| City | Latitude | Elevation (ft) | Longitude | Cooling | 
 | Heating | ||||||||||||
| 0.10% | 0.50% | 1.00% | 2.00% | Design Wetbulb 0.1% | Design Wetbulb 0.5% | Outdoor Daily Range | Winter Median of Extremes | Design Drybulb (0.2%) | Design Drybulb (0.6%) | HDD* | ||||||||
| DB | MCWB | DB | MCWB | DB | MCWB | DB | MCWB | |||||||||||
| Adelanto | 34.6 | 2865 | 117.4 | 105 | 67 | 101 | 65 | 100 | 64 | 97 | 62 | 70 | 68 | 39 | 14 | 24 | 27 | 1654 | 
| Adin RS | 41.2 | 4195 | 121 | 96 | 61 | 92 | 60 | 91 | 60 | 88 | 59 | 65 | 63 | 43 | -7 | -2 | 4 | 
 | 
| Agoura Hills | 34.2 | 700 | 118.8 | 103 | 70 | 96 | 68 | 94 | 68 | 90 | 66 | 73 | 71 | 29 | 27 | 31 | 34 | 
 | 
| Alameda NAS | 37.8 | 15 | 122.3 | 88 | 65 | 82 | 64 | 80 | 64 | 76 | 62 | 66 | 64 | 21 | 35 | 38 | 40 | 2507 | 
| Alamo | 37.9 | 410 | 122.9 | 102 | 69 | 97 | 68 | 96 | 68 | 92 | 66 | 72 | 70 | 30 | 23 | 28 | 31 | 
 | 
| Albany | 37.9 | 40 | 122.3 | 88 | 65 | 83 | 64 | 81 | 64 | 77 | 62 | 66 | 64 | 16 | 30 | 35 | 38 | 
 | 
| Alderpoint | 40.2 | 460 | 123.6 | 100 | 69 | 95 | 67 | 94 | 67 | 90 | 65 | 70 | 68 | 39 | 21 | 27 | 30 | 3424 | 
| Alhambra | 34 | 483 | 118.1 | 100 | 71 | 96 | 70 | 94 | 70 | 90 | 68 | 73 | 71 | 25 | 30 | 35 | 37 | 
 | 
| Aliso Viejo | 33.6 | 50 | 117.7 | 91 | 69 | 83 | 68 | 81 | 68 | 76 | 66 | 71 | 69 | 18 | 30 | 33 | 36 | 
 | 
| Almaden AFS | 37.2 | 3470 | 121.9 | 95 | 62 | 90 | 60 | 89 | 60 | 85 | 59 | 64 | 62 | 20 | 20 | 25 | 29 | 4468 | 
| Alondra Park | 33.9 | 50 | 118.3 | 91 | 69 | 86 | 68 | 85 | 68 | 81 | 66 | 71 | 69 | 17 | 35 | 40 | 42 | 
 | 
| Alpine | 32.8 | 1735 | 116.8 | 99 | 69 | 95 | 68 | 94 | 68 | 91 | 67 | 72 | 70 | 35 | 27 | 32 | 35 | 
 | 
| Alta Sierra | 35.7 | 6500 | 118.6 | 87 | 62 | 84 | 61 | 83 | 61 | 80 | 59 | 65 | 63 | 32 | -4 | 1 | 8 | 2428 | 
| Altadena | 34.2 | 1200 | 118.1 | 99 | 68 | 94 | 67 | 92 | 67 | 88 | 66 | 72 | 70 | 31 | 32 | 37 | 39 | 1920 | 
| Alturas RS | 41.5 | 4400 | 120.6 | 99 | 62 | 96 | 61 | 95 | 61 | 91 | 59 | 65 | 63 | 43 | -10 | -4 | 0 | 6895 | 
| Alum Rock | 37.4 | 70 | 121.8 | 95 | 68 | 90 | 66 | 88 | 66 | 84 | 64 | 70 | 68 | 22 | 28 | 33 | 36 | 
 | 
| American Canyon | 37.6 | 85 | 122.3 | 93 | 67 | 90 | 66 | 88 | 66 | 84 | 64 | 70 | 68 | 23 | 28 | 33 | 36 | 
 | 
| Anaheim | 33.8 | 158 | 117.9 | 99 | 69 | 92 | 68 | 90 | 68 | 85 | 67 | 73 | 71 | 26 | 32 | 37 | 39 | 
 | 
| Anderson | 40.5 | 430 | 122.3 | 107 | 71 | 103 | 70 | 101 | 70 | 97 | 68 | 72 | 70 | 30 | 26 | 31 | 34 | 
 | 
| Angwin | 38.6 | 1815 | 122.4 | 98 | 66 | 93 | 64 | 92 | 64 | 88 | 62 | 69 | 66 | 33 | 25 | 30 | 33 | 
 | 
| Antioch | 38 | 60 | 121.8 | 102 | 70 | 97 | 68 | 95 | 68 | 91 | 66 | 70 | 69 | 34 | 22 | 28 | 31 | 2627 | 
| Apple Valley | 34.5 | 2935 | 117.2 | 105 | 66 | 101 | 65 | 100 | 65 | 97 | 64 | 70 | 68 | 38 | 14 | 21 | 25 | 
 | 
| Aptos | 37 | 500 | 121.9 | 94 | 67 | 88 | 66 | 87 | 65 | 83 | 63 | 69 | 67 | 30 | 27 | 32 | 35 | 
 | 
| Arcadia | 34.2 | 475 | 118 | 100 | 69 | 96 | 68 | 95 | 68 | 91 | 67 | 73 | 71 | 30 | 31 | 36 | 38 | 
 | 
| Arcata | 41 | 218 | 124.1 | 75 | 61 | 69 | 59 | 68 | 59 | 65 | 58 | 61 | 60 | 11 | 28 | 31 | 33 | 5029 | 
| Arden | 38.5 | 80 | 121.4 | 104 | 70 | 100 | 69 | 98 | 69 | 94 | 67 | 73 | 71 | 35 | 28 | 33 | 35 | 
 | 
| Arroyo Grande | 35.1 | 105 | 120.6 | 92 | 66 | 86 | 64 | 84 | 64 | 79 | 62 | 67 | 65 | 18 | 28 | 32 | 35 | 
 | 
| Artesia | 33.8 | 50 | 118.1 | 99 | 71 | 91 | 70 | 89 | 70 | 85 | 68 | 73 | 71 | 23 | 33 | 37 | 40 | 
 | 
| Arvin | 35.2 | 445 | 118.8 | 106 | 71 | 102 | 69 | 101 | 69 | 98 | 68 | 74 | 72 | 30 | 26 | 29 | 32 | 
 | 
| Ash Mtn | 36.5 | 1708 | 118.8 | 105 | 69 | 101 | 68 | 100 | 68 | 97 | 66 | 72 | 70 | 30 | 25 | 31 | 33 | 2703 | 
| Ashland | 37.7 | 45 | 122.1 | 92 | 66 | 86 | 65 | 85 | 64 | 81 | 62 | 68 | 66 | 24 | 26 | 31 | 34 | 977 | 
| Atascadero | 35.5 | 837 | 120.7 | 94 | 66 | 89 | 67 | 88 | 67 | 84 | 65 | 70 | 68 | 42 | 25 | 29 | 32 | 
 | 
| Atherton | 37.5 | 50 | 122.2 | 90 | 66 | 84 | 64 | 82 | 64 | 78 | 62 | 68 | 66 | 27 | 23 | 29 | 33 | 
 | 
| Atwater | 37.3 | 150 | 120.6 | 102 | 72 | 99 | 70 | 98 | 69 | 94 | 67 | 74 | 72 | 38 | 24 | 30 | 34 | 
 | 
| Auberry | 37.1 | 2140 | 119.5 | 102 | 69 | 98 | 67 | 97 | 66 | 95 | 64 | 71 | 69 | 36 | 21 | 27 | 30 | 3313 | 
| Auburn | 38.9 | 1292 | 121.1 | 103 | 69 | 100 | 67 | 99 | 67 | 95 | 66 | 72 | 69 | 33 | 25 | 30 | 33 | 3089 | 
| Avalon | 33.4 | 25 | 118.3 | 83 | 64 | 75 | 62 | 73 | 62 | 69 | 60 | 68 | 66 | 11 | 37 | 41 | 44 | 2204 | 
| Avenal | 36 | 550 | 120.1 | 103 | 70 | 98 | 70 | 97 | 70 | 93 | 69 | 73 | 72 | 34 | 23 | 28 | 31 | 
 | 
| Avocado Heights | 34.2 | 550 | 118 | 101 | 69 | 97 | 68 | 95 | 68 | 91 | 68 | 74 | 72 | 30 | 28 | 32 | 35 | 741 | 
| Azusa | 34.1 | 605 | 118.2 | 101 | 70 | 97 | 69 | 95 | 69 | 91 | 68 | 74 | 72 | 36 | 31 | 36 | 38 | 
 | 
| Baker | 35.3 | 940 | 116.1 | 115 | 73 | 112 | 72 | 111 | 72 | 108 | 70 | 77 | 75 | 29 | 23 | 28 | 31 | 
 | 
| Bakersfield AP | 35.4 | 475 | 119.1 | 106 | 71 | 102 | 70 | 101 | 70 | 98 | 68 | 74 | 72 | 34 | 26 | 31 | 35 | 2185 | 
| Balch PH | 36.9 | 1720 | 116.0 | 100 | 67 | 97 | 66 | 96 | 66 | 93 | 64 | 71 | 69 | 26 | 26 | 31 | 34 | 
 | 
| Baldwin Park | 34 | 394 | 118 | 100 | 69 | 96 | 69 | 94 | 69 | 90 | 68 | 73 | 72 | 32 | 31 | 36 | 38 | 
 | 
| Banning | 33.9 | 2349 | 116.9 | 104 | 69 | 100 | 68 | 99 | 68 | 96 | 67 | 73 | 71 | 34 | 20 | 26 | 30 | 
 | 
| Barrett Dam | 32.7 | 1623 | 116.7 | 103 | 69 | 97 | 68 | 96 | 68 | 92 | 67 | 73 | 71 | 35 | 22 | 26 | 28 | 2656 | 
| Barstow | 34.9 | 2162 | 117 | 107 | 69 | 104 | 69 | 103 | 69 | 100 | 67 | 74 | 72 | 35 | 16 | 23 | 27 | 2580 | 
| Baywood-Los Osos | 35.3 | 100 | 
 | 88 | 65 | 82 | 64 | 80 | 64 | 76 | 62 | 67 | 65 | 14 | 31 | 36 | 38 | 
 | 
| Beale AFB | 39.1 | 113 | 121.4 | 105 | 71 | 102 | 70 | 101 | 70 | 97 | 68 | 74 | 72 | 34 | 25 | 28 | 30 | 2835 | 
| Beaumont | 33.9 | 2605 | 117 | 103 | 68 | 99 | 67 | 98 | 67 | 95 | 66 | 72 | 70 | 38 | 22 | 27 | 30 | 2628 | 
| Bell | 33.9 | 143 | 118.2 | 97 | 70 | 91 | 69 | 89 | 69 | 85 | 67 | 72 | 70 | 22 | 33 | 38 | 41 | 
 | 
| Bell Gardens | 33.9 | 160 | 118.2 | 97 | 70 | 91 | 69 | 87 | 67 | 85 | 67 | 72 | 70 | 22 | 32 | 37 | 40 | 
 | 
| Bellflower | 33.8 | 73 | 118.1 | 98 | 70 | 91 | 69 | 89 | 69 | 85 | 67 | 72 | 70 | 21 | 32 | 37 | 40 | 
 | 
| Belmont | 37.5 | 33 | 122.3 | 90 | 66 | 84 | 64 | 82 | 64 | 78 | 62 | 68 | 66 | 24 | 29 | 34 | 36 | 
 | 
| Ben Lomond | 37.1 | 450 | 122.1 | 92 | 67 | 85 | 66 | 83 | 65 | 79 | 63 | 69 | 67 | 30 | 25 | 30 | 33 | 
 | 
| Benicia | 38.1 | 55 | 122.1 | 99 | 69 | 93 | 67 | 91 | 67 | 87 | 65 | 70 | 68 | 30 | 28 | 33 | 36 | 
 | 
| Berkeley | 37.9 | 345 | 122.3 | 90 | 64 | 83 | 63 | 81 | 63 | 76 | 61 | 66 | 64 | 16 | 33 | 37 | 40 | 2950 | 
| Berryessa Lake | 38.6 | 480 | 122.1 | 102 | 70 | 98 | 69 | 96 | 69 | 92 | 67 | 72 | 70 | 35 | 26 | 31 | 34 | 
 | 
| Beverly Hills | 34.1 | 268 | 118.2 | 94 | 69 | 88 | 68 | 87 | 68 | 83 | 66 | 71 | 69 | 20 | 39 | 43 | 46 | 
 | 
| Big Bar RS | 40.8 | 1260 | 121.8 | 102 | 68 | 98 | 67 | 97 | 67 | 93 | 65 | 70 | 68 | 46 | 19 | 25 | 28 | 
 | 
| Big Bear Lake | 34.2 | 6745 | 116.9 | 87 | 59 | 83 | 58 | 82 | 58 | 79 | 56 | 64 | 62 | 32 | -3 | 3 | 7 | 6850 | 
| Bishop AP | 37.4 | 4108 | 118.4 | 103 | 61 | 100 | 60 | 99 | 60 | 97 | 58 | 65 | 63 | 40 | 5 | 12 | 16 | 4313 | 
| Blackhawk | 37.7 | 10 | 121.9 | 88 | 65 | 82 | 64 | 80 | 64 | 76 | 62 | 66 | 64 | 21 | 35 | 38 | 40 | 977 | 
| Blackwells Corner | 35.6 | 644 | 119.9 | 99 | 68 | 94 | 66 | 93 | 66 | 89 | 65 | 71 | 69 | 31 | 23 | 28 | 32 | 
 | 
| Bloomington | 34 | 980 | 117.4 | 106 | 71 | 102 | 70 | 101 | 70 | 98 | 69 | 75 | 73 | 34 | 30 | 35 | 38 | 
 | 
| Blue Canyon AP | 39.3 | 5280 | 120.7 | 88 | 60 | 85 | 59 | 84 | 59 | 81 | 57 | 64 | 62 | 20 | 13 | 20 | 24 | 5704 | 
| Blythe AP | 33.6 | 395 | 114.7 | 115 | 74 | 112 | 73 | 111 | 73 | 108 | 71 | 80 | 78 | 27 | 28 | 33 | 36 | 1219 | 
| Blythe CO | 33.6 | 268 | 114.6 | 115 | 74 | 112 | 73 | 111 | 73 | 108 | 71 | 80 | 78 | 27 | 24 | 29 | 32 | 1312 | 
| Boca | 39.4 | 5575 | 120.1 | 92 | 58 | 89 | 57 | 88 | 57 | 84 | 55 | 62 | 60 | 46 | -18 | -13 | -10 | 8340 | 
| Bodie | 38.2 | 8370 | 119 | 83 | 50 | 80 | 49 | 79 | 49 | 76 | 48 | 55 | 53 | 42 | -21 | -16 | -13 | 
 | 
| Bonadella Ranchos – Madera Rancho | 36.8 | 270 | 119.9 | 105 | 72 | 101 | 70 | 100 | 70 | 96 | 68 | 74 | 72 | 40 | 
 | 29 | 32 | 1273 | 
| Bonita | 32.7 | 105 | 117 | 91 | 69 | 82 | 67 | 81 | 66 | 78 | 64 | 70 | 68 | 20 | 28 | 32 | 44 | 1864 | 
| Boron AFS | 35.1 | 3015 | 117.6 | 106 | 70 | 103 | 69 | 102 | 69 | 98 | 68 | 73 | 71 | 35 | 18 | 23 | 26 | 3000 | 
| Borrego Desert PK | 33.2 | 805 | 116.4 | 112 | 76 | 107 | 74 | 105 | 74 | 101 | 72 | 79 | 77 | 36 | 25 | 30 | 33 | 
 | 
| Bostonia | 32.8 | 600 | 116.9 | 96 | 70 | 91 | 69 | 88 | 69 | 81 | 67 | 72 | 70 | 30 | 29 | 34 | 36 | 
 | 
