

35.3

400

119.1

106

71

102

70

101

70

98

68

74

72

34

26

31

35

934

Greenfield

36.2

287

121.2

92

67

88

65

87

65

84

64

70

68

32

22

27

30

1020

Grossmont

32.7

530

117

96

69

89

68

88

68

84

66

71

69

23

31

36

38

-

Grover City

35.1

100

120.6

93

69

86

64

84

64

80

62

67

65

18

30

34

37

-

Guadalupe

35

85

120.6

92

66

86

64

84

64

79

62

67

65

18

28

32

35

1035

Hacienda Hts

34

300

118

100

69

96

68

94

68

90

67

73

71

28

31

36

38

-

Haiwee

36.1

3825

118

102

65

99

64

98

64

95

62

68

66

27

15

22

26

3700

Half Moon Bay

37.5

60

122.4

83

64

76

62

74

61

69

59

65

63

15

32

37

39

3843

Hamilton AFB

38.1

3

122.5

95

69

88

67

86

67

81

65

73

70

28

27

30

32

3311

Hanford

36.3

242

119.7

102

71

99

70

98

70

94

68

73

71

37

22

28

31

2736

Happy Camp RS

41.8

1150

123.4

103

67

97

66

96

66

92

65

69

67

41

18

24

27

4263

Hat Creek PH 1

40.9

3015

121.6

99

65

96

64

95

64

91

62

68

66

48

2

7

17

5689

Hawaiian Gardens

33.8

75

118.1

97

70

91

69

89

69

84

67

72

70

23

32

37

39

-

Hawthorne

33.9

70

118.4

92

69

85

68

84

68

80

66

71

69

16

37

40

42

-

Hayfield Pumps

33.7

1370

115.6

112

71

108

70

107

70

104

68

77

75

31

24

29

32

1529

Hayward

37.7

530

122.1

92

66

86

65

85

64

81

62

68

66

24

26

31

34

2909

Healdsburg

38.6

102

122.9

102

69

95

68

94

68

90

66

71

69

37

26

31

34

2572

Hemet

33.7

1655

117

109

70

104

69

103

69

101

67

74

72

40

20

25

28

-

Henshaw Dam

33.2

2700

116.8

99

68

94

67

93

67

90

66

71

69

38

15

22

26

3708

Hercules

38

15

122.3

91

66

87

65

86

65

82

64

69

67

25

30

35

38

823

Hermosa Beach

33.9

16

118.4

92

69

84

68

82

68

78

66

71

69

12

38

42

45

-

Hesperia

34.4

3191

117.3

105

67

101

65

100

65

97

63

70

68

38

14

21

25

1654

Hetch Hetchy

38

3870

119.8

93

62

89

61

88

61

85

59

65

63

32

14

21

25

4816

Highland

34.1

1315

117.2

106

70

102

69

101

69

97

68

74

72

36

26

31

34

-

Hillcrest Center

35.4

500

-

106

71

102

70

101

70

98

68

74

72

34

26

31

35

-

Hillsborough

37.6

352

122.3

90

66

82

65

80

65

74

64

68

66

23

30

35

37

-

Hilt

42

2900

122.6

97

64

93

62

92

62

89

60

66

64

39

5

13

18

-

Hollister

36.9

280

121.4

96

68

89

67

87

67

81

65

70

68

30

21

27

30

2725

Hollywood

34

384

118.4

96

70

89

69

87

69

83

67

72

70

20

36

41

44

-

Home Gardens

33.9

678

117.5

104

70

100

69

98

69

92

67

74

72

35

26

31

34

-

Hoopa

41

360

123.7

100

67

92

66

91

66

87

64

69

67

25

23

28

31

-

Huntington Beach

33.7

40

117.8

91

69

83

67

81

67

76

66

71

69

14

34

38

41

-

Huntington Lake

37.2

7020

119.2

80

55

77

54

76

53

73

51

58

56

25

3

11

16

7632

Huntington Park

34

175

118

98

70

90

69

88

69

84

67

72

70

20

38

42

45

-

Idlewild

41.9

1250

124

103

68

96

66

95

66

92

65

69

67

40

18

24

27

-

Idria

36.4

2650

120.7

97

66

92

65

91

64

87

62

68

66

27

24

29

32

3128

Idyllwild

33.7

5397

116.7

93

62

89

61

88

61

84

60

67

65

35

9

16

21

-

Imperial AP

32.8

-59

115.6

114

74

110

73

109

73

106

72

81

79

31

26

31

34

1060

Imperial Beach

32.5

23

117.1

87

69

82

68

81

68

78

67

71

69

10

35

39

41

1839

Imperial CO

32.9

-64

115.6

112

73

108

72

107

72

104

71

80

78

31

29

34

36

976

Independence

36.8

3950

118.2

104

61

101

60

100

60

97

60

65

63

31

12

19

24

-

Indio

33.7

11

116.3

115

75

112

75

111

75

107

74

81

79

30

24

29

32

1059

Inglewood

33.9

105

118

92

68

85

67

84

67

80

65

70

68

15

37

40

42

-

Inyokern NAS

35.7

2440

117.8

110

71

106

68

105

68

102

66

75

71

37

15

22

26

2772

Ione

38.3

298

120.9

101

70

97

68

95

68

91

67

72

70

38

23

28

31

-

Iron Mtn

34.1

922

115.1

116

75

112

74

111

74

108

73

80

78

26

29

34

36

1251

Irvine

33.7

50

118

96

69

88

68

86

68

82

67

72

70

27

33

37

40

-

Isla Vista

34.5

40

119.9

90

69

83

67

81

67

77

65

70

68

20

33

38

40

-

Jess Valley

41.3

5300

120.3

92

59

89

58

88

58

84

56

63

61

35

-7

-2

4

7045

John Wayne AP

33.6

115

117.9

98

70

91

68

89

68

84

67

72

70

26

33

37

39

1496

Julian Wynola

33.1

3650

116.8

96

66

91

64

90

64

87

62

69

67

39

20

24

26

4049

Kentfield

38

120

122.6

97

66

91

65

89

65

84

63

70

68

35

27

32

35

3009

Kerman

36.6

216

120.1

105

73

101

71

100

70

97

68

75

73

34

24

28

30

1262

Kern River PH 1

35.5

970

118.8

106

72

103

71

102

71

99

69

75

73

26

30

35

37

1878

Kern River PH 3

35.8

2703

118.6

103

69

100

68

99

68

96

66

72

70

34

19

25

28

2891

Kettleman Stn

36.1

508

120.1

104

71

100

70

98

70

93

68

74

72

31

26

31

34

2180

King City

36.2

320

121.1

94

67

90

65

89

65

85

64

70

68

36

20

26

29

2639

Kingsburg

36.4

297

119.6

104

73

101

71

100

71

97

69

75

73

36

24

30

34

1300

Klamath

41.5

25

124.1

79

62

71

60

70

60

66

58

64

61

18

26

31

33

4509

Knights Ferry

37.8

315

120.6

103

70

99

68

98

68

94

67

73

71

37

19

25

28

-

La Canada-Flintridge

34.2

1365

118

99

69

95

68

93

68

88

66

72

70

30

32

36

38

-

La Crescenta-Montrose

34.2

1565

118

98

69

94

68

92

68

87

66

72

70

33

31

35

37

-

La Habra

33.9

305

118

100

69

94

68

92

68

87

67

72

70

27

30

35

37

-

La Habra Heights

34

400

118

100

69

94

68

92

68

87

67

72

70

27

30

35

37

-

La Mesa

32.8

530

117

94

70

88

69

87

69

84

67

72

70

23

34

39

41

1567

La Mirada

33.9

115

118

99

70

91

69

89

69

85

68

73

71

26

31

36

38

-

La Palma

33.9

75

118

98

69

92

68

90

68

85

67

72

70

25

31

35

38

-

La Puente

34

