EXCEPTION to Section 160.4(e)3: Boilers with steady state full-load thermal combustion efficiency 90 percent or higher.
| 
                 Fluid Operating Temperature Range (°F) 
             | 
            
                 Insulation Conductivity 
             | 
            
                 Nominal Pipe Diameter (in inches) 
             | 
        |||||||
| 
                 Conductivity 
            (in Btu·in /h·ft2 · °F)  | 
            
                 Mean Rating Temperature (°F) 
             | 
        ||||||||
| 
                 < 1 
             | 
            
                 1 to <1.5 
             | 
            
                 1.5 to < 4 
             | 
            
                 4 to < 8 
             | 
            
                 8 and larger 
             | 
        |||||
| 
                 Multifamily Domestic Hot Water Systems 
             | 
            
                 Minimum Pipe Insulation Required (Thickness in inches or R-value) 
             | 
        ||||||||
| 
                 105-1401 
             | 
            
                 0.22-0.28 
             | 
            
                 100 
             | 
            
                 Inches 
             | 
            
                 1.0 
             | 
            
                 1.5 
             | 
            
                 2.0 
             | 
            
                 2.0 
             | 
            
                 2.0 
             | 
        |
| 
                 R-value 
             | 
            
                 R 7.7 
             | 
            
                 R 12.5 
             | 
            
                 R 16 
             | 
            
                 R 12.5 
             | 
            
                 R 11 
             | 
        ||||
    Footnote to TABLE 160.4-A: 
1 Multifamily and hotel/motel domestic hot water systems with water temperature above 140°F shall use the row in Table 120.3-A for the applicable water temperature.
- Pipe insulation exposed to weather shall be protected by a cover suitable for outdoor service. The cover shall be water retardant and provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be used to provide this protection.
 - Pipe insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall include, or be protected by, a Class I or Class II vapor retarder. All penetrations and joints shall be sealed.
 - Pipe insulation buried below grade must be installed in a waterproof and non-crushable casing or sleeve.
 
        