| Boulder Creek | 37.2 | 493 | 122.1 | 92 | 67 | 85 | 65 | 83 | 65 | 79 | 63 | 69 | 67 | 30 | 25 | 30 | 33 | 1120 | 
| Bowman Dam | 39.4 | 5347 | 120.7 | 89 | 59 | 86 | 57 | 85 | 57 | 82 | 55 | 63 | 60 | 26 | 9 | 17 | 22 | 5964 | 
| Boyes Hot Sprgs | 38.2 | 300 | 122.5 | 100 | 70 | 95 | 69 | 93 | 69 | 89 | 67 | 72 | 70 | 40 | 22 | 28 | 31 | 1289 | 
| Brannan Island | 38.1 | 30 | 121.7 | 100 | 69 | 95 | 68 | 93 | 68 | 89 | 67 | 72 | 70 | 10 | 24 | 28 | 31 | 
 | 
| Brawley 2 SW | 33 | -100 | 115.6 | 113 | 74 | 110 | 73 | 109 | 73 | 105 | 73 | 81 | 79 | 32 | 25 | 30 | 33 | 1204 | 
| Brea Dam | 33.9 | 275 | 117.9 | 100 | 69 | 94 | 68 | 92 | 68 | 86 | 66 | 73 | 71 | 29 | 30 | 34 | 37 | 
 | 
| Brentwood | 37.9 | 71 | 121.7 | 102 | 70 | 97 | 68 | 95 | 67 | 89 | 65 | 71 | 68 | 34 | 27 | 32 | 35 | 
 | 
| Bridgeport | 38.2 | 6470 | 119.2 | 89 | 56 | 86 | 54 | 85 | 54 | 82 | 53 | 60 | 57 | 41 | -20 | -15 | -12 | 
 | 
| Broderick-Bryte | 38.6 | 20 | 121.5 | 104 | 71 | 100 | 69 | 98 | 69 | 94 | 67 | 72 | 71 | 36 | 25 | 31 | 35 | 
 | 
| Brooks Ranch | 38.8 | 294 | 122.2 | 104 | 71 | 99 | 70 | 97 | 70 | 93 | 68 | 73 | 71 | 35 | 19 | 25 | 28 | 2968 | 
| Buena Park | 33.9 | 75 | 118 | 98 | 69 | 92 | 68 | 90 | 68 | 85 | 67 | 72 | 70 | 25 | 31 | 35 | 38 | 
 | 
| Burbank AP | 34.2 | 699 | 118.4 | 101 | 70 | 96 | 68 | 94 | 68 | 90 | 67 | 72 | 70 | 28 | 29 | 34 | 36 | 1701 | 
| Burbank Vly Pump | 34.2 | 655 | 118.4 | 101 | 69 | 96 | 68 | 94 | 68 | 90 | 66 | 72 | 70 | 28 | 29 | 34 | 36 | 1678 | 
| Burlingame | 37.6 | 10 | 122.4 | 88 | 67 | 82 | 64 | 80 | 64 | 76 | 63 | 68 | 65 | 20 | 30 | 35 | 37 | 
 | 
| Burney | 40.9 | 3127 | 121.7 | 95 | 64 | 92 | 63 | 91 | 63 | 88 | 61 | 67 | 65 | 42 | 0 | 5 | 12 | 6404 | 
| Butler Valley (Korbel) | 40.7 | 420 | 123.9 | 91 | 66 | 86 | 64 | 85 | 64 | 81 | 62 | 67 | 65 | 22 | 20 | 26 | 29 | 
 | 
| Buttonwillow | 35.4 | 269 | 119.5 | 103 | 71 | 99 | 70 | 98 | 70 | 95 | 68 | 74 | 72 | 36 | 20 | 26 | 29 | 2621 | 
| Cabrillo NM | 32.7 | 410 | 117.2 | 89 | 69 | 84 | 68 | 83 | 68 | 80 | 67 | 71 | 69 | 12 | 39 | 43 | 45 | 
 | 
| Cachuma Lake | 34.6 | 781 | 120 | 97 | 69 | 92 | 67 | 91 | 67 | 87 | 65 | 70 | 68 | 19 | 26 | 31 | 34 | 
 | 
| Calabasas | 34.2 | 1100 | 118.6 | 102 | 71 | 98 | 70 | 97 | 70 | 93 | 69 | 73 | 71 | 26 | 26 | 30 | 33 | 2348 | 
| Calaveras Big Trees | 38.3 | 4696 | 120.3 | 92 | 61 | 88 | 60 | 87 | 60 | 84 | 58 | 64 | 62 | 33 | 11 | 18 | 23 | 5848 | 
| Calexico | 32.7 | 12 | 115.5 | 114 | 74 | 110 | 73 | 109 | 73 | 106 | 71 | 81 | 79 | 28 | 26 | 31 | 34 | 
 | 
| California City | 35.1 | 2400 | 118 | 107 | 69 | 104 | 68 | 103 | 68 | 99 | 66 | 72 | 70 | 33 | 10 | 17 | 22 | 2572 | 
| Callahan | 41.3 | 3185 | 122.8 | 97 | 63 | 93 | 62 | 92 | 62 | 88 | 60 | 66 | 64 | 35 | 7 | 15 | 20 | 
 | 
| Calwa | 36.8 | 330 | 119.8 | 105 | 73 | 101 | 71 | 100 | 70 | 97 | 68 | 75 | 73 | 34 | 23 | 27 | 29 | 
 | 
| Camarillo | 34.2 | 147 | 119.2 | 91 | 69 | 84 | 68 | 82 | 68 | 78 | 67 | 71 | 69 | 22 | 28 | 32 | 35 | 
 | 
| Cambria AFS | 35.5 | 690 | 121.1 | 78 | 62 | 72 | 61 | 70 | 61 | 66 | 59 | 64 | 62 | 16 | 30 | 35 | 38 | 3646 | 
| Cameron Park | 38.6 | 1800 | 121 | 101 | 67 | 98 | 66 | 97 | 66 | 93 | 65 | 70 | 68 | 42 | 20 | 26 | 29 | 2235 | 
| Camp Pardee | 38.2 | 658 | 120.9 | 106 | 71 | 103 | 70 | 102 | 70 | 98 | 69 | 74 | 72 | 36 | 27 | 32 | 35 | 2812 | 
| Camp Pendleton | 33.4 | 50 | 117.4 | 88 | 69 | 85 | 68 | 84 | 68 | 80 | 67 | 71 | 69 | 12 | 34 | 38 | 40 | 
 | 
| Camp Roberts | 35.8 | 765 | 120.8 | 106 | 72 | 101 | 71 | 99 | 71 | 95 | 69 | 74 | 72 | 45 | 16 | 24 | 27 | 2890 | 
| Campbell | 37.3 | 195 | 121.8 | 93 | 69 | 88 | 66 | 87 | 66 | 83 | 65 | 71 | 68 | 30 | 28 | 33 | 36 | 
 | 
| Campo | 32.6 | 2630 | 116.5 | 101 | 67 | 95 | 66 | 94 | 66 | 90 | 66 | 71 | 69 | 41 | 16 | 23 | 27 | 3303 | 
| Canoga Park | 34.2 | 790 | 118.6 | 104 | 71 | 99 | 70 | 97 | 70 | 93 | 69 | 74 | 72 | 38 | 25 | 30 | 33 | 1884 | 
| Cantil | 35.3 | 2010 | 118 | 111 | 71 | 107 | 71 | 106 | 71 | 103 | 70 | 74 | 73 | 32 | 12 | 19 | 24 | 
 | 
| Canyon Dam | 40.1 | 4555 | 121.1 | 93 | 60 | 90 | 59 | 89 | 59 | 85 | 57 | 64 | 62 | 39 | 1 | 6 | 13 | 6834 | 
| Canyon Lake | 33.8 | 1500 | 117.3 | 105 | 70 | 101 | 69 | 100 | 69 | 97 | 68 | 74 | 72 | 39 | 22 | 27 | 30 | 
 | 
| Capitola | 37 | 64 | 122 | 94 | 67 | 88 | 66 | 86 | 65 | 81 | 63 | 69 | 67 | 24 | 27 | 32 | 35 | 
 | 
| Cardiff-by-the-Sea | 33 | 80 | 117.3 | 87 | 68 | 83 | 67 | 81 | 67 | 77 | 65 | 70 | 68 | 12 | 35 | 39 | 41 | 
 | 
| Carlsbad | 33.2 | 44 | 117.4 | 87 | 68 | 83 | 67 | 81 | 67 | 77 | 65 | 70 | 68 | 10 | 34 | 38 | 40 | 
 | 
| Carmel Valley | 36.5 | 425 | 121.7 | 94 | 68 | 88 | 66 | 86 | 66 | 80 | 65 | 69 | 67 | 20 | 25 | 30 | 33 | 
 | 
| Carmel-by-the-Sea | 36.5 | 20 | 121.9 | 87 | 65 | 78 | 62 | 76 | 62 | 71 | 61 | 66 | 63 | 20 | 30 | 35 | 38 | 968 | 
| Carmichael | 38.6 | 100 | 121.5 | 104 | 70 | 100 | 69 | 98 | 69 | 94 | 68 | 73 | 71 | 35 | 25 | 35 | 37 | 1290 | 
| Carpinteria | 34.4 | 385 | 119.5 | 90 | 69 | 83 | 67 | 81 | 67 | 77 | 65 | 70 | 68 | 15 | 30 | 34 | 37 | 
 | 
| Carson | 33.8 | 60 | 118.3 | 96 | 69 | 88 | 68 | 86 | 68 | 82 | 66 | 71 | 69 | 19 | 33 | 38 | 40 | 
 | 
| Casa de Oro-Mount Helix | 32.7 | 530 | 117.0 | 96 | 71 | 88 | 69 | 87 | 69 | 84 | 67 | 72 | 70 | 19 | 34 | 38 | 41 | 404 | 
| Castle AFB | 37.4 | 188 | 120.6 | 105 | 71 | 101 | 70 | 100 | 70 | 96 | 69 | 73 | 71 | 33 | 24 | 28 | 31 | 2590 | 
| Castro Valley | 37.6 | 177 | 122.2 | 93 | 67 | 87 | 67 | 85 | 67 | 80 | 65 | 69 | 68 | 25 | 24 | 29 | 32 | 
 | 
| Castroville | 36.8 | 20 | 121.8 | 86 | 66 | 77 | 63 | 75 | 63 | 70 | 61 | 67 | 64 | 18 | 32 | 37 | 40 | 1151 | 
| Cathedral City | 33.8 | 400 | 116.5 | 117 | 74 | 113 | 73 | 112 | 73 | 109 | 72 | 79 | 78 | 33 | 26 | 31 | 34 | 374 | 
| Catheys Valley | 37.4 | 1000 | 120.1 | 102 | 69 | 99 | 68 | 98 | 68 | 94 | 67 | 72 | 70 | 38 | 21 | 27 | 30 | 
 | 
| Cecilville | 41.1 | 3000 | 123.1 | 95 | 63 | 89 | 62 | 88 | 61 | 84 | 59 | 65 | 63 | 44 | 13 | 20 | 24 | 
 | 
| Cedarville | 41.5 | 4670 | 120.2 | 97 | 61 | 94 | 60 | 93 | 60 | 89 | 58 | 65 | 63 | 35 | 1 | 6 | 13 | 6304 | 
| Centerville PH | 39.8 | 522 | 121.7 | 105 | 70 | 100 | 68 | 99 | 68 | 96 | 67 | 72 | 70 | 40 | 25 | 30 | 33 | 2895 | 
| Ceres | 37.6 | 90 | 121 | 101 | 72 | 96 | 70 | 94 | 69 | 90 | 67 | 74 | 72 | 36 | 24 | 30 | 34 | 
 | 
| Cerritos | 33.9 | 34 | 118.1 | 99 | 71 | 92 | 69 | 90 | 69 | 85 | 68 | 73 | 71 | 23 | 33 | 38 | 40 | 
 | 
| Charter Oak | 34.1 | 600 | 117.9 | 101 | 70 | 97 | 69 | 95 | 69 | 91 | 68 | 74 | 72 | 34 | 29 | 34 | 36 | 
 | 
| Chatsworth | 34.2 | 964 | 118.6 | 98 | 69 | 93 | 68 | 91 | 68 | 87 | 66 | 72 | 70 | 38 | 26 | 31 | 34 | 664 | 
| Cherry Valley Dam | 38 | 4765 | 119.9 | 96 | 62 | 92 | 61 | 91 | 61 | 88 | 59 | 65 | 63 | 32 | 9 | 16 | 21 | 
 | 
| Cherryland | 37.5 | 100 | 122.1 | 93 | 67 | 86 | 66 | 84 | 66 | 79 | 64 | 69 | 67 | 24 | 26 | 31 | 37 | 
 | 
| Chester | 40.3 | 4525 | 121.2 | 94 | 62 | 91 | 61 | 90 | 61 | 86 | 59 | 65 | 63 | 33 | -3 | 2 | 8 | 
 | 
| Chico Exp Sta | 39.7 | 205 | 121.8 | 105 | 70 | 102 | 69 | 100 | 69 | 96 | 68 | 72 | 71 | 37 | 22 | 27 | 30 | 2878 | 
| China Lake | 35.7 | 2220 | 117.7 | 112 | 70 | 108 | 68 | 107 | 68 | 104 | 68 | 74 | 72 | 33 | 15 | 22 | 25 | 2560 | 
| Chino | 34 | 714 | 117.7 | 104 | 70 | 100 | 69 | 98 | 69 | 94 | 68 | 74 | 72 | 35 | 27 | 32 | 35 | 
 | 
| Chino Hills | 34.1 | 800 | 117.7 | 104 | 70 | 100 | 69 | 98 | 69 | 94 | 68 | 74 | 72 | 35 | 27 | 32 | 35 | 800 | 
| Chowchilla | 37 | 200 | 120.3 | 104 | 72 | 101 | 70 | 100 | 70 | 96 | 68 | 74 | 72 | 38 | 22 | 28 | 31 | 1250 | 
| Chula Vista | 32.6 | 9 | 117.1 | 90 | 70 | 84 | 68 | 83 | 68 | 79 | 66 | 71 | 69 | 9 | 33 | 38 | 40 | 2072 | 
| Citrus Heights | 38.7 | 138 | 121.5 | 104 | 71 | 100 | 70 | 98 | 70 | 94 | 68 | 74 | 72 | 36 | 24 | 26 | 29 | 
 | 
| Claremont | 34.1 | 1201 | 117.8 | 101 | 69 | 97 | 68 | 95 | 68 | 91 | 66 | 73 | 71 | 34 | 29 | 34 | 36 | 2049 | 
| Clarksburg | 38.4 | 14 | 121.5 | 102 | 70 | 97 | 69 | 95 | 69 | 91 | 67 | 72 | 70 | 35 | 24 | 29 | 32 | 2971 | 
| Clayton | 38 | 60 | 121.9 | 102 | 70 | 97 | 68 | 95 | 67 | 89 | 65 | 71 | 68 | 34 | 27 | 32 | 35 | 
 | 
| Clearlake Highlands | 39 | 1360 | 122.7 | 101 | 69 | 97 | 68 | 95 | 67 | 89 | 65 | 71 | 69 | 36 | 15 | 22 | 26 | 
 | 
| Cloverdale | 38.8 | 320 | 123 | 102 | 70 | 97 | 69 | 95 | 68 | 89 | 66 | 72 | 70 | 37 | 26 | 31 | 34 | 2763 | 
| Clovis | 36.8 | 404 | 119.7 | 105 | 72 | 102 | 70 | 101 | 70 | 98 | 68 | 74 | 72 | 36 | 22 | 28 | 32 | 
 | 
| Coachella | 33.7 | -76 | 116.2 | 114 | 74 | 110 | 73 | 109 | 73 | 106 | 73 | 80 | 79 | 28 | 25 | 30 | 34 | 
 | 
| Coalinga | 36.2 | 671 | 120.4 | 103 | 70 | 98 | 70 | 97 | 70 | 93 | 69 | 73 | 72 | 34 | 23 | 28 | 31 | 2592 | 
| Colfax | 39.1 | 2418 | 121 | 100 | 66 | 97 | 65 | 96 | 65 | 92 | 63 | 69 | 67 | 29 | 22 | 28 | 31 | 3424 | 