320

118

101

71

97

70

95

70

91

69

74

72

28

31

36

38

-

La Quinta

33.8

400

116.3

116

74

112

73

111

73

108

72

79

78

34

26

32

34

332

La Riviera

38.6

190

121.3

104

71

100

70

98

70

94

68

73

71

32

30

35

37

1025

La Verne

34.1

1235

118

101

69

97

68

95

68

91

67

73

71

34

29

34

36

-

Ladera Heights

34.1

100

118.4

91

67

84

67

83

67

79

66

71

69

14

37

40

42

383

Lafayette

37.9

535

122.1

100

69

94

67

92

67

87

66

71

69

32

24

29

32

-

Laguna Beach

33.5

35

117.8

91

69

83

68

81

68

76

66

71

69

18

30

33

36

2222

Laguna Niguel

33.6

500

117.7

95

67

87

66

85

65

81

63

71

67

22

33

37

40

-

Lake Arrowhead

34.2

5205

117.2

90

62

86

61

85

61

81

59

66

64

26

13

20

24

5310

Lake Elsinore

33.7

1233

117.3

105

70

101

69

100

69

97

68

74

72

39

22

27

30

827

Lake Los Angeles

34.7

2300

117.8

106

68

102

67

101

67

98

66

72

70

35

12

17

20

1455

Lake Spaulding

39.3

5156

120.6

89

58

86

57

85

57

83

55

62

60

34

3

11

16

6447

Lakeland Village

33.6

1233

117.3

105

70

101

69

100

69

97

68

74

72

39

12

27

30

827

Lakeport

39

1347

122.9

97

67

93

66

92

65

88

63

69

67

41

20

26

29

3728

Lakeshore

40.9

1075

119.2

104

69

100

68

99

68

95

66

71

69

28

29

34

36

-

Lakeside

32.8

690

117

95

69

90

68

89

68

86

66

72

70

20

26

31

34

-

Lakewood

33.9

45

118

98

70

90

68

88

68

84

66

72

70

22

33

37

40

-

Lamont

35.3

500

120

106

72

102

71

101

71

98

69

75

73

34

26

32

35

-

Lancaster

34.7

2340

118.2

106

68

102

67

101

67

98

66

72

70

35

12

17

20

-

Larksfield-Wikiup

38.5

170

122.8

99

69

96

68

95

68

92

66

71

69

35

24

27

29

1249

Larkspur

37.9

20

122.5

97

68

91

66

89

66

84

64

69

68

34

28

33

35

-

Las Plumas

39.7

506

121.4

104

71

101

70

100

70

96

68

73

71

32

24

29

32

-

Lathrop

37.8

22

121.3

103

71

98

69

97

69

93

67

73

71

35

24

28

30

1300

Lava Beds

41.7

4770

121.5

93

59

89

58

88

58

84

56

63

61

41

-1

4

11

-

Lawndale

33.9

66

118

92

69

85

68

84

68

80

66

71

69

16

37

40

42

-

Le Grand

37.2

255

120.3

101

70

96

68

95

68

91

66

72

70

38

23

28

31

2696

Lemon Grove

32.7

437

117.2

96

71

88

69

87

69

84

67

72

70

19

34

38

41

-

Lemoncove

36.4

513

119

105

72

102

70

101

70

98

68

72

70

38

25

38

41

2513

Lemoore NAS

36.3

228

120

104

72

101

71

100

71

97

69

74

72

37

19

25

28

2960

Lennox

33.9

71

117.8

92

69

85

68

84

68

80

66

71

69

16

37

41

44

-

Lincoln Village

38

12

121.3

101

70

96

68

95

68

91

67

72

70

37

24

28

30

1334

Linda

39

60

121.6

105

72

102

70

101

70

97

68

74

72

30

27

32

35

1160

Lindsay

36.2

395

119.1

105

72

101

71

100

71

97

69

74

72

40

24

29

32

2634

Little Panoche

36.8

677

120.7

100

68

94

67

92

67

86

66

71

69

33

23

28

31

-

Live Oak

39.2

75

121.7

105

70

102

69

101

69

97

69

73

71

36

24

29

32

1160

Livermore

37.7

490

122

100

69

95

68

93

68

88

67

71

70

35

22

25

28

3012

Livingston

37.3

165

120.7

103

72

100

70

99

70

95

68

74

72

39

24

30

34

1244

Llano Shawnee

34.5

3820

117.8

104

68

99

67

98

67

95

65

71

69

31

21

27

31

-

Lodgepole

36.6

6735

118.7

84

57

80

56

80

56

78

54

60

58

26

-4

1

7

-

Lodi

38.1

40

121.3

101

70

97

68

95

68

91

67

72

70

38

23

28

31

2859

Loma Linda

34

1150

117.5

106

70

103

69

102

69

99

67

74

72

36

27

32

35

-

Lomita

33.8

56

119

95

69

87

68

85

68

81

66

71

69

18

33

38

40

-

Lompoc

34.9

95

120.5

84

63

77

62

76

62

72

60

65

63

18

26

31

34

2888

Long Beach

33.7

34

118.2

97

70

88

68

86

67

82

65

65

63

18

35

31

34

-

Long Beach AP

33.8

25

118.2

99

71

90

69

88

68

84

66

73

71

21

33

38

41

1606

Loomis

38.8

408

121.2

107

71

103

70

102

70

98

69

74

72

39

21

27

30

-

Los Alamitos NAS

33.8

30

118.1

98

71

89

69

87

69

83

68

73

71

23

32

37

39

1740

Los Altos

37.3

163

122

96

68

88

65

86

64

80

62

70

68

26

28

33

35

-

Los Altos Hills

37.3

183

122.1

93

67

85

64

83

64

77

63

68

66

25

28

33

35

1103

Los Angeles AP

33.9

97

118.4

91

67

84

67

83

67

79

66

71

69

14

37

40

42

1819

Los Angeles CO

34

270

118.2

99

69

92

68

90

68

86

67

72

70

21

38

41

43

1245

Los Banos

37

120

120.9

100

70

96

68

94

68

88

67

72

70

42

22

28

31

2616

Los Banos Res

37

407

120.9

101

70

97

68

95

68

89

67

72

70

42

23

29

31

-

Los Gatos

37.2

365

122

98

69

90

67

88

67

82

66

71

69

32

26

31

34

2741

Los Serranos

34.1

714

117.7

104

70

100

69

98

69

94

68

74

72

35

27

32

35

706

Lucas Vly-Marinwood

38.3

20

122.6

79

63

74

62

71

61

65

59

64

62

12

30

35

37

874

Lucerne Valley

34.5

2957

117

105

67

101

66

100

66

98

64

71

69

38

12

19

24

-

Lynwood

33.9

88

118

98

70

90

69

88

69

83

67

72

70

21

32

37

39

-

Madera

37

268

120.1

105

72

101

70

100

70

96

68

74

72

40

24

29

32

2673

Madera Acres

36.9

275

120.1

105

72

101

70

100

70

96

68

74

72

40

24

29

32

1250

Manhattan Beach

33.9

120

118

91

69

84

68

83

68

79

66

71

69

12

38

42

45

-

Manteca

37.8

34

121.2

102

70

97

68

95

68

91

67

72

70

37

24

29

32

-

Manzanita Lake

40.5

5850

121.6

87

58

84

57

83

57

79

55

61

59

34

-3

2

8

7617

March AFB

33.9

1511

117.3

103

70

99

68

98

67

94

65

74

71

34

23

30

33

2089

Maricopa

35.1

675

119.4

106

71

102

70

101

70

98

68

74

72

29

25

30

33

2302

Marina

36.7

20

121.8

86

66

77

63

75

63

70

61

67

64

18

32

37

40

-

Marina del Rey

34.1

40

118.5

91

69

84

68

83

68

79

66

71

69

12

38

42

45

383

Markley Cove

38.5

480