| Colton | 34.1 | 978 | 117.3 | 105 | 70 | 102 | 68 | 101 | 68 | 97 | 67 | 74 | 72 | 35 | 28 | 33 | 36 | 
 | 
| Colusa | 39.2 | 60 | 122 | 103 | 72 | 100 | 70 | 98 | 70 | 94 | 68 | 74 | 71 | 36 | 23 | 29 | 31 | 2793 | 
| Commerce | 33.9 | 175 | 118.2 | 98 | 69 | 92 | 68 | 90 | 68 | 86 | 67 | 72 | 70 | 23 | 33 | 37 | 39 | 
 | 
| Compton | 33.9 | 71 | 118.2 | 97 | 69 | 90 | 68 | 88 | 68 | 83 | 67 | 72 | 70 | 21 | 33 | 37 | 39 | 1606 | 
| Concord | 38 | 195 | 112 | 102 | 70 | 97 | 68 | 95 | 67 | 89 | 65 | 71 | 68 | 34 | 27 | 32 | 35 | 3035 | 
| Corcoran | 36.1 | 200 | 119.7 | 106 | 72 | 102 | 71 | 101 | 71 | 98 | 70 | 74 | 73 | 36 | 22 | 28 | 31 | 2666 | 
| Corning | 39.9 | 487 | 122.2 | 106 | 71 | 103 | 70 | 102 | 69 | 98 | 67 | 73 | 71 | 33 | 23 | 28 | 31 | 1330 | 
| Corona | 33.9 | 710 | 117.6 | 104 | 70 | 100 | 69 | 98 | 69 | 92 | 67 | 74 | 72 | 35 | 26 | 31 | 34 | 1794 | 
| Coronado | 32.7 | 20 | 117.2 | 89 | 69 | 82 | 67 | 80 | 67 | 76 | 65 | 70 | 68 | 10 | 36 | 39 | 41 | 1500 | 
| Corte Madera | 37.9 | 55 | 122.5 | 97 | 68 | 91 | 66 | 89 | 66 | 84 | 64 | 69 | 68 | 34 | 28 | 33 | 35 | 
 | 
| Costa Mesa | 33.7 | 100 | 117.9 | 88 | 68 | 81 | 66 | 79 | 66 | 73 | 65 | 70 | 68 | 16 | 31 | 36 | 38 | 1482 | 
| Cotati | 38.3 | 100 | 122.7 | 99 | 69 | 94 | 68 | 93 | 68 | 89 | 66 | 71 | 69 | 32 | 24 | 28 | 30 | 1205 | 
| Country Club | 37.8 | 600 | 121.3 | 102 | 69 | 97 | 68 | 96 | 68 | 92 | 66 | 72 | 70 | 30 | 68 | 28 | 31 | 977 | 
| Covelo | 39.8 | 1385 | 123.3 | 99 | 67 | 93 | 65 | 91 | 65 | 87 | 63 | 69 | 67 | 43 | 15 | 22 | 26 | 4179 | 
| Covina | 34.1 | 575 | 117.9 | 101 | 70 | 97 | 69 | 95 | 69 | 91 | 68 | 74 | 72 | 34 | 29 | 34 | 36 | 
 | 
| Crescent City | 41.8 | 40 | 124.2 | 75 | 61 | 69 | 59 | 68 | 59 | 65 | 58 | 61 | 60 | 18 | 28 | 33 | 36 | 4445 | 
| Crestline | 34.2 | 4900 | 117.3 | 90 | 62 | 86 | 61 | 85 | 61 | 81 | 59 | 66 | 64 | 26 | 13 | 20 | 24 | 3200 | 
| Crockett | 38 | 9 | 122.2 | 96 | 68 | 90 | 66 | 89 | 66 | 85 | 64 | 70 | 67 | 23 | 28 | 33 | 36 | 
 | 
| Crows Landing | 37.4 | 140 | 121.1 | 101 | 70 | 96 | 68 | 94 | 68 | 89 | 66 | 72 | 70 | 33 | 23 | 28 | 31 | 2767 | 
| Cucamonga | 34.1 | 1450 | 117.6 | 103 | 69 | 99 | 68 | 97 | 67 | 93 | 65 | 73 | 71 | 31 | 29 | 34 | 36 | 
 | 
| Cudahy | 33.9 | 130 | 118.2 | 98 | 70 | 91 | 69 | 89 | 69 | 85 | 67 | 72 | 70 | 21 | 33 | 37 | 39 | 
 | 
| Culver City | 34 | 106 | 118.4 | 96 | 70 | 88 | 69 | 87 | 69 | 83 | 67 | 72 | 70 | 18 | 35 | 40 | 42 | 1515 | 
| Cupertino | 37.3 | 70 | 122 | 96 | 68 | 88 | 67 | 86 | 66 | 80 | 64 | 70 | 68 | 30 | 28 | 33 | 36 | 
 | 
| Cuyama | 34.9 | 2255 | 116.6 | 99 | 68 | 96 | 67 | 94 | 67 | 89 | 66 | 72 | 70 | 42 | 13 | 20 | 24 | 
 | 
| Cuyamaca | 33 | 4650 | 116.6 | 92 | 64 | 85 | 62 | 84 | 61 | 81 | 59 | 67 | 65 | 29 | 11 | 18 | 23 | 4848 | 
| Cypress | 33.8 | 75 | 118 | 98 | 70 | 92 | 69 | 90 | 69 | 85 | 67 | 72 | 70 | 24 | 31 | 35 | 38 | 
 | 
| Daggett AP | 34.9 | 1915 | 116.8 | 109 | 68 | 106 | 68 | 105 | 68 | 102 | 66 | 73 | 72 | 33 | 21 | 26 | 29 | 2203 | 
| Daly City | 37.6 | 410 | 122.5 | 84 | 65 | 78 | 62 | 77 | 62 | 73 | 61 | 66 | 63 | 16 | 34 | 37 | 39 | 
 | 
| Dana Point | 33.5 | 100 | 117.7 | 91 | 69 | 84 | 68 | 82 | 68 | 78 | 66 | 71 | 69 | 13 | 30 | 33 | 36 | 600 | 
| Danville | 37.8 | 368 | 122 | 102 | 69 | 97 | 68 | 96 | 68 | 92 | 66 | 72 | 70 | 30 | 23 | 28 | 31 | 977 | 
| Davis | 38.5 | 60 | 121.8 | 103 | 72 | 99 | 70 | 97 | 70 | 93 | 68 | 74 | 71 | 41 | 24 | 30 | 34 | 2844 | 
| De Sabla | 39.9 | 2713 | 121.6 | 97 | 66 | 94 | 64 | 92 | 64 | 88 | 62 | 68 | 66 | 35 | 18 | 24 | 27 | 4237 | 
| Death Valley | 36.5 | -194 | 116.9 | 121 | 77 | 118 | 76 | 117 | 76 | 114 | 74 | 81 | 79 | 28 | 27 | 33 | 37 | 1147 | 
| Deep Springs Clg | 37.5 | 5225 | 118 | 98 | 60 | 95 | 59 | 94 | 59 | 92 | 58 | 64 | 62 | 35 | -3 | 2 | 8 | 
 | 
| Deer Creek PH | 39.3 | 4455 | 120.9 | 93 | 61 | 91 | 60 | 90 | 60 | 87 | 58 | 65 | 63 | 39 | 10 | 17 | 22 | 5863 | 
| Del Aire | 34 | 100 | 118.4 | 91 | 69 | 84 | 67 | 83 | 67 | 79 | 66 | 71 | 69 | 15 | 37 | 40 | 42 | 383 | 
| Delano | 35.8 | 323 | 119.3 | 106 | 71 | 102 | 70 | 101 | 70 | 98 | 69 | 74 | 72 | 36 | 22 | 25 | 28 | 
 | 
| Denair | 37.6 | 137 | 120.8 | 100 | 70 | 95 | 69 | 93 | 69 | 89 | 67 | 72 | 70 | 38 | 22 | 28 | 31 | 2974 | 
| Desert Hot Springs | 34 | 1060 | 116.5 | 115 | 73 | 111 | 72 | 110 | 72 | 107 | 71 | 78 | 77 | 35 | 24 | 29 | 32 | 400 | 
| Diamond Bar | 34 | 880 | 117.8 | 101 | 69 | 97 | 68 | 96 | 68 | 92 | 66 | 73 | 71 | 33 | 28 | 33 | 35 | 
 | 
| Dinuba | 36.5 | 340 | 119.4 | 104 | 73 | 101 | 70 | 100 | 70 | 96 | 69 | 75 | 73 | 36 | 24 | 30 | 34 | 
 | 
| Discovery Bay | 38.1 | 10 | 121.6 | 102 | 70 | 97 | 68 | 95 | 67 | 89 | 65 | 71 | 68 | 34 | 27 | 32 | 35 | 
 | 
| Dixon | 38.4 | 100 | 121.9 | 104 | 72 | 99 | 70 | 97 | 70 | 93 | 68 | 74 | 71 | 36 | 24 | 30 | 33 | 2826 | 
| Dobbins | 39.4 | 1640 | 121.2 | 104 | 70 | 101 | 68 | 100 | 68 | 96 | 67 | 72 | 70 | 31 | 24 | 29 | 32 | 
 | 
| Donner Mem Stt Pk | 39.3 | 5937 | 120.3 | 85 | 56 | 82 | 56 | 81 | 56 | 77 | 54 | 60 | 58 | 40 | -3 | 3 | 6 | 
 | 
| Donner Summit | 39.4 | 7239 | 120.3 | 80 | 53 | 77 | 53 | 76 | 52 | 72 | 50 | 57 | 55 | 40 | -8 | -1 | 3 | 8290 | 
| Downey | 33.9 | 110 | 118 | 98 | 71 | 90 | 70 | 88 | 70 | 84 | 68 | 73 | 71 | 21 | 32 | 37 | 39 | 
 | 
| Downieville RS | 39.6 | 2895 | 120.8 | 98 | 64 | 95 | 63 | 94 | 63 | 90 | 61 | 68 | 66 | 42 | 13 | 20 | 24 | 
 | 
| Doyle | 40 | 4390 | 120.1 | 96 | 63 | 93 | 62 | 92 | 61 | 88 | 59 | 66 | 64 | 42 | 0 | 5 | 12 | 
 | 
| Dry Canyon Res | 34.5 | 1455 | 118.5 | 105 | 71 | 100 | 69 | 99 | 69 | 96 | 68 | 74 | 72 | 32 | 24 | 29 | 32 | 
 | 
| Duarte | 34.1 | 500 | 118 | 100 | 69 | 96 | 68 | 94 | 68 | 90 | 67 | 73 | 71 | 33 | 31 | 36 | 38 | 
 | 
| Dublin | 37.7 | 200 | 121.5 | 99 | 69 | 93 | 67 | 91 | 67 | 86 | 65 | 70 | 68 | 35 | 24 | 29 | 32 | 
 | 
| Dudleys | 37.7 | 3000 | 120.1 | 97 | 65 | 94 | 64 | 93 | 64 | 90 | 62 | 68 | 66 | 44 | 10 | 17 | 22 | 4959 | 
| Duttons Landing | 38.2 | 20 | 122.3 | 96 | 68 | 91 | 66 | 89 | 66 | 84 | 64 | 70 | 68 | 31 | 26 | 31 | 34 | 
 | 
| Eagle Mtn | 33.8 | 973 | 115.5 | 113 | 72 | 110 | 71 | 109 | 71 | 105 | 69 | 77 | 75 | 24 | 32 | 37 | 39 | 1138 | 
| Earlimart | 35.8 | 283 | 119.3 | 106 | 71 | 102 | 70 | 101 | 70 | 98 | 69 | 74 | 72 | 36 | 23 | 26 | 29 | 1100 | 
| East Compton | 34 | 71 | 118.2 | 97 | 69 | 90 | 68 | 88 | 68 | 83 | 67 | 72 | 70 | 21 | 33 | 37 | 39 | 436 | 
| East Hemet | 33.7 | 1655 | 116.9 | 109 | 70 | 104 | 69 | 103 | 69 | 101 | 67 | 74 | 72 | 40 | 20 | 25 | 28 | 
 | 
| East La Mirada | 33.9 | 115 | 118.0 | 99 | 70 | 91 | 69 | 89 | 69 | 85 | 68 | 73 | 71 | 26 | 31 | 36 | 38 | 
 | 
| East Los Angeles | 34 | 250 | 118.3 | 99 | 69 | 92 | 68 | 90 | 68 | 86 | 67 | 72 | 70 | 21 | 38 | 41 | 43 | 
 | 
| East Palo Alto | 37.5 | 25 | 122.1 | 93 | 66 | 85 | 64 | 83 | 64 | 77 | 62 | 68 | 66 | 25 | 26 | 31 | 34 | 1103 | 
| East Park Res | 39.4 | 1205 | 122.5 | 101 | 69 | 97 | 68 | 96 | 68 | 92 | 66 | 71 | 69 | 38 | 19 | 25 | 28 | 3455 | 
| East Pasadena | 34.2 | 864 | 118.1 | 99 | 69 | 94 | 68 | 92 | 68 | 88 | 67 | 73 | 71 | 30 | 32 | 37 | 40 | 452 | 
| East Porterville | 36.1 | 393 | 119.0 | 106 | 71 | 102 | 70 | 101 | 70 | 97 | 69 | 74 | 72 | 36 | 25 | 30 | 33 | 1129 | 
| East San Gabriel | 34.1 | 450 | 118.1 | 99 | 70 | 94 | 69 | 92 | 69 | 88 | 68 | 73 | 71 | 30 | 30 | 35 | 37 | 431 | 
| Edwards AFB | 34.9 | 2316 | 117.9 | 107 | 69 | 104 | 68 | 103 | 68 | 99 | 66 | 72 | 70 | 35 | 10 | 17 | 22 | 3123 | 
| El Cajon | 32.7 | 525 | 117 | 96 | 70 | 91 | 69 | 90 | 69 | 87 | 67 | 72 | 70 | 30 | 29 | 34 | 36 | 
 | 
| El Capitan Dam | 32.9 | 600 | 116.8 | 105 | 71 | 98 | 70 | 97 | 70 | 93 | 68 | 74 | 72 | 35 | 29 | 34 | 36 | 1533 | 
| El Centro | 32.8 | -30 | 115.6 | 115 | 74 | 111 | 73 | 110 | 73 | 107 | 73 | 81 | 79 | 34 | 26 | 35 | 38 | 1212 | 
| El Cerrito | 37.8 | 70 | 122.3 | 91 | 66 | 84 | 64 | 81 | 64 | 75 | 62 | 68 | 65 | 17 | 30 | 35 | 38 | 
 | 
| El Dorado Hills | 38.6 | 673 | 121.1 | 103 | 70 | 100 | 69 | 98 | 69 | 94 | 67 | 72 | 71 | 36 | 24 | 30 | 34 | 
 | 
| El Mirage | 34.6 | 2910 | 117.6 | 105 | 69 | 101 | 68 | 100 | 68 | 97 | 66 | 72 | 70 | 31 | 9 | 16 | 21 | 
 | 
| El Monte | 34.1 | 271 | 118 | 101 | 71 | 97 | 70 | 95 | 70 | 91 | 68 | 73 | 71 | 30 | 31 | 36 | 39 | 
 | 
| El Paso de Robles | 35.6 | 721 | 120.7 | 102 | 65 | 95 | 65 | 94 | 65 | 90 | 65 | 69 | 67 | 44 | 16 | 20 | 23 | 1768 | 
| El Rio | 34.3 | 50 | 119.2 | 95 | 69 | 88 | 68 | 86 | 68 | 82 | 66 | 71 | 69 | 20 | 30 | 34 | 37 | 
 | 
| El Segundo | 33.9 | 105 | 118.4 | 91 | 69 | 84 | 68 | 83 | 68 | 79 | 66 | 71 | 69 | 14 | 37 | 40 | 42 | 
 | 
| El Sobrante | 37.9 | 55 | 122.3 | 91 | 66 | 87 | 65 | 86 | 65 | 82 | 64 | 69 | 67 | 25 | 30 | 35 | 38 | 823 | 
| El Toro MCAS | 33.7 | 380 | 117.7 | 96 | 69 | 89 | 69 | 87 | 69 | 82 | 68 | 73 | 71 | 26 | 34 | 38 | 41 | 1591 | 