122.1

104

70

99

69

97

69

93

67

72

70

39

23

29

31

-

Martinez FS

38

40

122.1

99

67

94

66

92

66

88

65

71

69

36

28

33

35

-

Marysville

39.2

60

121.6

105

72

102

70

101

70

97

68

74

72

36

27

32

35

2552

Mather AFB

38.6

96

121.3

104

71

100

70

98

70

94

68

73

71

35

28

33

35

-

Maywood

34

170

118

97

70

91

69

89

69

85

67

72

70

21

34

38

41

-

McClellan AFB

38.7

86

121.4

105

71

102

70

100

70

96

68

74

71

35

23

28

21

2566

McCloud

41.3

3300

122.1

96

63

93

62

91

62

87

60

66

64

42

5

13

18

5990

McFarland

35.6

350

119.2

106

71

102

70

101

70

98

69

74

72

36

22

25

28

1162

McKinleyville

40.9

33

124.1

75

61

69

59

68

59

65

58

61

60

11

28

31

33

1995

Mecca FS

33.6

-180

116.1

115

75

111

75

110

75

107

74

81

79

30

24

29

32

1185

Mendota

36.7

169

120.4

105

73

101

71

100

70

97

68

75

73

34

24

28

30

1273

Menlo Park

37.4

65

122.3

94

67

86

65

84

65

78

63

69

67

25

27

32

34

-

Mentone

34.1

1700

117.1

106

70

102

69

101

69

98

67

74

72

34

27

32

35

741

Merced AP

37.3

153

120.6

103

71

100

69

99

69

95

67

73

71

36

21

27

30

2653

Mill Creek

35.1

2940

117

102

67

97

66

96

66

94

65

70

68

28

28

33

36

-

Mill Valley

37.9

80

122.6

97

68

91

66

89

66

84

64

70

68

28

28

33

35

3400

Millbrae

37.6

10

122.4

90

66

82

63

80

63

74

61

67

65

24

30

35

37

-

Milpitas

37.4

15

121.9

94

68

87

65

85

65

79

63

70

67

27

27

32

35

-

Mineral

40.4

4911

121.6

90

60

87

59

86

59

82

57

63

61

38

2

7

14

7257

Mira Loma

34

700

117.5

105

70

101

69

99

68

95

66

74

72

34

25

33

36

600

Miramar AFS

32.9

477

117.1

97

69

91

68

90

68

86

67

72

70

22

32

36

38

1532

Miramonte

34.4

750

119.1

102

71

97

69

95

69

91

68

73

71

38

25

29

32

771

Mission Viejo

33.6

350

118

95

67

87

66

85

65

81

63

71

67

22

33

37

40

-

Mitchell Caverns

34.9

4350

117.0

102

64

98

63

97

63

94

61

69

67

29

21

27

30

-

Modesto

37.6

91

121

102

73

99

70

98

70

95

68

75

72

36

25

30

33

2671

Moffett Field NAS

37.4

39

122.1

89

68

84

66

82

66

78

64

70

68

23

30

34

36

2511

Mojave

35.1

2735

118.2

106

68

102

67

101

67

98

66

71

69

35

16

22

26

3012

Mono Lake

38

6450

119.2

91

58

88

57

87

57

84

55

62

60

32

4

12

17

6518

Monrovia

34.2

562

118.3

100

69

96

68

94

68

90

67

73

71

30

33

38

41

-

Montague

41.8

2648

122.5

99

66

95

65

94

65

90

63

69

67

39

3

11

16

5474

Montclair

34

1220

117

104

69

100

68

98

68

94

66

73

71

35

28

33

35

-

Montebello

34

205

118.1

98

69

93

68

91

68

86

67

72

70

24

33

37

39

-

Monterey AP

36.6

245

121.9

86

65

77

62

75

62

70

61

66

63

20

30

35

38

3556

Monterey CO

36.6

345

121.9

87

65

78

62

76

62

71

61

66

63

20

32

37

40

3169

Monterey Park

34

380

118

99

69

94

68

92

68

87

67

72

70

23

30

35

37

-

Monticello Dam

38.5

505

122.1

105

71

100

70

98

70

94

68

73

71

39

26

31

34

-

Moraga

37.8

600

122.2

99

68

93

66

91

66

86

64

70

68

27

21

26

29

Moreno Valley

33.9

1600

117.2

103

70

99

68

98

67

94

65

74

71

34

27

30

33

611

Morgan Hill

37.1

350

120

100

69

92

68

90

68

85

66

71

69

25

26

31

34

-

Morro Bay FD

35.4

115

120.9

88

65

82

64

80

64

76

62

67

65

14

31

36

38

-

Mount Baldy Notch

34.3

7735

117.6

80

58

76

57

75

56

71

54

61

59

32

4

10

14

-

Mount Diablo

37.9

2100

121.9

101

68

96

66

93

66

87

65

68

59

28

27

32

35

4600

Mount Hamilton

37.3

4206

121.7

95

59

88

58

86

58

81

56

63

61

18

18

24

27

4724

Mount Hebron RS

41.8

4250

122

92

60

88

59

86

59

82

57

63

61

42

-10

-4

0

-

Mount San Jacinto

33.8

8417

116.6

82

56

77

55

76

55

73

53

61

59

35

-1

4

11

-

Mount Shasta

41.3

3535

122.3

93

62

89

61

88

61

84

59

65

63

34

8

15

20

5890

Mount Wilson

34.2

5709

118.1

90

63

85

61

83

60

79

58

66

64

21

15

22

26

4296

Mountain Pass

35.5

4730

115.5

100

65

96

64

95

64

92

63

68

66

29

11

18

23

-

Mountain View

37.5

95

121.9

93

67

85

64

83

64

77

62

68

66

25

28

33

35

-

Muscoy

34.2

1400

117.3

105

71

101

69

100

68

96

66

75

72

37

26

31

34

614

Nacimiento Dam

35.8

770

120.9

100

68

94

66

92

66

88

64

70

68

35

22

28

31

-

Napa State Hospital

37.3

60

122.3

94

67

91

67

90

67

86

66

71

70

29

26

31

34

2749

National City

32.7

34

117

87

70

82

68

81

68

78

66

71

69

10

36

40

42

-

Needles AP

34.8

913

114.6

117

73

114

72

113

72

110

71

77

75

26

27

32

35

1391

Nevada City

39.3

2600

121

97

66

94

64

92

64

88

63

68

66

41

14

21

25

4900

Newark

37.5

10

122

94

68

89

67

87

67

82

65

70

68

24

29

34

36

-

Newhall Soledad

34.4

1243

118.6

104

70

100

68

99

68

95

67

73

71

42

27

33

36

-

Newman

37.3

90

121.1

104

71

99

69

97

69

93

67

73

71

38

22

28

31

-

Newport Beach

33.6

10

117.9

87

68

80

66

78

66

72

65

70

68

12

34

39

41

1952

Nipomo

35

330

120.5

90

66

83

64

82

63

78

61

67

65

23

25

31

33

1035

Norco

33.9

700

117

103

70

99

69

98

69

94

67

74

72

34

27

32

35

-

North Auburn

38.9

1300

121.1

103

69

100

67

99

67

95

66

72

69

33

25

30

33

1518

North Fork RS

37.2

2630

119.5

98

66

95

65

94

64

92

62

69

67

36

15

22

26

-

North Highlands

38.6

45

121.4

104

71

100

69

98

69

94

67

73

71

35

23

28

31

2566

North Hollywood

34.2

619

118.4

102

70

97

69

95

69

91

67

73

71

31

28

33

36

-

Northridge

34.2

875

118.5

101

70

96

69

94

69

90

67

73

71

36

30

35

38

650

Norwalk

33.9

97

118.1

99

69

90

68

88

68

84

67

72

70

26

31

35

37

-

Novato

38.1

370

122.5