| El Toro Station | 33.7 | 380 | 117.7 | 96 | 69 | 89 | 69 | 87 | 69 | 82 | 68 | 73 | 71 | 26 | 34 | 38 | 41 | 560 | 
| Electra PH | 38.3 | 715 | 120.7 | 106 | 70 | 102 | 69 | 101 | 69 | 98 | 68 | 73 | 71 | 41 | 23 | 28 | 31 | 2858 | 
| Elk Grove | 38.4 | 50 | 121.4 | 104 | 71 | 100 | 69 | 98 | 69 | 94 | 68 | 73 | 71 | 35 | 29 | 34 | 36 | 1150 | 
| Elk Valley | 42 | 1705 | 123.7 | 96 | 65 | 90 | 63 | 88 | 63 | 84 | 61 | 67 | 65 | 39 | 16 | 23 | 27 | 5404 | 
| Elsinore | 33.7 | 1285 | 117.3 | 105 | 71 | 101 | 70 | 100 | 70 | 98 | 69 | 74 | 72 | 39 | 22 | 26 | 29 | 2128 | 
| Encinitas | 33 | 50 | 117.3 | 87 | 68 | 83 | 67 | 81 | 67 | 77 | 65 | 70 | 68 | 10 | 35 | 39 | 41 | 
 | 
| Encino | 34.2 | 750 | 118.5 | 103 | 71 | 98 | 69 | 96 | 69 | 92 | 67 | 74 | 71 | 27 | 28 | 33 | 36 | 664 | 
| Enterprise | 40.6 | 470 | 122.3 | 107 | 69 | 103 | 68 | 101 | 68 | 97 | 67 | 72 | 70 | 29 | 26 | 31 | 34 | 
 | 
| Escondido | 33.1 | 660 | 117.1 | 97 | 69 | 90 | 68 | 88 | 68 | 84 | 67 | 72 | 70 | 29 | 26 | 31 | 34 | 2005 | 
| Eureka | 40.8 | 43 | 124.2 | 75 | 61 | 69 | 59 | 68 | 59 | 65 | 58 | 61 | 60 | 11 | 30 | 35 | 38 | 4679 | 
| Exeter | 36.3 | 350 | 119.1 | 104 | 72 | 101 | 71 | 100 | 71 | 97 | 69 | 74 | 72 | 39 | 24 | 29 | 32 | 1236 | 
| Fair Oaks | 38.7 | 50 | 121.3 | 104 | 70 | 100 | 69 | 98 | 69 | 94 | 69 | 72 | 71 | 36 | 23 | 29 | 33 | 
 | 
| Fairfax | 38 | 110 | 122.6 | 96 | 68 | 90 | 66 | 88 | 65 | 83 | 63 | 71 | 68 | 34 | 26 | 31 | 34 | 
 | 
| Fairfield FS | 38.3 | 38 | 122 | 103 | 69 | 98 | 68 | 96 | 68 | 91 | 66 | 73 | 71 | 34 | 24 | 30 | 33 | 2686 | 
| Fairmont | 34.7 | 3060 | 118.4 | 100 | 67 | 96 | 66 | 95 | 66 | 92 | 65 | 71 | 69 | 22 | 22 | 28 | 31 | 3330 | 
| Fairview | 35.9 | 3519 | 118.5 | 97 | 67 | 94 | 66 | 93 | 66 | 90 | 64 | 70 | 68 | 43 | 11 | 18 | 23 | 
 | 
| Fallbrook | 33.6 | 660 | 117.3 | 94 | 68 | 89 | 67 | 88 | 67 | 85 | 66 | 71 | 69 | 29 | 26 | 31 | 34 | 2077 | 
| Farmersville | 36.3 | 350 | 119.2 | 104 | 72 | 101 | 72 | 100 | 71 | 97 | 69 | 74 | 72 | 39 | 24 | 29 | 32 | 1236 | 
| Felton | 37 | 100 | 122.1 | 94 | 68 | 88 | 66 | 86 | 66 | 81 | 64 | 69 | 67 | 28 | 27 | 32 | 35 | 1097 | 
| Ferndale | 40.5 | 1445 | 124.3 | 76 | 57 | 66 | 56 | 65 | 56 | 62 | 54 | 59 | 57 | 12 | 28 | 33 | 35 | 
 | 
| Fillmore | 34.4 | 435 | 118.9 | 100 | 70 | 94 | 69 | 92 | 69 | 87 | 67 | 73 | 71 | 30 | 28 | 32 | 35 | 
 | 
| Five Points | 36.4 | 285 | 120.2 | 103 | 71 | 99 | 70 | 97 | 70 | 93 | 68 | 73 | 71 | 36 | 21 | 27 | 30 | 
 | 
| Fleming Fish & Game | 40.4 | 4000 | 120.3 | 96 | 62 | 93 | 61 | 92 | 61 | 88 | 59 | 66 | 64 | 40 | -3 | 2 | 8 | 
 | 
| Florence-Graham | 34 | 175 | 118.3 | 98 | 69 | 90 | 68 | 88 | 68 | 84 | 67 | 72 | 70 | 19 | 35 | 40 | 43 | 
 | 
| Florin | 38.5 | 100 | 121.4 | 104 | 71 | 100 | 69 | 98 | 69 | 94 | 68 | 73 | 71 | 35 | 29 | 34 | 36 | 
 | 
| Folsom Dam | 38.7 | 350 | 121.2 | 104 | 70 | 101 | 69 | 99 | 69 | 95 | 67 | 72 | 71 | 36 | 25 | 31 | 35 | 
 | 
| Fontana | 34.1 | 1090 | 117.4 | 105 | 70 | 101 | 69 | 100 | 69 | 97 | 67 | 74 | 72 | 33 | 30 | 35 | 38 | 1530 | 
| Foothill Farms | 38.6 | 90 | 121.3 | 104 | 71 | 100 | 70 | 98 | 70 | 94 | 68 | 73 | 71 | 36 | 24 | 30 | 34 | 
 | 
| Forest Glen | 40.4 | 2340 | 123.3 | 96 | 65 | 92 | 64 | 91 | 64 | 88 | 62 | 67 | 65 | 42 | 12 | 19 | 24 | 
 | 
| Fort Baker | 37.8 | 15 | 122.5 | 87 | 66 | 81 | 65 | 79 | 65 | 73 | 65 | 67 | 65 | 12 | 33 | 38 | 40 | 3080 | 
| Fort Bidwell | 41.9 | 4498 | 120.1 | 93 | 60 | 90 | 59 | 89 | 59 | 85 | 57 | 64 | 62 | 38 | -2 | 3 | 10 | 6381 | 
| Fort Bragg | 39.5 | 80 | 123.8 | 75 | 60 | 67 | 59 | 66 | 59 | 62 | 58 | 62 | 61 | 15 | 29 | 34 | 37 | 4424 | 
| Fort Jones RS | 41.6 | 2725 | 122.9 | 98 | 64 | 93 | 63 | 92 | 63 | 88 | 61 | 67 | 65 | 44 | 5 | 13 | 18 | 5590 | 
| Fort MacArthur | 33.7 | 200 | 118.3 | 92 | 69 | 84 | 68 | 82 | 68 | 78 | 66 | 71 | 69 | 13 | 35 | 40 | 42 | 1819 | 
| Fort Ord | 36.7 | 134 | 121.8 | 86 | 65 | 77 | 63 | 75 | 62 | 70 | 60 | 67 | 64 | 18 | 24 | 29 | 32 | 3818 | 
| Fort Ross | 38.5 | 116 | 123.3 | 79 | 63 | 74 | 62 | 71 | 61 | 65 | 59 | 64 | 62 | 19 | 30 | 35 | 37 | 4127 | 
| Fortuna | 40.6 | 100 | 124.2 | 75 | 61 | 69 | 59 | 68 | 59 | 65 | 58 | 61 | 60 | 11 | 30 | 35 | 38 | 2000 | 
| Foster City | 37.5 | 20 | 122.7 | 92 | 67 | 84 | 65 | 82 | 65 | 76 | 63 | 68 | 66 | 22 | 29 | 34 | 36 | 
 | 
| Fountain Valley | 33.7 | 60 | 118 | 97 | 70 | 90 | 68 | 88 | 68 | 84 | 67 | 72 | 70 | 18 | 33 | 38 | 40 | 
 | 
| Freedom | 37 | 1495 | 121.8 | 89 | 67 | 85 | 64 | 83 | 64 | 79 | 62 | 68 | 65 | 22 | 27 | 32 | 34 | 
 | 
| Fremont | 37.5 | 56 | 122 | 94 | 67 | 88 | 65 | 86 | 65 | 81 | 63 | 69 | 67 | 24 | 25 | 30 | 33 | 
 | 
| Fresno AP | 36.8 | 328 | 119.7 | 104 | 73 | 101 | 71 | 100 | 70 | 97 | 68 | 75 | 73 | 34 | 24 | 28 | 30 | 2650 | 
| Friant Gov Camp | 37 | 410 | 119.7 | 106 | 72 | 103 | 70 | 102 | 70 | 100 | 68 | 74 | 72 | 40 | 23 | 28 | 31 | 2768 | 
| Fullerton | 33.9 | 340 | 117.9 | 100 | 70 | 94 | 69 | 92 | 69 | 87 | 68 | 73 | 71 | 26 | 30 | 35 | 37 | 
 | 
| Galt | 38.2 | 40 | 121.3 | 101 | 70 | 97 | 68 | 95 | 68 | 91 | 67 | 72 | 70 | 38 | 23 | 28 | 31 | 1240 | 
| Garden Acres | 38 | 20 | 121.3 | 103 | 71 | 98 | 69 | 97 | 69 | 93 | 67 | 73 | 71 | 35 | 24 | 28 | 30 | 1334 | 
| Garden Grove | 33.6 | 85 | 117.9 | 98 | 70 | 91 | 68 | 89 | 68 | 84 | 67 | 72 | 70 | 23 | 31 | 36 | 38 | 
 | 
| Gardena | 33.9 | 40 | 118.3 | 92 | 69 | 85 | 68 | 84 | 68 | 80 | 66 | 71 | 69 | 18 | 32 | 37 | 39 | 
 | 
| George AFB | 34.6 | 2875 | 117.4 | 105 | 67 | 102 | 65 | 101 | 64 | 98 | 62 | 70 | 68 | 31 | 19 | 23 | 26 | 2887 | 
| Georgetown RS | 38.9 | 3001 | 120.8 | 98 | 64 | 95 | 63 | 94 | 63 | 90 | 61 | 68 | 66 | 31 | 18 | 24 | 27 | 
 | 
| Giant Forest | 36.6 | 6412 | 118.8 | 84 | 56 | 81 | 55 | 80 | 55 | 77 | 53 | 60 | 58 | 26 | 5 | 13 | 18 | 
 | 
| Gillespie Field | 32.8 | 385 | 117.0 | 98 | 71 | 91 | 70 | 89 | 70 | 85 | 68 | 73 | 71 | 30 | 24 | 29 | 32 | 
 | 
| Gilroy | 37 | 194 | 121.6 | 101 | 70 | 93 | 68 | 91 | 67 | 86 | 65 | 72 | 69 | 25 | 23 | 28 | 31 | 
 | 
| Glen Avon | 34 | 827 | 117.5 | 105 | 70 | 101 | 69 | 99 | 69 | 95 | 67 | 74 | 72 | 35 | 28 | 33 | 35 | 
 | 
| Glendale | 34.2 | 563 | 118.3 | 101 | 70 | 96 | 68 | 94 | 68 | 90 | 67 | 73 | 71 | 28 | 30 | 35 | 37 | 
 | 
| Glendora | 34.1 | 822 | 117.9 | 102 | 69 | 98 | 68 | 96 | 68 | 92 | 67 | 73 | 71 | 35 | 30 | 35 | 37 | 
 | 
| Glennville | 35.7 | 3140 | 118.7 | 97 | 67 | 94 | 66 | 93 | 66 | 90 | 64 | 70 | 68 | 43 | 11 | 18 | 23 | 4423 | 
| Gold Rock Rch | 32.9 | 485 | 114.8 | 113 | 73 | 110 | 72 | 109 | 72 | 106 | 70 | 79 | 77 | 28 | 31 | 36 | 38 | 
 | 
| Golden Hills | 35.1 | 4000 | 118.5 | 97 | 66 | 93 | 65 | 92 | 65 | 89 | 64 | 69 | 67 | 33 | 13 | 20 | 24 | 
 | 
| Granada Hills | 34.4 | 1032 | 118.5 | 100 | 70 | 95 | 68 | 93 | 68 | 89 | 66 | 73 | 70 | 37 | 28 | 31 | 34 | 664 | 
| Grand Terrace | 34.1 | 1000 | 117.3 | 105 | 70 | 102 | 68 | 101 | 68 | 97 | 67 | 74 | 72 | 35 | 28 | 33 | 36 | 611 | 
| Grant Grove | 36.7 | 6600 | 119 | 82 | 56 | 78 | 55 | 77 | 54 | 74 | 52 | 59 | 57 | 26 | 6 | 14 | 19 | 7044 | 
| Grass Valley | 39.2 | 2400 | 121.1 | 99 | 67 | 96 | 65 | 95 | 65 | 91 | 63 | 69 | 67 | 29 | 19 | 25 | 28 | 
 | 
| Graton | 38.4 | 200 | 122.9 | 95 | 68 | 91 | 67 | 88 | 66 | 82 | 64 | 70 | 68 | 34 | 22 | 28 | 31 | 3409 | 
| Greenacres | 35.3 | 400 | 119.1 | 106 | 71 | 102 | 70 | 101 | 70 | 98 | 68 | 74 | 72 | 34 | 26 | 31 | 35 | 934 | 
| Greenfield | 36.2 | 287 | 121.2 | 92 | 67 | 88 | 65 | 87 | 65 | 84 | 64 | 70 | 68 | 32 | 22 | 27 | 30 | 1020 | 
| Grossmont | 32.7 | 530 | 117 | 96 | 69 | 89 | 68 | 88 | 68 | 84 | 66 | 71 | 69 | 23 | 31 | 36 | 38 | 
 | 
| Grover City | 35.1 | 100 | 120.6 | 93 | 69 | 86 | 64 | 84 | 64 | 80 | 62 | 67 | 65 | 18 | 30 | 34 | 37 | 
 | 
| Guadalupe | 35 | 85 | 120.6 | 92 | 66 | 86 | 64 | 84 | 64 | 79 | 62 | 67 | 65 | 18 | 28 | 32 | 35 | 1035 | 
| Hacienda Hts | 34 | 300 | 118 | 100 | 69 | 96 | 68 | 94 | 68 | 90 | 67 | 73 | 71 | 28 | 31 | 36 | 38 | 
 | 
| Haiwee | 36.1 | 3825 | 118 | 102 | 65 | 99 | 64 | 98 | 64 | 95 | 62 | 68 | 66 | 27 | 15 | 22 | 26 | 3700 | 
| Half Moon Bay | 37.5 | 60 | 122.4 | 83 | 64 | 76 | 62 | 74 | 61 | 69 | 59 | 65 | 63 | 15 | 32 | 37 | 39 | 3843 | 
| Hamilton AFB | 38.1 | 3 | 122.5 | 95 | 69 | 88 | 67 | 86 | 67 | 81 | 65 | 73 | 70 | 28 | 27 | 30 | 32 | 3311 | 
| Hanford | 36.3 | 242 | 119.7 | 102 | 71 | 99 | 70 | 98 | 70 | 94 | 68 | 73 | 71 | 37 | 22 | 28 | 31 | 2736 | 
| Happy Camp RS | 41.8 | 1150 | 123.4 | 103 | 67 | 97 | 66 | 96 | 66 | 92 | 65 | 69 | 67 | 41 | 18 | 24 | 27 | 4263 | 
| Hat Creek PH 1 | 40.9 | 3015 | 121.6 | 99 | 65 | 96 | 64 | 95 | 64 | 91 | 62 | 68 | 66 | 48 | 2 | 7 | 17 | 5689 | 
| Hawaiian Gardens | 33.8 | 75 | 118.1 | 97 | 70 | 91 | 69 | 89 | 69 | 84 | 67 | 72 | 70 | 23 | 32 | 37 | 39 | 
 | 
| Hawthorne | 33.9 | 70 | 118.4 | 92 | 69 | 85 | 68 | 84 | 68 | 80 | 66 | 71 | 69 | 16 | 37 | 40 | 42 | 