94

64

87

63

85

63

80

61

68

66

30

25

30

32

-

Oakdale

37.8

215

120.9

102

71

99

69

97

69

93

67

73

71

37

22

28

32

-

Oakland AP

37.7

6

122.2

91

66

84

64

82

64

77

62

67

65

20

32

34

37

2909

Oakland Museum

37.8

30

122.2

96

68

89

66

87

65

82

63

69

67

20

31

33

36

-

Oakley

38

20

121.7

102

70

97

68

95

68

91

66

70

69

34

22

28

31

-

Oceano

35.1

20

120.6

93

69

86

64

84

64

80

62

67

65

18

30

34

37

795

Oceanside

33.2

10

117.4

84

69

80

67

78

67

74

65

70

68

10

33

37

39

-

Oildale

35.5

450

119

106

71

102

70

101

70

98

68

74

72

34

26

31

35

-

Ojai

34.5

750

119.3

102

71

97

69

95

69

91

68

73

71

38

25

29

32

2145

Olivehurst

39

64

121.6

105

72

102

70

101

70

97

68

74

72

36

27

32

35

1160

Ontario AP

34

934

117

105

70

101

69

99

68

95

66

74

72

34

26

33

36

1710

Opal Cliffs

37

125

122

94

68

88

66

86

66

81

64

69

67

28

27

32

35

1097

Orange

33.6

194

118

99

70

92

68

90

68

85

67

72

70

27

33

37

40

-

Orange Cove

36.6

431

119.3

104

71

100

69

99

69

97

68

73

71

38

25

30

33

2684

Orangevale

38.7

140

121.2

105

72

102

70

100

70

96

68

74

71

36

24

30

34

-

Orick Prairie Creek

41.4

161

124

80

61

75

60

74

60

70

59

63

61

23

25

30

33

4816

Orinda

37.9

550

122.2

99

68

93

66

91

66

86

64

70

68

32

21

26

29

-

Orland

39.8

254

122.2

105

71

102

70

101

70

97

68

73

71

36

22

28

31

2824

Orleans

41.3

403

123.5

104

70

97

68

95

68

91

66

71

69

42

21

27

30

3628

Orosi

36.5

400

119.3

104

73

101

70

100

70

96

69

75

73

36

24

30

34

1130

Oroville East

39.5

171

121.6

106

71

104

70

102

70

98

69

74

72

37

25

30

33

1385

Oroville RS

39.5

300

121.6

106

71

104

70

102

70

98

69

74

72

37

25

30

33

-

Otay-Castle Pk

32.6

500

117

87

68

81

66

79

65

74

63

69

67

10

33

38

40

-

Oxnard AFB

34.2

49

119.2

94

69

86

68

84

68

79

67

71

69

21

30

34

37

2068

Pacific Grove

36.7

114

122

87

66

78

63

76

63

71

61

67

64

19

31

35

37

-

Pacifica

37.6

13

122

87

65

79

62

77

62

71

60

66

64

16

31

35

37

-

Pacoima

34.3

895

118.4

104

71

99

70

98

70

94

68

74

72

35

29

34

37

664

Palermo

39.4

154

121.5

106

71

104

70

102

70

98

69

74

72

37

25

30

33

1170

Palm Desert

33.7

200

116.5

116

74

112

73

111

73

108

72

79

78

34

26

32

34

-

Palm Desert Country

33.7

243

116.3

116

74

112

73

111

73

108

72

79

78

34

26

32

34

374

Palm Springs

33.8

411

116.5

117

74

113

73

112

73

109

72

79

78

35

26

31

34

1109

Palmdale AP

34.6

2517

118.1

107

67

103

67

102

66

98

64

71

69

33

12

20

24

2929

Palmdale CO

34.6

2596

118.1

106

67

102

67

101

66

97

64

71

69

35

13

21

25

2908

Palo Alto

37.5

25

122.1

93

66

85

64

83

64

77

62

68

66

25

26

31

34

2891

Palomar Obsy

33.4

5545

116.9

90

62

85

61

84

61

80

59

66

64

22

16

20

23

4141

Palos Verdes

33.8

216

119

92

69

84

68

82

68

78

66

71

69

14

38

43

46

-

Panorama City

34.2

801

118.5

103

71

98

69

96

69

92

67

74

71

32

28

33

36

664

Paradise

39.8

1750

121.6

102

69

99

67

98

67

94

66

71

69

34

25

30

33

-

Paramount

33.9

70

117

98

70

90

69

88

69

84

67

72

70

22

32

37

40

-

Parker Res

34.3

738

114.2

115

74

112

73

111

73

108

72

79

77

26

32

37

40

1223

Parkway-South Sacramento

38.5

17

121.4

104

71

100

70

98

70

94

68

73

71

32

30

35

37

1150

Parlier

36.6

320

119.5

104

73

101

71

100

70

97

68

75

73

38

24

30

34

1262

Pasadena

34.2

864

118.2

99

69

94

68

92

68

88

67

73

71

30

32

37

40

1551

Paso Robles AP

35.7

815

120.7

104

66

97

66

96

66

92

65

70

68

40

19

23

26

2973

Paso Robles CO

35.6

700

120.7

102

65

95

65

94

65

90

65

69

67

44

16

20

23

2885

Patterson

37.4

97

121.1

101

72

96

70

94

69

90

67

74

72

36

24

30

34

1240

Pedley

34

718

117.5

105

70

101

69

99

68

95

66

74

72

34

26

33

36

600

Pendleton MCB

33.3

63

117.3

92

68

87

67

85

67

81

66

71

69

22

34

39

41

1532

Pendleton MCB Coast

33.2

24

117.4

84

69

80

67

79

67

75

65

70

68

10

39

44

46

1782

Perris

33.8

1470

117.2

105

70

101

69

100

69

97

68

74

72

39

22

27

30

-

Petaluma FS 2

38.2

16

122.6

98

69

92

67

90

67

85

66

72

69

31

24

29

32

2959

Pico Rivera

34

180

118

98

70

91

69

89

69

85

67

72

70

24

31

35

38

-

Piedmont

37.8

325

122

96

68

89

66

87

65

82

63

70

68

23

31

33

36

-

Pinnacles NM

36.5

1307

121.2

98

68

94

67

93

66

89

64

70

68

45

20

26

29

2956

Pinole

38

10

122.3

91

66

87

65

86

65

82

64

69

67

25

30

35

38

-

Pismo Beach

35.1

80

120.6

92

66

85

64

84

64

80

62

67

65

16

30

34

37

2756

Pittsburg

38

50

121.8

102

70

97

68

95

68

90

67

72

70

34

26

32

35

-

Placentia

33.9

323

118

101

69

93

68

91

68

87

67

73

71

28

30

34

37

-

Placerville

38.7

1890

120.8

101

67

98

66

97

66

93

65

70

68

42

20

26

29

4086

Placerville IFG

38.7

2755

120.8

100

66

97

65

96

65

92

64

69

67

42

23

28

31

-

Platina

40.4

2260

122.9

96

65

92

64

91

63

87

61

67

65

36

13

20

24

-

Pleasant Hill

37.9

102

122

96

68

93

67

92

67

88

65

70

68

34

25

30

33

-

Pleasanton

37.6

350

121.8

97

68

94

67

93

67

89

65

70

68

35

24

29

32

-

Point Arena

38.9

100

123.7

76

62

72

60

71

60

67

58

63

61

19

29

32

34

4747

Point Arguello

34.6

76

120.7

75

64

71

63

69

62

65

59

65

63

17

29

32

35

3826

Point Mugu

34.1

14

119.1

88

68

81

67

79

67

75

66

70

68

15

33

37

39

2328

Point Piedras Blancas

35.7

59

121.3

73

60

67

59

65

59

61

57

62

60

10

36

41

43

3841

Pomona Cal Poly

34.1

740