 | 
| Hayfield Pumps | 33.7 | 1370 | 115.6 | 112 | 71 | 108 | 70 | 107 | 70 | 104 | 68 | 77 | 75 | 31 | 24 | 29 | 32 | 1529 | 
| Hayward | 37.7 | 530 | 122.1 | 92 | 66 | 86 | 65 | 85 | 64 | 81 | 62 | 68 | 66 | 24 | 26 | 31 | 34 | 2909 | 
| Healdsburg | 38.6 | 102 | 122.9 | 102 | 69 | 95 | 68 | 94 | 68 | 90 | 66 | 71 | 69 | 37 | 26 | 31 | 34 | 2572 | 
| Hemet | 33.7 | 1655 | 117 | 109 | 70 | 104 | 69 | 103 | 69 | 101 | 67 | 74 | 72 | 40 | 20 | 25 | 28 | 
 | 
| Henshaw Dam | 33.2 | 2700 | 116.8 | 99 | 68 | 94 | 67 | 93 | 67 | 90 | 66 | 71 | 69 | 38 | 15 | 22 | 26 | 3708 | 
| Hercules | 38 | 15 | 122.3 | 91 | 66 | 87 | 65 | 86 | 65 | 82 | 64 | 69 | 67 | 25 | 30 | 35 | 38 | 823 | 
| Hermosa Beach | 33.9 | 16 | 118.4 | 92 | 69 | 84 | 68 | 82 | 68 | 78 | 66 | 71 | 69 | 12 | 38 | 42 | 45 | 
 | 
| Hesperia | 34.4 | 3191 | 117.3 | 105 | 67 | 101 | 65 | 100 | 65 | 97 | 63 | 70 | 68 | 38 | 14 | 21 | 25 | 1654 | 
| Hetch Hetchy | 38 | 3870 | 119.8 | 93 | 62 | 89 | 61 | 88 | 61 | 85 | 59 | 65 | 63 | 32 | 14 | 21 | 25 | 4816 | 
| Highland | 34.1 | 1315 | 117.2 | 106 | 70 | 102 | 69 | 101 | 69 | 97 | 68 | 74 | 72 | 36 | 26 | 31 | 34 | 
 | 
| Hillcrest Center | 35.4 | 500 | 
 | 106 | 71 | 102 | 70 | 101 | 70 | 98 | 68 | 74 | 72 | 34 | 26 | 31 | 35 | 
 | 
| Hillsborough | 37.6 | 352 | 122.3 | 90 | 66 | 82 | 65 | 80 | 65 | 74 | 64 | 68 | 66 | 23 | 30 | 35 | 37 | 
 | 
| Hilt | 42 | 2900 | 122.6 | 97 | 64 | 93 | 62 | 92 | 62 | 89 | 60 | 66 | 64 | 39 | 5 | 13 | 18 | 
 | 
| Hollister | 36.9 | 280 | 121.4 | 96 | 68 | 89 | 67 | 87 | 67 | 81 | 65 | 70 | 68 | 30 | 21 | 27 | 30 | 2725 | 
| Hollywood | 34 | 384 | 118.4 | 96 | 70 | 89 | 69 | 87 | 69 | 83 | 67 | 72 | 70 | 20 | 36 | 41 | 44 | 
 | 
| Home Gardens | 33.9 | 678 | 117.5 | 104 | 70 | 100 | 69 | 98 | 69 | 92 | 67 | 74 | 72 | 35 | 26 | 31 | 34 | 
 | 
| Hoopa | 41 | 360 | 123.7 | 100 | 67 | 92 | 66 | 91 | 66 | 87 | 64 | 69 | 67 | 25 | 23 | 28 | 31 | 
 | 
| Huntington Beach | 33.7 | 40 | 117.8 | 91 | 69 | 83 | 67 | 81 | 67 | 76 | 66 | 71 | 69 | 14 | 34 | 38 | 41 | 
 | 
| Huntington Lake | 37.2 | 7020 | 119.2 | 80 | 55 | 77 | 54 | 76 | 53 | 73 | 51 | 58 | 56 | 25 | 3 | 11 | 16 | 7632 | 
| Huntington Park | 34 | 175 | 118 | 98 | 70 | 90 | 69 | 88 | 69 | 84 | 67 | 72 | 70 | 20 | 38 | 42 | 45 | 
 | 
| Idlewild | 41.9 | 1250 | 124 | 103 | 68 | 96 | 66 | 95 | 66 | 92 | 65 | 69 | 67 | 40 | 18 | 24 | 27 | 
 | 
| Idria | 36.4 | 2650 | 120.7 | 97 | 66 | 92 | 65 | 91 | 64 | 87 | 62 | 68 | 66 | 27 | 24 | 29 | 32 | 3128 | 
| Idyllwild | 33.7 | 5397 | 116.7 | 93 | 62 | 89 | 61 | 88 | 61 | 84 | 60 | 67 | 65 | 35 | 9 | 16 | 21 | 
 | 
| Imperial AP | 32.8 | -59 | 115.6 | 114 | 74 | 110 | 73 | 109 | 73 | 106 | 72 | 81 | 79 | 31 | 26 | 31 | 34 | 1060 | 
| Imperial Beach | 32.5 | 23 | 117.1 | 87 | 69 | 82 | 68 | 81 | 68 | 78 | 67 | 71 | 69 | 10 | 35 | 39 | 41 | 1839 | 
| Imperial CO | 32.9 | -64 | 115.6 | 112 | 73 | 108 | 72 | 107 | 72 | 104 | 71 | 80 | 78 | 31 | 29 | 34 | 36 | 976 | 
| Independence | 36.8 | 3950 | 118.2 | 104 | 61 | 101 | 60 | 100 | 60 | 97 | 60 | 65 | 63 | 31 | 12 | 19 | 24 | 
 | 
| Indio | 33.7 | 11 | 116.3 | 115 | 75 | 112 | 75 | 111 | 75 | 107 | 74 | 81 | 79 | 30 | 24 | 29 | 32 | 1059 | 
| Inglewood | 33.9 | 105 | 118 | 92 | 68 | 85 | 67 | 84 | 67 | 80 | 65 | 70 | 68 | 15 | 37 | 40 | 42 | 
 | 
| Inyokern NAS | 35.7 | 2440 | 117.8 | 110 | 71 | 106 | 68 | 105 | 68 | 102 | 66 | 75 | 71 | 37 | 15 | 22 | 26 | 2772 | 
| Ione | 38.3 | 298 | 120.9 | 101 | 70 | 97 | 68 | 95 | 68 | 91 | 67 | 72 | 70 | 38 | 23 | 28 | 31 | 
 | 
| Iron Mtn | 34.1 | 922 | 115.1 | 116 | 75 | 112 | 74 | 111 | 74 | 108 | 73 | 80 | 78 | 26 | 29 | 34 | 36 | 1251 | 
| Irvine | 33.7 | 50 | 118 | 96 | 69 | 88 | 68 | 86 | 68 | 82 | 67 | 72 | 70 | 27 | 33 | 37 | 40 | 
 | 
| Isla Vista | 34.5 | 40 | 119.9 | 90 | 69 | 83 | 67 | 81 | 67 | 77 | 65 | 70 | 68 | 20 | 33 | 38 | 40 | 
 | 
| Jess Valley | 41.3 | 5300 | 120.3 | 92 | 59 | 89 | 58 | 88 | 58 | 84 | 56 | 63 | 61 | 35 | -7 | -2 | 4 | 7045 | 
| John Wayne AP | 33.6 | 115 | 117.9 | 98 | 70 | 91 | 68 | 89 | 68 | 84 | 67 | 72 | 70 | 26 | 33 | 37 | 39 | 1496 | 
| Julian Wynola | 33.1 | 3650 | 116.8 | 96 | 66 | 91 | 64 | 90 | 64 | 87 | 62 | 69 | 67 | 39 | 20 | 24 | 26 | 4049 | 
| Kentfield | 38 | 120 | 122.6 | 97 | 66 | 91 | 65 | 89 | 65 | 84 | 63 | 70 | 68 | 35 | 27 | 32 | 35 | 3009 | 
| Kerman | 36.6 | 216 | 120.1 | 105 | 73 | 101 | 71 | 100 | 70 | 97 | 68 | 75 | 73 | 34 | 24 | 28 | 30 | 1262 | 
| Kern River PH 1 | 35.5 | 970 | 118.8 | 106 | 72 | 103 | 71 | 102 | 71 | 99 | 69 | 75 | 73 | 26 | 30 | 35 | 37 | 1878 | 
| Kern River PH 3 | 35.8 | 2703 | 118.6 | 103 | 69 | 100 | 68 | 99 | 68 | 96 | 66 | 72 | 70 | 34 | 19 | 25 | 28 | 2891 | 
| Kettleman Stn | 36.1 | 508 | 120.1 | 104 | 71 | 100 | 70 | 98 | 70 | 93 | 68 | 74 | 72 | 31 | 26 | 31 | 34 | 2180 | 
| King City | 36.2 | 320 | 121.1 | 94 | 67 | 90 | 65 | 89 | 65 | 85 | 64 | 70 | 68 | 36 | 20 | 26 | 29 | 2639 | 
| Kingsburg | 36.4 | 297 | 119.6 | 104 | 73 | 101 | 71 | 100 | 71 | 97 | 69 | 75 | 73 | 36 | 24 | 30 | 34 | 1300 | 
| Klamath | 41.5 | 25 | 124.1 | 79 | 62 | 71 | 60 | 70 | 60 | 66 | 58 | 64 | 61 | 18 | 26 | 31 | 33 | 4509 | 
| Knights Ferry | 37.8 | 315 | 120.6 | 103 | 70 | 99 | 68 | 98 | 68 | 94 | 67 | 73 | 71 | 37 | 19 | 25 | 28 | 
 | 
| La Canada-Flintridge | 34.2 | 1365 | 118 | 99 | 69 | 95 | 68 | 93 | 68 | 88 | 66 | 72 | 70 | 30 | 32 | 36 | 38 | 
 | 
| La Crescenta-Montrose | 34.2 | 1565 | 118 | 98 | 69 | 94 | 68 | 92 | 68 | 87 | 66 | 72 | 70 | 33 | 31 | 35 | 37 | 
 | 
| La Habra | 33.9 | 305 | 118 | 100 | 69 | 94 | 68 | 92 | 68 | 87 | 67 | 72 | 70 | 27 | 30 | 35 | 37 | 
 | 
| La Habra Heights | 34 | 400 | 118 | 100 | 69 | 94 | 68 | 92 | 68 | 87 | 67 | 72 | 70 | 27 | 30 | 35 | 37 | 
 | 
| La Mesa | 32.8 | 530 | 117 | 94 | 70 | 88 | 69 | 87 | 69 | 84 | 67 | 72 | 70 | 23 | 34 | 39 | 41 | 1567 | 
| La Mirada | 33.9 | 115 | 118 | 99 | 70 | 91 | 69 | 89 | 69 | 85 | 68 | 73 | 71 | 26 | 31 | 36 | 38 | 
 | 
| La Palma | 33.9 | 75 | 118 | 98 | 69 | 92 | 68 | 90 | 68 | 85 | 67 | 72 | 70 | 25 | 31 | 35 | 38 | 
 | 
| La Puente | 34 | 320 | 118 | 101 | 71 | 97 | 70 | 95 | 70 | 91 | 69 | 74 | 72 | 28 | 31 | 36 | 38 | 
 | 
| La Quinta | 33.8 | 400 | 116.3 | 116 | 74 | 112 | 73 | 111 | 73 | 108 | 72 | 79 | 78 | 34 | 26 | 32 | 34 | 332 | 
| La Riviera | 38.6 | 190 | 121.3 | 104 | 71 | 100 | 70 | 98 | 70 | 94 | 68 | 73 | 71 | 32 | 30 | 35 | 37 | 1025 | 
| La Verne | 34.1 | 1235 | 118 | 101 | 69 | 97 | 68 | 95 | 68 | 91 | 67 | 73 | 71 | 34 | 29 | 34 | 36 | 
 | 
| Ladera Heights | 34.1 | 100 | 118.4 | 91 | 67 | 84 | 67 | 83 | 67 | 79 | 66 | 71 | 69 | 14 | 37 | 40 | 42 | 383 | 
| Lafayette | 37.9 | 535 | 122.1 | 100 | 69 | 94 | 67 | 92 | 67 | 87 | 66 | 71 | 69 | 32 | 24 | 29 | 32 | 
 | 
| Laguna Beach | 33.5 | 35 | 117.8 | 91 | 69 | 83 | 68 | 81 | 68 | 76 | 66 | 71 | 69 | 18 | 30 | 33 | 36 | 2222 | 
| Laguna Niguel | 33.6 | 500 | 117.7 | 95 | 67 | 87 | 66 | 85 | 65 | 81 | 63 | 71 | 67 | 22 | 33 | 37 | 40 | 
 | 
| Lake Arrowhead | 34.2 | 5205 | 117.2 | 90 | 62 | 86 | 61 | 85 | 61 | 81 | 59 | 66 | 64 | 26 | 13 | 20 | 24 | 5310 | 
| Lake Elsinore | 33.7 | 1233 | 117.3 | 105 | 70 | 101 | 69 | 100 | 69 | 97 | 68 | 74 | 72 | 39 | 22 | 27 | 30 | 827 | 
| Lake Los Angeles | 34.7 | 2300 | 117.8 | 106 | 68 | 102 | 67 | 101 | 67 | 98 | 66 | 72 | 70 | 35 | 12 | 17 | 20 | 1455 | 
| Lake Spaulding | 39.3 | 5156 | 120.6 | 89 | 58 | 86 | 57 | 85 | 57 | 83 | 55 | 62 | 60 | 34 | 3 | 11 | 16 | 6447 | 
| Lakeland Village | 33.6 | 1233 | 117.3 | 105 | 70 | 101 | 69 | 100 | 69 | 97 | 68 | 74 | 72 | 39 | 12 | 27 | 30 | 827 | 
| Lakeport | 39 | 1347 | 122.9 | 97 | 67 | 93 | 66 | 92 | 65 | 88 | 63 | 69 | 67 | 41 | 20 | 26 | 29 | 3728 | 
| Lakeshore | 40.9 | 1075 | 119.2 | 104 | 69 | 100 | 68 | 99 | 68 | 95 | 66 | 71 | 69 | 28 | 29 | 34 | 36 | 
 | 
| Lakeside | 32.8 | 690 | 117 | 95 | 69 | 90 | 68 | 89 | 68 | 86 | 66 | 72 | 70 | 20 | 26 | 31 | 34 | 
 | 
| Lakewood | 33.9 | 45 | 118 | 98 | 70 | 90 | 68 | 88 | 68 | 84 | 66 | 72 | 70 | 22 | 33 | 37 | 40 | 
 | 
| Lamont | 35.3 | 500 | 120 | 106 | 72 | 102 | 71 | 101 | 71 | 98 | 69 | 75 | 73 | 34 | 26 | 32 | 35 | 
 | 
| Lancaster | 34.7 | 2340 | 118.2 | 106 | 68 | 102 | 67 | 101 | 67 | 98 | 66 | 72 | 70 | 35 | 12 | 17 | 20 | 
 | 
| Larksfield-Wikiup | 38.5 | 170 | 122.8 | 99 | 69 | 96 | 68 | 95 | 68 | 92 | 66 | 71 | 69 | 35 | 24 | 27 | 29 | 1249 | 
| Larkspur | 37.9 | 20 | 122.5 | 97 | 68 | 91 | 66 | 89 | 66 | 84 | 64 | 69 | 68 | 34 | 28 | 33 | 35 | 
 | 
| Las Plumas | 39.7 | 506 | 121.4 | 104 | 71 | 101 | 70 | 100 | 70 | 96 | 68 | 73 | 71 | 32 | 24 | 29 | 32 | 
 | 
| Lathrop | 37.8 | 22 | 121.3 | 103 | 71 | 98 | 69 | 97 | 69 | 93 | 67 | 73 | 71 | 35 | 24 | 28 | 30 | 1300 | 
| Lava Beds | 41.7 | 4770 | 121.5 | 93 | 59 | 89 | 58 | 88 | 58 | 84 | 56 | 63 | 61 | 41 | -1 | 4 | 11 | 
 | 