117.8

102

70

98

69

97

69

93

67

74

72

36

27

32

35

1971

Port Chicago ND

38

50

122

98

69

94

68

92

68

88

66

71

69

34

28

33

36

-

Port Hueneme

34.2

13

119

88

68

81

67

79

67

75

66

70

68

15

33

37

39

2334

Porterville

36.1

393

119

106

71

102

70

101

70

97

69

74

72

36

25

30

33

2456

Portola

39.8

4850

120.5

92

63

89

61

88

61

84

59

65

63

48

-9

-3

1

7111

Posey 3 E

35.8

4960

119

89

62

86

61

85

61

82

59

65

63

26

9

16

21

-

Potter Valley PH

39.4

1015

123.1

101

68

96

67

94

67

89

65

70

68

40

20

26

29

3276

Poway Valley

33

500

117

100

70

94

69

93

69

89

68

73

71

26

29

33

35

-

Priest Valley

36.2

2300

120.7

97

66

93

65

92

65

88

63

69

67

34

13

20

24

4144

Prunedale

36.6

260

121.7

86

66

83

65

82

64

79

62

68

66

20

26

31

34

1100

Quartz Hill

34.6

2428

118.2

106

68

102

67

101

67

98

66

72

70

35

12

17

20

1455

Quincy

39.9

3409

120.9

101

64

98

63

97

63

93

62

68

66

45

1

6

13

5763

Ramona Spaulding

33.1

1480

116.8

103

70

97

69

96

69

92

68

73

71

40

22

28

31

-

Rancho Bernardo

33

500

117.1

96

69

91

68

89

68

85

67

72

70

26

29

34

36

-

Rancho Cordova

38.6

190

121.3

104

72

100

69

98

69

94

68

74

71

35

26

31

33

-

Rancho Mirage

33.8

248

116.4

117

74

113

73

112

73

109

72

79

78

33

26

31

34

374

Rancho Palos Verdes

33.7

216

118.2

92

69

84

68

82

68

78

66

71

69

14

38

43

46

-

Rancho San Diego

32.8

300

117.0

94

69

86

68

85

68

82

66

71

69

30

34

38

41

404

Rancho Santa Margarita

33.6

116

117.6

95

67

87

66

85

65

81

63

71

67

22

33

37

40

496

Randsburg

35.3

3570

117.7

105

67

102

66

101

66

97

65

70

68

30

19

25

28

2922

Red Bluff AP

40.2

342

122.3

107

70

104

69

102

68

98

66

73

71

31

24

29

31

2688

Redding FS 4

40.6

470

122.4

107

69

103

68

101

68

97

67

72

70

30

26

31

34

2544

Redlands

34.1

1318

117.2

106

70

102

69

101

69

98

67

74

72

34

27

32

35

1993

Redondo Beach

33.8

45

118.3

92

69

84

68

82

68

78

66

71

69

12

37

42

44

-

Redwood City

37.5

31

122.2

90

67

86

66

85

66

81

64

69

67

28

28

33

35

2599

Reedley

36.6

344

119.7

104

71

101

70

100

70

96

68

74

72

40

24

30

34

-

Reseda

34.2

736

118.5

103

71

98

69

96

69

92

67

74

71

32

28

33

36

664

Rialto

34.1

1254

117

105

70

101

69

100

68

96

66

74

72

35

28

33

35

-

Richardson Grove

40

500

123.8

96

67

92

66

91

66

87

64

69

67

28

25

30

33

-

Richmond

37.9

55

121.6

88

65

84

64

82

64

77

62

67

65

17

31

36

38

2684

Ridgecrest

35.6

2340

117.8

110

70

106

68

105

68

102

66

75

71

35

15

22

26

-

Rio Del Mar

37

50

121.9

94

67

88

66

87

65

83

63

69

67

30

27

32

35

1097

Rio Linda

38.6

86

121.5

104

72

100

70

98

70

94

68

74

71

32

28

33

35

1290

Ripon

37.7

61

121.1

102

70

97

68

95

68

91

67

72

70

37

23

30

33

1240

Riverbank

37.7

133

120.9

102

73

99

70

98

70

95

68

75

72

36

25

30

33

1240

Riverside Exp Sta

34

986

117.4

106

71

102

69

101

69

97

67

75

72

36

29

34

36

-

Riverside FS 3

34

840

117.4

104

70

100

69

99

68

95

65

74

72

37

27

32

35

1818

Rocklin

38.8

239

121.2

108

72

104

70

103

70

99

69

74

72

39

20

26

29

3143

Rodeo

38.1

15

122.3

93

67

90

66

88

66

84

64

70

68

23

28

33

36

823

Rohnert Park

38.4

106

122.6

99

69

96

68

95

68

92

66

71

69

33

24

27

29

-

Rolling Hills

33.6

216

119

92

69

84

68

82

68

78

66

71

69

15

38

43

46

-

Rosamond

34.8

2326

118.2

106

68

102

67

101

67

98

66

71

69

35

16

22

26

1455

Roseland

38.4

167

122.7

99

69

96

68

95

68

92

66

71

69

35

24

27

29

1249

Rosemead

34

275

118

98

70

90

69

88

69

84

67

72

70

27

30

35

37

-

Rosemont

38.3

190

121.4

104

71

100

70

98

70

94

68

73

71

32

30

35

37

1025

Roseville

38.7

160

121.2

105

71

102

70

100

70

96

68

74

71

36

24

30

34

-

Rossmoor

33.8

20

118.1

92

67

85

64

83

64

79

62

71

69

19

32

37

39

-

Rowland Hts

33.9

540

118

99

70

93

69

91

69

86

68

73

71

27

29

34

36

-

Rubidoux

34

792

117

106

71

102

70

101

70

97

68

75

73

36

27

32

35

-

Sacramento AP

38.5

17

121.5

104

72

100

70

98

70

94

68

74

71

35

26

31

33

2843

Sacramento CO

38.6

84

121.5

104

71

100

70

98

70

94

68

73

71

32

30

35

37

-

Saint Helena

38.5

225

122.5

102

70

98

69

97

69

93

67

72

70

40

22

28

31

2878

Saint Mary's College

37.8

623

122.1

98

69

93

68

91

68

86

66

71

69

28

21

27

30

3543

Salinas 3 E

36.7

85

121.6

86

66

83

65

82

64

79

62

68

66

20

26

31

34

-

Salinas AP

36.7

69

121.6

85

67

82

65

81

64

78

62

69

66

20

28

33

35

2959

Salt Springs PH

38.5

3700

120.2

95

62

92

61

91

61

87

59

66

64

27

19

25

28

3857

Salyer RS

40.9

623

123.6

102

69

95

67

93

66

87

64

70

68

33

22

28

31

-

San Anselmo

38

50

122

95

67

89

66

87

66

82

65

70

68

32

26

31

33

-

San Antonio Canyon

34.2

2394

117.7

100

68

96

67

94

67

90

65

72

70

33

29

35

39

-

San Antonio Mission

36

1060

117.7

99

69

94

68

92

68

88

67

71

69

28

19

25

28

-

San Bernardino

34.1

1125

117.3

106

70

102

69

101

69

98

68

75

72

39

27

31

33

1777

San Bruno

37.7

20

122.4

86

66

80

64

78

64

73

62

67

65

23

30

35

38

3042

San Carlos

37.5

26

122.3

92

67

88

65

86

65

82

63

68

66

28

28

33

35

-

San Clemente

33.4

208

118.6

91

68

85

67

84

67

80

66

71

69

12

31

35

37

-

San Diego AP

32.7

13

117.2

88

70

83

69

82

69

78

68

72

70

13

38

42

44

1507

San Dimas

34

955

118.4

102

70

98

69

96

69

92

67

74

72

35

30

35

37

-

San Fernando

34.3

977

118.5

104

71

99

70

98