| Lawndale | 33.9 | 66 | 118 | 92 | 69 | 85 | 68 | 84 | 68 | 80 | 66 | 71 | 69 | 16 | 37 | 40 | 42 | 
 | 
| Le Grand | 37.2 | 255 | 120.3 | 101 | 70 | 96 | 68 | 95 | 68 | 91 | 66 | 72 | 70 | 38 | 23 | 28 | 31 | 2696 | 
| Lemon Grove | 32.7 | 437 | 117.2 | 96 | 71 | 88 | 69 | 87 | 69 | 84 | 67 | 72 | 70 | 19 | 34 | 38 | 41 | 
 | 
| Lemoncove | 36.4 | 513 | 119 | 105 | 72 | 102 | 70 | 101 | 70 | 98 | 68 | 72 | 70 | 38 | 25 | 38 | 41 | 2513 | 
| Lemoore NAS | 36.3 | 228 | 120 | 104 | 72 | 101 | 71 | 100 | 71 | 97 | 69 | 74 | 72 | 37 | 19 | 25 | 28 | 2960 | 
| Lennox | 33.9 | 71 | 117.8 | 92 | 69 | 85 | 68 | 84 | 68 | 80 | 66 | 71 | 69 | 16 | 37 | 41 | 44 | 
 | 
| Lincoln Village | 38 | 12 | 121.3 | 101 | 70 | 96 | 68 | 95 | 68 | 91 | 67 | 72 | 70 | 37 | 24 | 28 | 30 | 1334 | 
| Linda | 39 | 60 | 121.6 | 105 | 72 | 102 | 70 | 101 | 70 | 97 | 68 | 74 | 72 | 30 | 27 | 32 | 35 | 1160 | 
| Lindsay | 36.2 | 395 | 119.1 | 105 | 72 | 101 | 71 | 100 | 71 | 97 | 69 | 74 | 72 | 40 | 24 | 29 | 32 | 2634 | 
| Little Panoche | 36.8 | 677 | 120.7 | 100 | 68 | 94 | 67 | 92 | 67 | 86 | 66 | 71 | 69 | 33 | 23 | 28 | 31 | 
 | 
| Live Oak | 39.2 | 75 | 121.7 | 105 | 70 | 102 | 69 | 101 | 69 | 97 | 69 | 73 | 71 | 36 | 24 | 29 | 32 | 1160 | 
| Livermore | 37.7 | 490 | 122 | 100 | 69 | 95 | 68 | 93 | 68 | 88 | 67 | 71 | 70 | 35 | 22 | 25 | 28 | 3012 | 
| Livingston | 37.3 | 165 | 120.7 | 103 | 72 | 100 | 70 | 99 | 70 | 95 | 68 | 74 | 72 | 39 | 24 | 30 | 34 | 1244 | 
| Llano Shawnee | 34.5 | 3820 | 117.8 | 104 | 68 | 99 | 67 | 98 | 67 | 95 | 65 | 71 | 69 | 31 | 21 | 27 | 31 | 
 | 
| Lodgepole | 36.6 | 6735 | 118.7 | 84 | 57 | 80 | 56 | 80 | 56 | 78 | 54 | 60 | 58 | 26 | -4 | 1 | 7 | 
 | 
| Lodi | 38.1 | 40 | 121.3 | 101 | 70 | 97 | 68 | 95 | 68 | 91 | 67 | 72 | 70 | 38 | 23 | 28 | 31 | 2859 | 
| Loma Linda | 34 | 1150 | 117.5 | 106 | 70 | 103 | 69 | 102 | 69 | 99 | 67 | 74 | 72 | 36 | 27 | 32 | 35 | 
 | 
| Lomita | 33.8 | 56 | 119 | 95 | 69 | 87 | 68 | 85 | 68 | 81 | 66 | 71 | 69 | 18 | 33 | 38 | 40 | 
 | 
| Lompoc | 34.9 | 95 | 120.5 | 84 | 63 | 77 | 62 | 76 | 62 | 72 | 60 | 65 | 63 | 18 | 26 | 31 | 34 | 2888 | 
| Long Beach | 33.7 | 34 | 118.2 | 97 | 70 | 88 | 68 | 86 | 67 | 82 | 65 | 65 | 63 | 18 | 35 | 31 | 34 | 
 | 
| Long Beach AP | 33.8 | 25 | 118.2 | 99 | 71 | 90 | 69 | 88 | 68 | 84 | 66 | 73 | 71 | 21 | 33 | 38 | 41 | 1606 | 
| Loomis | 38.8 | 408 | 121.2 | 107 | 71 | 103 | 70 | 102 | 70 | 98 | 69 | 74 | 72 | 39 | 21 | 27 | 30 | 
 | 
| Los Alamitos NAS | 33.8 | 30 | 118.1 | 98 | 71 | 89 | 69 | 87 | 69 | 83 | 68 | 73 | 71 | 23 | 32 | 37 | 39 | 1740 | 
| Los Altos | 37.3 | 163 | 122 | 96 | 68 | 88 | 65 | 86 | 64 | 80 | 62 | 70 | 68 | 26 | 28 | 33 | 35 | 
 | 
| Los Altos Hills | 37.3 | 183 | 122.1 | 93 | 67 | 85 | 64 | 83 | 64 | 77 | 63 | 68 | 66 | 25 | 28 | 33 | 35 | 1103 | 
| Los Angeles AP | 33.9 | 97 | 118.4 | 91 | 67 | 84 | 67 | 83 | 67 | 79 | 66 | 71 | 69 | 14 | 37 | 40 | 42 | 1819 | 
| Los Angeles CO | 34 | 270 | 118.2 | 99 | 69 | 92 | 68 | 90 | 68 | 86 | 67 | 72 | 70 | 21 | 38 | 41 | 43 | 1245 | 
| Los Banos | 37 | 120 | 120.9 | 100 | 70 | 96 | 68 | 94 | 68 | 88 | 67 | 72 | 70 | 42 | 22 | 28 | 31 | 2616 | 
| Los Banos Res | 37 | 407 | 120.9 | 101 | 70 | 97 | 68 | 95 | 68 | 89 | 67 | 72 | 70 | 42 | 23 | 29 | 31 | 
 | 
| Los Gatos | 37.2 | 365 | 122 | 98 | 69 | 90 | 67 | 88 | 67 | 82 | 66 | 71 | 69 | 32 | 26 | 31 | 34 | 2741 | 
| Los Serranos | 34.1 | 714 | 117.7 | 104 | 70 | 100 | 69 | 98 | 69 | 94 | 68 | 74 | 72 | 35 | 27 | 32 | 35 | 706 | 
| Lucas Vly-Marinwood | 38.3 | 20 | 122.6 | 79 | 63 | 74 | 62 | 71 | 61 | 65 | 59 | 64 | 62 | 12 | 30 | 35 | 37 | 874 | 
| Lucerne Valley | 34.5 | 2957 | 117 | 105 | 67 | 101 | 66 | 100 | 66 | 98 | 64 | 71 | 69 | 38 | 12 | 19 | 24 | 
 | 
| Lynwood | 33.9 | 88 | 118 | 98 | 70 | 90 | 69 | 88 | 69 | 83 | 67 | 72 | 70 | 21 | 32 | 37 | 39 | 
 | 
| Madera | 37 | 268 | 120.1 | 105 | 72 | 101 | 70 | 100 | 70 | 96 | 68 | 74 | 72 | 40 | 24 | 29 | 32 | 2673 | 
| Madera Acres | 36.9 | 275 | 120.1 | 105 | 72 | 101 | 70 | 100 | 70 | 96 | 68 | 74 | 72 | 40 | 24 | 29 | 32 | 1250 | 
| Manhattan Beach | 33.9 | 120 | 118 | 91 | 69 | 84 | 68 | 83 | 68 | 79 | 66 | 71 | 69 | 12 | 38 | 42 | 45 | 
 | 
| Manteca | 37.8 | 34 | 121.2 | 102 | 70 | 97 | 68 | 95 | 68 | 91 | 67 | 72 | 70 | 37 | 24 | 29 | 32 | 
 | 
| Manzanita Lake | 40.5 | 5850 | 121.6 | 87 | 58 | 84 | 57 | 83 | 57 | 79 | 55 | 61 | 59 | 34 | -3 | 2 | 8 | 7617 | 
| March AFB | 33.9 | 1511 | 117.3 | 103 | 70 | 99 | 68 | 98 | 67 | 94 | 65 | 74 | 71 | 34 | 23 | 30 | 33 | 2089 | 
| Maricopa | 35.1 | 675 | 119.4 | 106 | 71 | 102 | 70 | 101 | 70 | 98 | 68 | 74 | 72 | 29 | 25 | 30 | 33 | 2302 | 
| Marina | 36.7 | 20 | 121.8 | 86 | 66 | 77 | 63 | 75 | 63 | 70 | 61 | 67 | 64 | 18 | 32 | 37 | 40 | 
 | 
| Marina del Rey | 34.1 | 40 | 118.5 | 91 | 69 | 84 | 68 | 83 | 68 | 79 | 66 | 71 | 69 | 12 | 38 | 42 | 45 | 383 | 
| Markley Cove | 38.5 | 480 | 122.1 | 104 | 70 | 99 | 69 | 97 | 69 | 93 | 67 | 72 | 70 | 39 | 23 | 29 | 31 | 
 | 
| Martinez FS | 38 | 40 | 122.1 | 99 | 67 | 94 | 66 | 92 | 66 | 88 | 65 | 71 | 69 | 36 | 28 | 33 | 35 | 
 | 
| Marysville | 39.2 | 60 | 121.6 | 105 | 72 | 102 | 70 | 101 | 70 | 97 | 68 | 74 | 72 | 36 | 27 | 32 | 35 | 2552 | 
| Mather AFB | 38.6 | 96 | 121.3 | 104 | 71 | 100 | 70 | 98 | 70 | 94 | 68 | 73 | 71 | 35 | 28 | 33 | 35 | 
 | 
| Maywood | 34 | 170 | 118 | 97 | 70 | 91 | 69 | 89 | 69 | 85 | 67 | 72 | 70 | 21 | 34 | 38 | 41 | 
 | 
| McClellan AFB | 38.7 | 86 | 121.4 | 105 | 71 | 102 | 70 | 100 | 70 | 96 | 68 | 74 | 71 | 35 | 23 | 28 | 21 | 2566 | 
| McCloud | 41.3 | 3300 | 122.1 | 96 | 63 | 93 | 62 | 91 | 62 | 87 | 60 | 66 | 64 | 42 | 5 | 13 | 18 | 5990 | 
| McFarland | 35.6 | 350 | 119.2 | 106 | 71 | 102 | 70 | 101 | 70 | 98 | 69 | 74 | 72 | 36 | 22 | 25 | 28 | 1162 | 
| McKinleyville | 40.9 | 33 | 124.1 | 75 | 61 | 69 | 59 | 68 | 59 | 65 | 58 | 61 | 60 | 11 | 28 | 31 | 33 | 1995 | 
| Mecca FS | 33.6 | -180 | 116.1 | 115 | 75 | 111 | 75 | 110 | 75 | 107 | 74 | 81 | 79 | 30 | 24 | 29 | 32 | 1185 | 
| Mendota | 36.7 | 169 | 120.4 | 105 | 73 | 101 | 71 | 100 | 70 | 97 | 68 | 75 | 73 | 34 | 24 | 28 | 30 | 1273 | 
| Menlo Park | 37.4 | 65 | 122.3 | 94 | 67 | 86 | 65 | 84 | 65 | 78 | 63 | 69 | 67 | 25 | 27 | 32 | 34 | 
 | 
| Mentone | 34.1 | 1700 | 117.1 | 106 | 70 | 102 | 69 | 101 | 69 | 98 | 67 | 74 | 72 | 34 | 27 | 32 | 35 | 741 | 
| Merced AP | 37.3 | 153 | 120.6 | 103 | 71 | 100 | 69 | 99 | 69 | 95 | 67 | 73 | 71 | 36 | 21 | 27 | 30 | 2653 | 
| Mill Creek | 35.1 | 2940 | 117 | 102 | 67 | 97 | 66 | 96 | 66 | 94 | 65 | 70 | 68 | 28 | 28 | 33 | 36 | 
 | 
| Mill Valley | 37.9 | 80 | 122.6 | 97 | 68 | 91 | 66 | 89 | 66 | 84 | 64 | 70 | 68 | 28 | 28 | 33 | 35 | 3400 | 
| Millbrae | 37.6 | 10 | 122.4 | 90 | 66 | 82 | 63 | 80 | 63 | 74 | 61 | 67 | 65 | 24 | 30 | 35 | 37 | 
 | 
| Milpitas | 37.4 | 15 | 121.9 | 94 | 68 | 87 | 65 | 85 | 65 | 79 | 63 | 70 | 67 | 27 | 27 | 32 | 35 | 
 | 
| Mineral | 40.4 | 4911 | 121.6 | 90 | 60 | 87 | 59 | 86 | 59 | 82 | 57 | 63 | 61 | 38 | 2 | 7 | 14 | 7257 | 
| Mira Loma | 34 | 700 | 117.5 | 105 | 70 | 101 | 69 | 99 | 68 | 95 | 66 | 74 | 72 | 34 | 25 | 33 | 36 | 600 | 
| Miramar AFS | 32.9 | 477 | 117.1 | 97 | 69 | 91 | 68 | 90 | 68 | 86 | 67 | 72 | 70 | 22 | 32 | 36 | 38 | 1532 | 
| Miramonte | 34.4 | 750 | 119.1 | 102 | 71 | 97 | 69 | 95 | 69 | 91 | 68 | 73 | 71 | 38 | 25 | 29 | 32 | 771 | 
| Mission Viejo | 33.6 | 350 | 118 | 95 | 67 | 87 | 66 | 85 | 65 | 81 | 63 | 71 | 67 | 22 | 33 | 37 | 40 | 
 | 
| Mitchell Caverns | 34.9 | 4350 | 117.0 | 102 | 64 | 98 | 63 | 97 | 63 | 94 | 61 | 69 | 67 | 29 | 21 | 27 | 30 | 
 | 
| Modesto | 37.6 | 91 | 121 | 102 | 73 | 99 | 70 | 98 | 70 | 95 | 68 | 75 | 72 | 36 | 25 | 30 | 33 | 2671 | 
| Moffett Field NAS | 37.4 | 39 | 122.1 | 89 | 68 | 84 | 66 | 82 | 66 | 78 | 64 | 70 | 68 | 23 | 30 | 34 | 36 | 2511 | 
| Mojave | 35.1 | 2735 | 118.2 | 106 | 68 | 102 | 67 | 101 | 67 | 98 | 66 | 71 | 69 | 35 | 16 | 22 | 26 | 3012 | 
| Mono Lake | 38 | 6450 | 119.2 | 91 | 58 | 88 | 57 | 87 | 57 | 84 | 55 | 62 | 60 | 32 | 4 | 12 | 17 | 6518 | 
| Monrovia | 34.2 | 562 | 118.3 | 100 | 69 | 96 | 68 | 94 | 68 | 90 | 67 | 73 | 71 | 30 | 33 | 38 | 41 | 
 | 
| Montague | 41.8 | 2648 | 122.5 | 99 | 66 | 95 | 65 | 94 | 65 | 90 | 63 | 69 | 67 | 39 | 3 | 11 | 16 | 5474 | 
| Montclair | 34 | 1220 | 117 | 104 | 69 | 100 | 68 | 98 | 68 | 94 | 66 | 73 | 71 | 35 | 28 | 33 | 35 | 
 | 
| Montebello | 34 | 205 | 118.1 | 98 | 69 | 93 | 68 | 91 | 68 | 86 | 67 | 72 | 70 | 24 | 33 | 37 | 39 | 
 | 
| Monterey AP | 36.6 | 245 | 121.9 | 86 | 65 | 77 | 62 | 75 | 62 | 70 | 61 | 66 | 63 | 20 | 30 | 35 | 38 | 3556 | 
| Monterey CO | 36.6 | 345 | 121.9 | 87 | 65 | 78 | 62 | 76 | 62 | 71 | 61 | 66 | 63 | 20 | 32 | 37 | 40 | 3169 | 
| Monterey Park | 34 | 380 | 118 | 99 | 69 | 94 | 68 | 92 | 68 | 87 | 67 | 72 | 70 | 23 | 30 | 35 | 37 | 
 | 