70

94

68

74

72

37

30

35

37

1800

San Francisco AP

37.6

8

122.4

89

66

83

64

80

63

74

61

67

64

20

31

35

38

3042

San Francisco CO

37.8

52

122.4

84

65

79

63

77

62

71

60

66

63

14

38

41

44

3080

San Gabriel FD

34.1

450

118.1

99

70

94

69

92

69

88

68

73

71

30

30

35

37

1532

San Gregorio 2 SE

37.3

275

122.4

87

66

81

63

79

63

74

61

68

65

30

27

32

35

-

San Jacinto

33.8

1535

117

110

70

105

69

104

69

102

68

75

73

41

20

26

29

2376

San Jose

37.4

67

121.9

94

68

86

66

84

66

78

64

70

68

26

29

34

36

2438

San Leandro

37.7

45

122.2

89

67

83

64

81

64

76

62

69

66

22

28

33

35

-

San Lorenzo

37.7

45

122.1

89

67

83

64

81

64

76

62

69

66

23

28

33

36

-

San Luis Dam

37.1

277

121.1

97

68

91

66

90

66

86

64

70

68

32

25

30

33

-

San Luis Obispo

35.3

320

120.7

94

63

87

63

85

63

81

62

67

65

26

30

33

35

2498

San Marcos

33.1

567

117.2

97

69

98

68

94

68

84

67

72

70

29

26

31

34

662

San Marino

34.2

300

118.1

100

69

95

68

93

68

88

66

73

71

28

30

35

37

-

San Mateo

37.5

21

122.3

92

67

84

65

82

65

76

63

68

66

24

31

36

38

2655

San Nicholas Island

33.2

504

119.5

85

66

78

65

76

65

70

64

69

67

11

39

43

45

2454

San Pablo

37.6

30

122.3

90

65

84

63

82

63

77

61

69

66

17

29

34

37

-

San Pedro

33.7

10

118.3

92

69

84

68

82

68

78

66

72

70

13

35

31

34

1819

San Rafael

38

40

122.6

96

67

90

65

88

65

83

63

71

68

29

30

35

37

2440

San Ramon

37.7

360

122

99

69

93

67

91

67

86

65

70

68

35

24

29

32

1369

Sandberg

34.8

4517

118.7

95

63

91

61

90

61

87

59

67

65

32

17

21

24

4427

Sanger

36.7

364

119.6

105

72

101

70

100

70

96

68

74

72

37

24

30

34

-

Santa Ana FS

33.8

115

117.8

98

70

91

68

89

68

84

67

72

70

26

33

35

38

1430

Santa Barbara AP

34.4

9

119.8

90

69

83

67

81

67

77

65

70

68

20

29

34

36

2487

Santa Barbara CO

34.4

5

119.7

91

69

84

67

82

67

78

65

70

68

22

33

38

40

1994

Santa Clara Univ

37.4

88

121.9

90

67

87

65

86

65

82

63

69

67

30

29

34

36

2566

Santa Clarita

34.4

1300

118.5

103

71

98

70

97

70

93

68

74

72

36

30

35

37

-

Santa Cruz

37

125

122

94

68

88

66

86

66

81

64

69

67

28

27

32

35

3136

Santa Fe Springs

33.9

280

118.1

99

69

90

68

88

68

84

67

72

70

24

31

36

38

-

Santa Maria AP

34.9

236

120.5

90

66

83

64

82

63

78

61

67

65

23

25

31

33

3053

Santa Monica

34

15

118.5

85

67

78

66

76

66

72

64

69

67

15

39

44

46

1873

Santa Paula

34.4

263

119.1

101

71

94

70

92

70

87

68

73

71

28

28

33

35

2030

Santa Rosa

38.5

167

122.8

99

69

96

68

95

68

92

66

71

69

35

24

27

29

2980

Santee

32.8

400

117

96

69

91

68

90

68

87

67

72

70

20

25

30

33

-

Saratoga

37.3

500

122

96

67

88

66

86

66

80

65

70

68

31

27

32

35

-

Sausalito

37.9

10

122.5

85

66

80

65

78

65

73

63

67

65

12

30

34

36

-

Sawyer's Bar RS

41.3

2169

123.1

100

66

95

65

93

64

88

62

68

66

38

14

21

25

4102

Scotia

40.5

139

124.4

78

61

74

60

73

60

69

58

63

61

19

28

33

35

3954

Scotts Valley

37

400

122

94

68

88

66

86

66

81

64

69

67

28

27

32

35

1097

Seal Beach

33.8

21

118.1

94

69

86

68

84

67

80

65

71

69

15

35

40

42

1519

Seaside

36.6

17

122.9

85

66

79

64

77

64

73

62

67

65

20

30

35

37

-

Sebastapol

38.4

102

122.8

99

69

96

68

95

68

92

66

71

69

35

24

27

29

1249

Selma

36.6

305

119.6

104

73

101

71

100

70

97

68

75

73

38

24

30

34

-

Sepulveda

34.2

818

118.5

103

71

98

69

96

69

92

67

74

71

32

28

33

36

664

Shafter

35.5

345

119.2

106

71

102

70

101

70

98

68

74

72

28

24

29

32

2185

Shasta Dam

40.7

1076

122.4

105

69

101

68

99

68

95

67

72

70

27

29

34

36

2943

Shelter Cove

40

110

124.1

80

61

73

60

72

59

68

57

63

61

15

34

39

41

-

Sherman Oaks

34.2

657

118.5

103

71

98

69

96

69

92

67

74

71

28

29

34

37

664

Sierra City

39.6

4230

120.1

96

62

93

61

92

61

89

59

66

64

43

12

19

24

-

Sierra Madre

34.2

1153

118.1

102

69

96

68

94

68

90

67

73

71

27

32

37

39

-

Sierraville RS

39.6

4975

120.4

94

60

91

59

90

59

86

57

64

62

44

-10

-4

0

6893

Signal Hill

33.5

100

118.2

99

70

90

69

88

68

84

66

72

70

19

35

39

42

-

Simi Valley

34.4

500

118.8

98

70

93

68

91

68

87

66

73

71

30

28

33

35

-

Solana Beach

33

15

117.3

87

68

83

67

81

67

77

65

70

68

10

35

39

41

-

Soledad

36.4

200

121.3

90

67

87

65

86

65

82

64

70

67

23

24

29

32

1020

Sonoma

38.3

70

122.5

101

70

96

69

94

69

90

67

72

70

40

22

28

31

2998

Sonora RS

38

1749

120.4

103

68

100

67

99

67

95

66

72

70

34

20

26

29

3537

Soquel

37

50

122

94

67

88

66

86

65

81

63

69

67

24

27

32

35

1097

South El Monte

34

270

118.1

101

72

97

70

95

70

91

68

74

72

28

31

36

38

-

South Entr Yosemite

37.5

5120

119.6

92

61

88

60

87

60

84

59

64

62

36

8

15

20

5789

South Gate

33.9

120

118.2

97

70

90

69

88

69

84

67

72

70

21

32

37

39

-

South Laguna

33.6

100

117.7

91

69

83

68

82

68

78

66

71

69

18

30

33

36

586

South Lake Tahoe

38.9

6200

120

85

56

82

55

79

55

71

54

60

58

33

-2

3

10

-

South Oroville

39.5

174

121.6

106

71

104

70

102

70

98

69

74

72

37

25

30

33

1385

South Pasadena

34

657

118.2

99

69

94

68

92

68

88

67

73

71

30

31

36

38

-

South San Francisco

37.7

10

122.4

87

67

81

64

78

64

72

62

68

65

20

32

36

38

-

South San Gabriel

34.1

450

118.1

99

70

94

69

92

69

88

68

73

71

73

30

35

37

431

South Whittier

33.9

300

118

100

70

92

69

90

69

84

68

73

71

30

31

36

38

-

South Yuba City