| Monticello Dam | 38.5 | 505 | 122.1 | 105 | 71 | 100 | 70 | 98 | 70 | 94 | 68 | 73 | 71 | 39 | 26 | 31 | 34 | 
 | 
| Moraga | 37.8 | 600 | 122.2 | 99 | 68 | 93 | 66 | 91 | 66 | 86 | 64 | 70 | 68 | 27 | 21 | 26 | 29 | 
 | 
| Moreno Valley | 33.9 | 1600 | 117.2 | 103 | 70 | 99 | 68 | 98 | 67 | 94 | 65 | 74 | 71 | 34 | 27 | 30 | 33 | 611 | 
| Morgan Hill | 37.1 | 350 | 120 | 100 | 69 | 92 | 68 | 90 | 68 | 85 | 66 | 71 | 69 | 25 | 26 | 31 | 34 | 
 | 
| Morro Bay FD | 35.4 | 115 | 120.9 | 88 | 65 | 82 | 64 | 80 | 64 | 76 | 62 | 67 | 65 | 14 | 31 | 36 | 38 | 
 | 
| Mount Baldy Notch | 34.3 | 7735 | 117.6 | 80 | 58 | 76 | 57 | 75 | 56 | 71 | 54 | 61 | 59 | 32 | 4 | 10 | 14 | 
 | 
| Mount Diablo | 37.9 | 2100 | 121.9 | 101 | 68 | 96 | 66 | 93 | 66 | 87 | 65 | 68 | 59 | 28 | 27 | 32 | 35 | 4600 | 
| Mount Hamilton | 37.3 | 4206 | 121.7 | 95 | 59 | 88 | 58 | 86 | 58 | 81 | 56 | 63 | 61 | 18 | 18 | 24 | 27 | 4724 | 
| Mount Hebron RS | 41.8 | 4250 | 122 | 92 | 60 | 88 | 59 | 86 | 59 | 82 | 57 | 63 | 61 | 42 | -10 | -4 | 0 | 
 | 
| Mount San Jacinto | 33.8 | 8417 | 116.6 | 82 | 56 | 77 | 55 | 76 | 55 | 73 | 53 | 61 | 59 | 35 | -1 | 4 | 11 | 
 | 
| Mount Shasta | 41.3 | 3535 | 122.3 | 93 | 62 | 89 | 61 | 88 | 61 | 84 | 59 | 65 | 63 | 34 | 8 | 15 | 20 | 5890 | 
| Mount Wilson | 34.2 | 5709 | 118.1 | 90 | 63 | 85 | 61 | 83 | 60 | 79 | 58 | 66 | 64 | 21 | 15 | 22 | 26 | 4296 | 
| Mountain Pass | 35.5 | 4730 | 115.5 | 100 | 65 | 96 | 64 | 95 | 64 | 92 | 63 | 68 | 66 | 29 | 11 | 18 | 23 | 
 | 
| Mountain View | 37.5 | 95 | 121.9 | 93 | 67 | 85 | 64 | 83 | 64 | 77 | 62 | 68 | 66 | 25 | 28 | 33 | 35 | 
 | 
| Muscoy | 34.2 | 1400 | 117.3 | 105 | 71 | 101 | 69 | 100 | 68 | 96 | 66 | 75 | 72 | 37 | 26 | 31 | 34 | 614 | 
| Nacimiento Dam | 35.8 | 770 | 120.9 | 100 | 68 | 94 | 66 | 92 | 66 | 88 | 64 | 70 | 68 | 35 | 22 | 28 | 31 | 
 | 
| Napa State Hospital | 37.3 | 60 | 122.3 | 94 | 67 | 91 | 67 | 90 | 67 | 86 | 66 | 71 | 70 | 29 | 26 | 31 | 34 | 2749 | 
| National City | 32.7 | 34 | 117 | 87 | 70 | 82 | 68 | 81 | 68 | 78 | 66 | 71 | 69 | 10 | 36 | 40 | 42 | 
 | 
| Needles AP | 34.8 | 913 | 114.6 | 117 | 73 | 114 | 72 | 113 | 72 | 110 | 71 | 77 | 75 | 26 | 27 | 32 | 35 | 1391 | 
| Nevada City | 39.3 | 2600 | 121 | 97 | 66 | 94 | 64 | 92 | 64 | 88 | 63 | 68 | 66 | 41 | 14 | 21 | 25 | 4900 | 
| Newark | 37.5 | 10 | 122 | 94 | 68 | 89 | 67 | 87 | 67 | 82 | 65 | 70 | 68 | 24 | 29 | 34 | 36 | 
 | 
| Newhall Soledad | 34.4 | 1243 | 118.6 | 104 | 70 | 100 | 68 | 99 | 68 | 95 | 67 | 73 | 71 | 42 | 27 | 33 | 36 | 
 | 
| Newman | 37.3 | 90 | 121.1 | 104 | 71 | 99 | 69 | 97 | 69 | 93 | 67 | 73 | 71 | 38 | 22 | 28 | 31 | 
 | 
| Newport Beach | 33.6 | 10 | 117.9 | 87 | 68 | 80 | 66 | 78 | 66 | 72 | 65 | 70 | 68 | 12 | 34 | 39 | 41 | 1952 | 
| Nipomo | 35 | 330 | 120.5 | 90 | 66 | 83 | 64 | 82 | 63 | 78 | 61 | 67 | 65 | 23 | 25 | 31 | 33 | 1035 | 
| Norco | 33.9 | 700 | 117 | 103 | 70 | 99 | 69 | 98 | 69 | 94 | 67 | 74 | 72 | 34 | 27 | 32 | 35 | 
 | 
| North Auburn | 38.9 | 1300 | 121.1 | 103 | 69 | 100 | 67 | 99 | 67 | 95 | 66 | 72 | 69 | 33 | 25 | 30 | 33 | 1518 | 
| North Fork RS | 37.2 | 2630 | 119.5 | 98 | 66 | 95 | 65 | 94 | 64 | 92 | 62 | 69 | 67 | 36 | 15 | 22 | 26 | 
 | 
| North Highlands | 38.6 | 45 | 121.4 | 104 | 71 | 100 | 69 | 98 | 69 | 94 | 67 | 73 | 71 | 35 | 23 | 28 | 31 | 2566 | 
| North Hollywood | 34.2 | 619 | 118.4 | 102 | 70 | 97 | 69 | 95 | 69 | 91 | 67 | 73 | 71 | 31 | 28 | 33 | 36 | 
 | 
| Northridge | 34.2 | 875 | 118.5 | 101 | 70 | 96 | 69 | 94 | 69 | 90 | 67 | 73 | 71 | 36 | 30 | 35 | 38 | 650 | 
| Norwalk | 33.9 | 97 | 118.1 | 99 | 69 | 90 | 68 | 88 | 68 | 84 | 67 | 72 | 70 | 26 | 31 | 35 | 37 | 
 | 
| Novato | 38.1 | 370 | 122.5 | 94 | 64 | 87 | 63 | 85 | 63 | 80 | 61 | 68 | 66 | 30 | 25 | 30 | 32 | 
 | 
| Oakdale | 37.8 | 215 | 120.9 | 102 | 71 | 99 | 69 | 97 | 69 | 93 | 67 | 73 | 71 | 37 | 22 | 28 | 32 | 
 | 
| Oakland AP | 37.7 | 6 | 122.2 | 91 | 66 | 84 | 64 | 82 | 64 | 77 | 62 | 67 | 65 | 20 | 32 | 34 | 37 | 2909 | 
| Oakland Museum | 37.8 | 30 | 122.2 | 96 | 68 | 89 | 66 | 87 | 65 | 82 | 63 | 69 | 67 | 20 | 31 | 33 | 36 | 
 | 
| Oakley | 38 | 20 | 121.7 | 102 | 70 | 97 | 68 | 95 | 68 | 91 | 66 | 70 | 69 | 34 | 22 | 28 | 31 | 
 | 
| Oceano | 35.1 | 20 | 120.6 | 93 | 69 | 86 | 64 | 84 | 64 | 80 | 62 | 67 | 65 | 18 | 30 | 34 | 37 | 795 | 
| Oceanside | 33.2 | 10 | 117.4 | 84 | 69 | 80 | 67 | 78 | 67 | 74 | 65 | 70 | 68 | 10 | 33 | 37 | 39 | 
 | 
| Oildale | 35.5 | 450 | 119 | 106 | 71 | 102 | 70 | 101 | 70 | 98 | 68 | 74 | 72 | 34 | 26 | 31 | 35 | 
 | 
| Ojai | 34.5 | 750 | 119.3 | 102 | 71 | 97 | 69 | 95 | 69 | 91 | 68 | 73 | 71 | 38 | 25 | 29 | 32 | 2145 | 
| Olivehurst | 39 | 64 | 121.6 | 105 | 72 | 102 | 70 | 101 | 70 | 97 | 68 | 74 | 72 | 36 | 27 | 32 | 35 | 1160 | 
| Ontario AP | 34 | 934 | 117 | 105 | 70 | 101 | 69 | 99 | 68 | 95 | 66 | 74 | 72 | 34 | 26 | 33 | 36 | 1710 | 
| Opal Cliffs | 37 | 125 | 122 | 94 | 68 | 88 | 66 | 86 | 66 | 81 | 64 | 69 | 67 | 28 | 27 | 32 | 35 | 1097 | 
| Orange | 33.6 | 194 | 118 | 99 | 70 | 92 | 68 | 90 | 68 | 85 | 67 | 72 | 70 | 27 | 33 | 37 | 40 | 
 | 
| Orange Cove | 36.6 | 431 | 119.3 | 104 | 71 | 100 | 69 | 99 | 69 | 97 | 68 | 73 | 71 | 38 | 25 | 30 | 33 | 2684 | 
| Orangevale | 38.7 | 140 | 121.2 | 105 | 72 | 102 | 70 | 100 | 70 | 96 | 68 | 74 | 71 | 36 | 24 | 30 | 34 | 
 | 
| Orick Prairie Creek | 41.4 | 161 | 124 | 80 | 61 | 75 | 60 | 74 | 60 | 70 | 59 | 63 | 61 | 23 | 25 | 30 | 33 | 4816 | 
| Orinda | 37.9 | 550 | 122.2 | 99 | 68 | 93 | 66 | 91 | 66 | 86 | 64 | 70 | 68 | 32 | 21 | 26 | 29 | 
 | 
| Orland | 39.8 | 254 | 122.2 | 105 | 71 | 102 | 70 | 101 | 70 | 97 | 68 | 73 | 71 | 36 | 22 | 28 | 31 | 2824 | 
| Orleans | 41.3 | 403 | 123.5 | 104 | 70 | 97 | 68 | 95 | 68 | 91 | 66 | 71 | 69 | 42 | 21 | 27 | 30 | 3628 | 
| Orosi | 36.5 | 400 | 119.3 | 104 | 73 | 101 | 70 | 100 | 70 | 96 | 69 | 75 | 73 | 36 | 24 | 30 | 34 | 1130 | 
| Oroville East | 39.5 | 171 | 121.6 | 106 | 71 | 104 | 70 | 102 | 70 | 98 | 69 | 74 | 72 | 37 | 25 | 30 | 33 | 1385 | 
| Oroville RS | 39.5 | 300 | 121.6 | 106 | 71 | 104 | 70 | 102 | 70 | 98 | 69 | 74 | 72 | 37 | 25 | 30 | 33 | 
 | 
| Otay-Castle Pk | 32.6 | 500 | 117 | 87 | 68 | 81 | 66 | 79 | 65 | 74 | 63 | 69 | 67 | 10 | 33 | 38 | 40 | 
 | 
| Oxnard AFB | 34.2 | 49 | 119.2 | 94 | 69 | 86 | 68 | 84 | 68 | 79 | 67 | 71 | 69 | 21 | 30 | 34 | 37 | 2068 | 
| Pacific Grove | 36.7 | 114 | 122 | 87 | 66 | 78 | 63 | 76 | 63 | 71 | 61 | 67 | 64 | 19 | 31 | 35 | 37 | 
 | 
| Pacifica | 37.6 | 13 | 122 | 87 | 65 | 79 | 62 | 77 | 62 | 71 | 60 | 66 | 64 | 16 | 31 | 35 | 37 | 
 | 
| Pacoima | 34.3 | 895 | 118.4 | 104 | 71 | 99 | 70 | 98 | 70 | 94 | 68 | 74 | 72 | 35 | 29 | 34 | 37 | 664 | 
| Palermo | 39.4 | 154 | 121.5 | 106 | 71 | 104 | 70 | 102 | 70 | 98 | 69 | 74 | 72 | 37 | 25 | 30 | 33 | 1170 | 
| Palm Desert | 33.7 | 200 | 116.5 | 116 | 74 | 112 | 73 | 111 | 73 | 108 | 72 | 79 | 78 | 34 | 26 | 32 | 34 | 
 | 
| Palm Desert Country | 33.7 | 243 | 116.3 | 116 | 74 | 112 | 73 | 111 | 73 | 108 | 72 | 79 | 78 | 34 | 26 | 32 | 34 | 374 | 
| Palm Springs | 33.8 | 411 | 116.5 | 117 | 74 | 113 | 73 | 112 | 73 | 109 | 72 | 79 | 78 | 35 | 26 | 31 | 34 | 1109 | 
| Palmdale AP | 34.6 | 2517 | 118.1 | 107 | 67 | 103 | 67 | 102 | 66 | 98 | 64 | 71 | 69 | 33 | 12 | 20 | 24 | 2929 | 
| Palmdale CO | 34.6 | 2596 | 118.1 | 106 | 67 | 102 | 67 | 101 | 66 | 97 | 64 | 71 | 69 | 35 | 13 | 21 | 25 | 2908 | 
| Palo Alto | 37.5 | 25 | 122.1 | 93 | 66 | 85 | 64 | 83 | 64 | 77 | 62 | 68 | 66 | 25 | 26 | 31 | 34 | 2891 | 
| Palomar Obsy | 33.4 | 5545 | 116.9 | 90 | 62 | 85 | 61 | 84 | 61 | 80 | 59 | 66 | 64 | 22 | 16 | 20 | 23 | 4141 | 
| Palos Verdes | 33.8 | 216 | 119 | 92 | 69 | 84 | 68 | 82 | 68 | 78 | 66 | 71 | 69 | 14 | 38 | 43 | 46 | 
 | 
| Panorama City | 34.2 | 801 | 118.5 | 103 | 71 | 98 | 69 | 96 | 69 | 92 | 67 | 74 | 71 | 32 | 28 | 33 | 36 | 664 | 
| Paradise | 39.8 | 1750 | 121.6 | 102 | 69 | 99 | 67 | 98 | 67 | 94 | 66 | 71 | 69 | 34 | 25 | 30 | 33 | 
 | 
| Paramount | 33.9 | 70 | 117 | 98 | 70 | 90 | 69 | 88 | 69 | 84 | 67 | 72 | 70 | 22 | 32 | 37 | 40 | 
 | 
| Parker Res | 34.3 | 738 | 114.2 | 115 | 74 | 112 | 73 | 111 | 73 | 108 | 72 | 79 | 77 | 26 | 32 | 37 | 40 | 1223 | 
| Parkway-South Sacramento | 38.5 | 17 | 121.4 | 104 | 71 | 100 | 70 | 98 | 70 | 94 | 68 | 73 | 71 | 32 | 30 | 35 | 37 | 1150 | 
| Parlier | 36.6 | 320 | 119.5 | 104 | 73 | 101 | 71 | 100 | 70 | 97 | 68 | 75 | 73 | 38 | 24 | 30 | 34 | 1262 | 
| Pasadena | 34.2 | 864 | 118.2 | 99 | 69 | 94 | 68 | 92 | 68 | 88 | 67 | 73 | 71 | 30 | 32 | 37 | 40 | 1551 | 
| Paso Robles AP | 35.7 | 815 | 120.7 | 104 | 66 | 97 | 66 | 96 | 66 | 92 | 65 | 70 | 68 | 40 | 19 | 23 | 26 | 2973 | 
| Paso Robles CO | 35.6 | 700 | 120.7 | 102 | 65 | 95 | 65 | 94 | 65 | 90 | 65 | 69 | 67 | 44 | 16 | 20 | 23 | 2885 | 