39.1

59

121.6

105

69

101

69

100

69

96

68

72

71

36

24

29

32

1160

Spring Valley

32.7

300

117

94

69

86

68

85

68

82

66

71

69

30

34

38

41

-

Squaw Valley

39.2

6235

120.2

88

57

85

56

84

56

80

54

61

59

40

-10

-4

0

-

Squirrel Inn

34.2

5680

117.2

86

61

82

60

81

60

77

58

65

63

23

12

18

22

5175

Stanford

37.5

23

122.1

93

66

85

64

83

64

77

62

68

66

25

26

31

34

1103

Stanton

33.6

45

118

98

69

91

68

89

68

84

67

72

70

24

31

36

38

-

Stockton AP

37.9

22

121.3

103

71

98

69

97

69

93

67

73

71

35

24

28

30

2806

Stockton FS 4

38

12

121.3

101

70

96

68

95

68

91

67

72

70

37

24

28

30

2846

Stony Gorge Res

39.6

791

122.5

104

70

99

69

97

69

93

67

72

70

37

21

27

30

3149

Strawberry Valley

39.6

3808

121.1

96

63

93

62

92

62

88

60

66

64

32

14

21

25

5120

Studio City

34.3

620

118.4

102

70

97

69

95

69

91

67

73

71

31

28

33

36

664

Suisun City

38.2

72

122

103

71

98

69

96

68

91

66

73

70

35

24

29

32

1299

Sun City

33.7

1420

117.2

105

70

101

69

100

69

97

68

74

72

39

22

27

30

827

Sunland

34.3

1460

118.3

107

71

102

70

100

70

96

68

74

72

36

28

33

36

-

Sunnyvale

37.3

97

122

96

68

88

66

86

66

80

64

70

68

26

29

34

36

2511

Susanville AP

40.4

4148

120.6

98

62

95

61

94

61

90

59

66

64

38

-1

4

11

6233

Taft

35.1

987

119.5

106

71

102

70

101

70

98

68

74

72

34

26

31

35

934

Tahoe City

39.2

6230

120.1

84

56

81

55

80

55

76

53

60

58

36

2

7

14

8085

Tahoe Valley AP

38.9

6254

120.0

85

56

82

55

81

55

77

53

60

58

38

-5

2

6

-

Tamalpais-Homestead Valley

37.9

25

122.5

97

68

91

66

89

66

84

64

70

68

28

28

33

35

874

Tarzana

34.2

800

118.6

104

71

99

69

97

69

93

68

74

71

27

27

32

35

664

Tehachapi

35.1

3975

118.5

97

66

93

65

92

65

89

64

69

67

33

13

20

24

4494

Tejon Rancho

35

1425

118.8

107

71

103

70

102

70

99

68

74

72

27

24

29

32

2602

Temecula

33.5

1006

117.2

101

69

96

68

95

68

91

67

73

71

34

24

29

32

-

Temple City

34.1

403

118.1

101

70

95

69

93

69

89

68

73

71

27

30

35

37

-

Termo

40.9

5300

120.5

95

60

92

59

91

59

87

57

64

62

37

-17

-11

-4

-

Thermal AP

33.6

-112

116.1

114

74

110

74

109

74

106

74

80

79

29

26

31

35

1154

Thermalito

37.9

25

121.6

106

71

104

70

102

70

98

69

74

72

37

25

30

33

-

Thousand Oaks

34.2

810

118.8

98

69

93

68

92

68

88

67

72

70

30

27

32

35

-

Three Rivers PH 1

36.5

1140

118.9

105

70

102

69

101

69

98

67

73

71

38

24

30

32

2642

Tiburon

37.9

90

122.5

85

66

80

65

78

65

73

63

67

65

12

30

34

36

-

Tiger Creek PH

38.5

2355

120.5

100

66

96

65

95

65

92

63

69

67

36

20

26

29

3795

Torrance

33.8

110

118.3

93

69

86

68

84

68

80

66

71

69

18

32

37

39

1859

Tracy Carbona

37.7

140

121.4

102

70

97

68

95

68

90

67

72

70

38

24

29

32

2704

Tracy Pumps

37.8

61

121.4

104

71

99

69

97

69

92

68

73

71

39

23

28

31

-

Travis AFB

38.3

72

121.9

103

71

98

69

96

68

91

66

73

70

35

24

29

32

2725

Trinity Dam

40.8

2500

122.8

99

65

94

64

92

64

88

62

68

66

37

17

24

28

-

Trona

35.8

1695

117.4

113

72

109

70

108

70

105

68

76

73

35

18

24

27

2415

Truckee RS

39.3

5995

120.2

90

58

87

57

86

57

82

55

62

60

40

-10

-4

0

8230

Tujunga

34.3

1820

118.3

103

70

99

69

98

69

94

67

73

71

36

20

26

29

-

Tulare

36.2

290

119.4

105

72

101

71

100

71

96

69

74

72

39

24

30

34

-

Tulelake

42

4035

121.5

92

60

88

59

87

59

83

57

63

61

41

-5

0

6

6854

Turlock

37.5

100

120.9

104

72

100

70

99

70

95

68

74

72

40

24

30

34

-

Turntable Creek

40.8

1067

120.9

105

69

101

68

99

68

95

66

72

70

28

24

29

32

-

Tustin Foothills

33.8

500

117.8

99

71

92

69

90

69

85

68

73

71

27

28

31

34

550

Tustin Irvine Rch

33.7

118

117.8

99

71

92

69

90

69

85

68

73

71

27

28

31

34

1856

Twentynine Palms

34.1

1975

116.1

110

71

107

70

106

70

103

69

76

74

31

21

26

29

1973

Twin Lakes

38.7

7829

119.1

73

49

64

47

62

47

57

46

53

50

30

-7

-2

4

9196

Twitchell Dam

35

582

120.3

99

70

93

68

92

68

88

66

71

69

26

26

31

34

-

UCLA

34.1

430

118.4

93

69

86

68

84

68

80

66

71

69

20

39

43

46

1509

Ukiah

39.2

623

123.2

100

70

97

69

96

69

92

68

72

71

42

22

28

31

2958

Union City

37.6

5

122.1

90

67

87

66

85

65

81

63

69

67

20

25

30

33

-

Upland

34.1

1605

117.7

102

69

98

68

96

68

92

66

73

71

31

29

34

36

2175

Upper Lake RS

39.2

1347

123

98

68

95

67

94

66

91

64

73

71

39

18

34

36

-

Upper San Leandro

37.8

394

122.1

93

67

87

66

85

65

80

63

69

67

22

28

33

35

-

Vacaville

38.4

105

122

103

71

100

70

98

70

94

68

73

71

40

23

28

31

2788

Valinda

34

340

117.9

102

70

98

69

96

69

92

68

74

72

28

31

36

38

-

Valle Vista

33.8

1655

116.9

109

70

104

69

103

69

101

67

74

72

40

20

25

28

-

Vallejo

38.1

85

122.3

93

67

90

66

88

66

84

64

70

68

23

28

33

36

-

Valyermo RS

34.5

3600

117.9

100

67

96

66

95

66

91

65

70

68

41

12

19

24

3870

Van Nuys

34.2

708

118.5

103

71

98

69

96

69

92

67

74

71

30

28

33

39

664

Vandenburg AFB

34.7

368

122.8

85

62

77

61

75

61

71

60

64

62

16

30

35

37

3451

Ventura

34.3

341

119.3

89

68

82

67

80

67

76

66

70

68

15

29

34

36

-

Victorville Pumps

34.5

2858

117.3

105

67

101

65

100

64

97

62

70

68

39

14

24

27

3191

View Park

34

300

118.3

95

69

88

68

85

68

78

66

71

69

18

36

40

43

-

Villa Park

33.8

300

117.8

99

70

92

68

90

68

85

67

72

70

27

33

37

40

550

Vincent

34.5

3135

118.1

105

67

101

65

100

65

96

64

71

69

33

10

18

22

1455

Visalia

36.3

325

119.3

103

71

100

70

99

70

96

69

73

72

38

25

30

33

2459

Vista

33.2

510

117.2

96

69

90

68

89

68

85

67

72

70

16

30

35

37

-

Volta PH

40.5

2220

120.9

101

66

98

65

97

65

93

63

69

67

33

21

27

30

-

Walnut

34

550

117.9

101

70

97

69

96

69

92

69

74

72

30

28

33

35

-

Walnut Creek

37.9

245

122.1

100

69

94

67

92

67

87

66

71

69

32

23

29

31

-

Walnut Grove

38.2

23

121.5

102

70

98

69

96

69

92

68

72

71

37

24

30

32

-

Walnut Park

33.9

45

118.2

92

69

84

68

82

68

78

66

71

69

12

37

42

44

450

Warner Springs

33.3

3180

116.6

100

67

95

66

94

66

91

65

71

69

40

15

22

26

3591

Wasco

35.6

333

119.3

105

71

101

70

100

70

97

68

74

72

36

23

28

31

2466

Watsonville

36.9

95

121.8

86

66

82

64

81

63

79

61

68

65

22

28

33

35

3418

Weaverville RS

40.7

2050

122.9

100

67

95

66

93

65

89

63

69

67

46

10

17

22

4992

Weed FD

41.4

3590

122.4

92

63

89

62

88

61

84

59

65

63

35

4

12

17

-

West Athens

33.9

25

118.3

92

69

85

68

84

68

80

66

71

69

18

32

37

39

450

West Carson

33.8

100

118.3

92

69

87

68

85

68

81

66

71

69

18

32

37

39

-

West Compton

33.9

71

118.3

97

69

90

68

88

68

83

67

72

70

21

33

37

39

450

West Covina

34

365

117.9

102

70

98

69

96

69

92

68

74

72

34

29

34

36

-

West Hollywood

34

290

118.4

95

70

89

69

87

69

82

67

72

70

20

38

42

45

-

West Pittsburg

38

12

121.9

102

70

97

68

95

68

90

67

72

70

34

26

32

35

-

West Puente Valley

34

500

117.9

101

71

97

70

95

70

91

68

73

71

26

31

36

39

-

West Sacramento

38.6

19

121.5

104

72

100

70

98

70

94

68

74

71

35

26

31

33

1290

West Whittier-Los Nietos

34

320

118.1

99

69

90

68

88

68

84

67

72

70

24

31

35

38

-

Westlake Village

34.2

750

118.8

103

71

99

70

98

70

94

69

73

71

26

26

30

33

-

Westminster

33.8

38

118

95

70

88

68

86

68

81

67

72

70

23

33

38

41

-

Westmont

33.9

110

118.3

96

70

89

69

87

69

83

67

72

70

20

36

41

44

400

Whiskeytown Res

40.6

1295

122.6

105

69

101

68

100

68

96

67

72

70

31

25

30

33

-

White Mtn 1

37.5

10150

119.3

73

49

69

47

68

47

65

45

53

50

37

-15

-9

-6

-

White Mtn 2

37.6

12470

119.3

61

42

58

41

57

41

54

40

46

43

38

-20

-15

-12

-

Whittier

34

320

118

99

69

90

68

88

68

84

67

72

70

24

31

35

38

-

Wildomar

33.6

1255

117.3

103

70

99

69

98

69

94

68

74

72

36

23

28

30

827

Wildrose RS

36.3

4100

100

64

97

63

96

63

93

61

68

66

33

13

20

24

-

Williams

39.2

85

122.2

104

71

100

70

98

70

94

68

73

71

36

24

29

32

-

Willits

39.4

1350

123.3

95

66

89

65

87

64

82

62

68

66

38

18

24

27

-

Willow Brook

33.9

60

118.2

97

70

90

69

88

69

83

67

72

70

21

35

39

42

-

Willow Creek

41

461

123

104

70

98

68

96

68

92

66

71

69

35

22

28

31

-

Willows

39.5

140

122.2

104

71

100

70

98

70

94

68

73

71

36

22

28

31

2836

Windsor

38.5

130

122.8

99

69

96

68

95

68

92

66

71

69

35

24

27

29

1249

Winters

38.5

135

122

104

71

99

70

97

70

93

68

73

71

38

24

29

32

2593

Winton

37.4

168

120.6

103

71

100

69

99

69

95

67

73

71

36

21

27

30

1244

Woodcrest

33.9

1500

117.4

104

70

100

69

99

68

95

65

74

72

37

27

32

35

611

Woodfords

38.8

5671

119.8

92

59

89

58

88

58

84

56

63

61

32

0

5

12

6047

Woodlake

36.3

500

119.1

103

71

100

70

99

70

96

69

73

72

38

25

30

33

1130

Woodland

38.7

69

121.8

106

72

101

71

100

71

96

69

74

72

40

25

30

33

2708

Woodland Hills

34.2

944

118.6

104

71

99

70

97

70

93

68

74

72

32

26

31

34

664

Woodside

37.5

75

122.3

92

67

84

66

82

65

76

63

69

67

24

22

28

31

-

Yorba Linda

33.9

350

117.8

102

70

94

69

92

69

88

68

73

71

31

30

35

37

1643

Yosemite Park Hq

37.7

3970

119.6

97

63

94

62

93

62

90

60

67

65

38

11

18

23

4785

Yreka

41.7

2625

122.6

99

66

95

65

94

65

90

64

69

67

39

8

15

20

5395

Yuba City

39.1

70

121.6

105

69

101

69

100

69

96

68

72

71

36

24

29

32

-

Yucaipa

34

2600

117

106

68

102

67

101

67

98

65

73

71

35

27

32

35

-

Yucca Valley

34.2

2600

116.4

108

71

105

70

104

70

101

69

75

73

32

19

24

27

862

*Heating Degree Day is a unit, based on temperature difference and time, used in estimating fuel consumption and specifying nominal annual heating load of a building. For any one day when the mean temperature is less than 65ºF (18ºC), there exist as many degree days as there are Fahrenheit degrees difference in temperature between mean temperature for the day and 65ºF (18ºC).

KEY TO ABBREVIATIONS:

AFB
Air Force Base
AFS
Air Force Station
AP
Airport
CO
City/County Office
FD
Fire Department
FS
F ire Station
MCB
Marine Corps Base
MCWB
Mean Coincident Wet Bulb
NAS
Naval Air Station
NM
National Monument
PH
Power House
RS
Ranger Station

This panel displays referenced content when certain links are clicked.

This program is funded by California utility customers and administered by Pacific Gas and Electric Company (PG&E), San Diego Gas & Electric Company (SDG&E®), and Southern California Edison Company (SCE) under the auspices of the California Public Utilities Commission.

© 2025 PG&E, SDG&E and SCE. All rights reserved, except that this content may be used, copied, and distributed without modification. Neither PG&E, SDG&E, nor SCE — nor any of their employees makes any warranty, express of implied; or assumes any legal liability or responsibility for the accuracy, completeness or usefulness of any data, information, method, product, policy or process disclosed in this document; or represents that its use will not infringe any privately-owned rights including, but not limited to patents, trademarks or copyrights.