| Patterson | 37.4 | 97 | 121.1 | 101 | 72 | 96 | 70 | 94 | 69 | 90 | 67 | 74 | 72 | 36 | 24 | 30 | 34 | 1240 | 
| Pedley | 34 | 718 | 117.5 | 105 | 70 | 101 | 69 | 99 | 68 | 95 | 66 | 74 | 72 | 34 | 26 | 33 | 36 | 600 | 
| Pendleton MCB | 33.3 | 63 | 117.3 | 92 | 68 | 87 | 67 | 85 | 67 | 81 | 66 | 71 | 69 | 22 | 34 | 39 | 41 | 1532 | 
| Pendleton MCB Coast | 33.2 | 24 | 117.4 | 84 | 69 | 80 | 67 | 79 | 67 | 75 | 65 | 70 | 68 | 10 | 39 | 44 | 46 | 1782 | 
| Perris | 33.8 | 1470 | 117.2 | 105 | 70 | 101 | 69 | 100 | 69 | 97 | 68 | 74 | 72 | 39 | 22 | 27 | 30 | 
 | 
| Petaluma FS 2 | 38.2 | 16 | 122.6 | 98 | 69 | 92 | 67 | 90 | 67 | 85 | 66 | 72 | 69 | 31 | 24 | 29 | 32 | 2959 | 
| Pico Rivera | 34 | 180 | 118 | 98 | 70 | 91 | 69 | 89 | 69 | 85 | 67 | 72 | 70 | 24 | 31 | 35 | 38 | 
 | 
| Piedmont | 37.8 | 325 | 122 | 96 | 68 | 89 | 66 | 87 | 65 | 82 | 63 | 70 | 68 | 23 | 31 | 33 | 36 | 
 | 
| Pinnacles NM | 36.5 | 1307 | 121.2 | 98 | 68 | 94 | 67 | 93 | 66 | 89 | 64 | 70 | 68 | 45 | 20 | 26 | 29 | 2956 | 
| Pinole | 38 | 10 | 122.3 | 91 | 66 | 87 | 65 | 86 | 65 | 82 | 64 | 69 | 67 | 25 | 30 | 35 | 38 | 
 | 
| Pismo Beach | 35.1 | 80 | 120.6 | 92 | 66 | 85 | 64 | 84 | 64 | 80 | 62 | 67 | 65 | 16 | 30 | 34 | 37 | 2756 | 
| Pittsburg | 38 | 50 | 121.8 | 102 | 70 | 97 | 68 | 95 | 68 | 90 | 67 | 72 | 70 | 34 | 26 | 32 | 35 | 
 | 
| Placentia | 33.9 | 323 | 118 | 101 | 69 | 93 | 68 | 91 | 68 | 87 | 67 | 73 | 71 | 28 | 30 | 34 | 37 | 
 | 
| Placerville | 38.7 | 1890 | 120.8 | 101 | 67 | 98 | 66 | 97 | 66 | 93 | 65 | 70 | 68 | 42 | 20 | 26 | 29 | 4086 | 
| Placerville IFG | 38.7 | 2755 | 120.8 | 100 | 66 | 97 | 65 | 96 | 65 | 92 | 64 | 69 | 67 | 42 | 23 | 28 | 31 | 
 | 
| Platina | 40.4 | 2260 | 122.9 | 96 | 65 | 92 | 64 | 91 | 63 | 87 | 61 | 67 | 65 | 36 | 13 | 20 | 24 | 
 | 
| Pleasant Hill | 37.9 | 102 | 122 | 96 | 68 | 93 | 67 | 92 | 67 | 88 | 65 | 70 | 68 | 34 | 25 | 30 | 33 | 
 | 
| Pleasanton | 37.6 | 350 | 121.8 | 97 | 68 | 94 | 67 | 93 | 67 | 89 | 65 | 70 | 68 | 35 | 24 | 29 | 32 | 
 | 
| Point Arena | 38.9 | 100 | 123.7 | 76 | 62 | 72 | 60 | 71 | 60 | 67 | 58 | 63 | 61 | 19 | 29 | 32 | 34 | 4747 | 
| Point Arguello | 34.6 | 76 | 120.7 | 75 | 64 | 71 | 63 | 69 | 62 | 65 | 59 | 65 | 63 | 17 | 29 | 32 | 35 | 3826 | 
| Point Mugu | 34.1 | 14 | 119.1 | 88 | 68 | 81 | 67 | 79 | 67 | 75 | 66 | 70 | 68 | 15 | 33 | 37 | 39 | 2328 | 
| Point Piedras Blancas | 35.7 | 59 | 121.3 | 73 | 60 | 67 | 59 | 65 | 59 | 61 | 57 | 62 | 60 | 10 | 36 | 41 | 43 | 3841 | 
| Pomona Cal Poly | 34.1 | 740 | 117.8 | 102 | 70 | 98 | 69 | 97 | 69 | 93 | 67 | 74 | 72 | 36 | 27 | 32 | 35 | 1971 | 
| Port Chicago ND | 38 | 50 | 122 | 98 | 69 | 94 | 68 | 92 | 68 | 88 | 66 | 71 | 69 | 34 | 28 | 33 | 36 | 
 | 
| Port Hueneme | 34.2 | 13 | 119 | 88 | 68 | 81 | 67 | 79 | 67 | 75 | 66 | 70 | 68 | 15 | 33 | 37 | 39 | 2334 | 
| Porterville | 36.1 | 393 | 119 | 106 | 71 | 102 | 70 | 101 | 70 | 97 | 69 | 74 | 72 | 36 | 25 | 30 | 33 | 2456 | 
| Portola | 39.8 | 4850 | 120.5 | 92 | 63 | 89 | 61 | 88 | 61 | 84 | 59 | 65 | 63 | 48 | -9 | -3 | 1 | 7111 | 
| Posey 3 E | 35.8 | 4960 | 119 | 89 | 62 | 86 | 61 | 85 | 61 | 82 | 59 | 65 | 63 | 26 | 9 | 16 | 21 | 
 | 
| Potter Valley PH | 39.4 | 1015 | 123.1 | 101 | 68 | 96 | 67 | 94 | 67 | 89 | 65 | 70 | 68 | 40 | 20 | 26 | 29 | 3276 | 
| Poway Valley | 33 | 500 | 117 | 100 | 70 | 94 | 69 | 93 | 69 | 89 | 68 | 73 | 71 | 26 | 29 | 33 | 35 | 
 | 
| Priest Valley | 36.2 | 2300 | 120.7 | 97 | 66 | 93 | 65 | 92 | 65 | 88 | 63 | 69 | 67 | 34 | 13 | 20 | 24 | 4144 | 
| Prunedale | 36.6 | 260 | 121.7 | 86 | 66 | 83 | 65 | 82 | 64 | 79 | 62 | 68 | 66 | 20 | 26 | 31 | 34 | 1100 | 
| Quartz Hill | 34.6 | 2428 | 118.2 | 106 | 68 | 102 | 67 | 101 | 67 | 98 | 66 | 72 | 70 | 35 | 12 | 17 | 20 | 1455 | 
| Quincy | 39.9 | 3409 | 120.9 | 101 | 64 | 98 | 63 | 97 | 63 | 93 | 62 | 68 | 66 | 45 | 1 | 6 | 13 | 5763 | 
| Ramona Spaulding | 33.1 | 1480 | 116.8 | 103 | 70 | 97 | 69 | 96 | 69 | 92 | 68 | 73 | 71 | 40 | 22 | 28 | 31 | 
 | 
| Rancho Bernardo | 33 | 500 | 117.1 | 96 | 69 | 91 | 68 | 89 | 68 | 85 | 67 | 72 | 70 | 26 | 29 | 34 | 36 | 
 | 
| Rancho Cordova | 38.6 | 190 | 121.3 | 104 | 72 | 100 | 69 | 98 | 69 | 94 | 68 | 74 | 71 | 35 | 26 | 31 | 33 | 
 | 
| Rancho Mirage | 33.8 | 248 | 116.4 | 117 | 74 | 113 | 73 | 112 | 73 | 109 | 72 | 79 | 78 | 33 | 26 | 31 | 34 | 374 | 
| Rancho Palos Verdes | 33.7 | 216 | 118.2 | 92 | 69 | 84 | 68 | 82 | 68 | 78 | 66 | 71 | 69 | 14 | 38 | 43 | 46 | 
 | 
| Rancho San Diego | 32.8 | 300 | 117.0 | 94 | 69 | 86 | 68 | 85 | 68 | 82 | 66 | 71 | 69 | 30 | 34 | 38 | 41 | 404 | 
| Rancho Santa Margarita | 33.6 | 116 | 117.6 | 95 | 67 | 87 | 66 | 85 | 65 | 81 | 63 | 71 | 67 | 22 | 33 | 37 | 40 | 496 | 
| Randsburg | 35.3 | 3570 | 117.7 | 105 | 67 | 102 | 66 | 101 | 66 | 97 | 65 | 70 | 68 | 30 | 19 | 25 | 28 | 2922 | 
| Red Bluff AP | 40.2 | 342 | 122.3 | 107 | 70 | 104 | 69 | 102 | 68 | 98 | 66 | 73 | 71 | 31 | 24 | 29 | 31 | 2688 | 
| Redding FS 4 | 40.6 | 470 | 122.4 | 107 | 69 | 103 | 68 | 101 | 68 | 97 | 67 | 72 | 70 | 30 | 26 | 31 | 34 | 2544 | 
| Redlands | 34.1 | 1318 | 117.2 | 106 | 70 | 102 | 69 | 101 | 69 | 98 | 67 | 74 | 72 | 34 | 27 | 32 | 35 | 1993 | 
| Redondo Beach | 33.8 | 45 | 118.3 | 92 | 69 | 84 | 68 | 82 | 68 | 78 | 66 | 71 | 69 | 12 | 37 | 42 | 44 | 
 | 
| Redwood City | 37.5 | 31 | 122.2 | 90 | 67 | 86 | 66 | 85 | 66 | 81 | 64 | 69 | 67 | 28 | 28 | 33 | 35 | 2599 | 
| Reedley | 36.6 | 344 | 119.7 | 104 | 71 | 101 | 70 | 100 | 70 | 96 | 68 | 74 | 72 | 40 | 24 | 30 | 34 | 
 | 
| Reseda | 34.2 | 736 | 118.5 | 103 | 71 | 98 | 69 | 96 | 69 | 92 | 67 | 74 | 71 | 32 | 28 | 33 | 36 | 664 | 
| Rialto | 34.1 | 1254 | 117 | 105 | 70 | 101 | 69 | 100 | 68 | 96 | 66 | 74 | 72 | 35 | 28 | 33 | 35 | 
 | 
| Richardson Grove | 40 | 500 | 123.8 | 96 | 67 | 92 | 66 | 91 | 66 | 87 | 64 | 69 | 67 | 28 | 25 | 30 | 33 | 
 | 
| Richmond | 37.9 | 55 | 121.6 | 88 | 65 | 84 | 64 | 82 | 64 | 77 | 62 | 67 | 65 | 17 | 31 | 36 | 38 | 2684 | 
| Ridgecrest | 35.6 | 2340 | 117.8 | 110 | 70 | 106 | 68 | 105 | 68 | 102 | 66 | 75 | 71 | 35 | 15 | 22 | 26 | 
 | 
| Rio Del Mar | 37 | 50 | 121.9 | 94 | 67 | 88 | 66 | 87 | 65 | 83 | 63 | 69 | 67 | 30 | 27 | 32 | 35 | 1097 | 
| Rio Linda | 38.6 | 86 | 121.5 | 104 | 72 | 100 | 70 | 98 | 70 | 94 | 68 | 74 | 71 | 32 | 28 | 33 | 35 | 1290 | 
| Ripon | 37.7 | 61 | 121.1 | 102 | 70 | 97 | 68 | 95 | 68 | 91 | 67 | 72 | 70 | 37 | 23 | 30 | 33 | 1240 | 
| Riverbank | 37.7 | 133 | 120.9 | 102 | 73 | 99 | 70 | 98 | 70 | 95 | 68 | 75 | 72 | 36 | 25 | 30 | 33 | 1240 | 
| Riverside Exp Sta | 34 | 986 | 117.4 | 106 | 71 | 102 | 69 | 101 | 69 | 97 | 67 | 75 | 72 | 36 | 29 | 34 | 36 | 
 | 
| Riverside FS 3 | 34 | 840 | 117.4 | 104 | 70 | 100 | 69 | 99 | 68 | 95 | 65 | 74 | 72 | 37 | 27 | 32 | 35 | 1818 | 
| Rocklin | 38.8 | 239 | 121.2 | 108 | 72 | 104 | 70 | 103 | 70 | 99 | 69 | 74 | 72 | 39 | 20 | 26 | 29 | 3143 | 
| Rodeo | 38.1 | 15 | 122.3 | 93 | 67 | 90 | 66 | 88 | 66 | 84 | 64 | 70 | 68 | 23 | 28 | 33 | 36 | 823 | 
| Rohnert Park | 38.4 | 106 | 122.6 | 99 | 69 | 96 | 68 | 95 | 68 | 92 | 66 | 71 | 69 | 33 | 24 | 27 | 29 | 
 | 
| Rolling Hills | 33.6 | 216 | 119 | 92 | 69 | 84 | 68 | 82 | 68 | 78 | 66 | 71 | 69 | 15 | 38 | 43 | 46 | 
 | 
| Rosamond | 34.8 | 2326 | 118.2 | 106 | 68 | 102 | 67 | 101 | 67 | 98 | 66 | 71 | 69 | 35 | 16 | 22 | 26 | 1455 | 
| Roseland | 38.4 | 167 | 122.7 | 99 | 69 | 96 | 68 | 95 | 68 | 92 | 66 | 71 | 69 | 35 | 24 | 27 | 29 | 1249 | 
| Rosemead | 34 | 275 | 118 | 98 | 70 | 90 | 69 | 88 | 69 | 84 | 67 | 72 | 70 | 27 | 30 | 35 | 37 | 
 | 
| Rosemont | 38.3 | 190 | 121.4 | 104 | 71 | 100 | 70 | 98 | 70 | 94 | 68 | 73 | 71 | 32 | 30 | 35 | 37 | 1025 | 
| Roseville | 38.7 | 160 | 121.2 | 105 | 71 | 102 | 70 | 100 | 70 | 96 | 68 | 74 | 71 | 36 | 24 | 30 | 34 | 
 | 
| Rossmoor | 33.8 | 20 | 118.1 | 92 | 67 | 85 | 64 | 83 | 64 | 79 | 62 | 71 | 69 | 19 | 32 | 37 | 39 | 
 | 
| Rowland Hts | 33.9 | 540 | 118 | 99 | 70 | 93 | 69 | 91 | 69 | 86 | 68 | 73 | 71 | 27 | 29 | 34 | 36 | 
 | 
| Rubidoux | 34 | 792 | 117 | 106 | 71 | 102 | 70 | 101 | 70 | 97 | 68 | 75 | 73 | 36 | 27 | 32 | 35 | 
 | 
| Sacramento AP | 38.5 | 17 | 121.5 | 104 | 72 | 100 | 70 | 98 | 70 | 94 | 68 | 74 | 71 | 35 | 26 | 31 | 33 | 2843 | 
| Sacramento CO | 38.6 | 84 | 121.5 | 104 | 71 | 100 | 70 | 98 | 70 | 94 | 68 | 73 | 71 | 32 | 30 | 35 | 37 | 
 | 
| Saint Helena | 38.5 | 225 | 122.5 | 102 | 70 | 98 | 69 | 97 | 69 | 93 | 67 | 72 | 70 | 40 | 22 | 28 | 31 | 2878 | 
| Saint Mary's College | 37.8 | 623 | 122.1 | 98 | 69 | 93 | 68 | 91 | 68 | 86 | 66 | 71 | 69 | 28 | 21 | 27 | 30 | 3543 | 
| Salinas 3 E | 36.7 | 85 | 121.6 | 86 | 66 | 83 | 65 | 82 | 64 | 79 | 62 | 68 | 66 | 20 | 26 | 31 | 34 | 
 | 
| Salinas AP | 36.7 | 69 | 121.6 | 85 | 67 | 82 | 65 | 81 | 64 | 78 | 62 | 69 | 66 | 20 | 28 | 33 | 35 | 2959 | 
| Salt Springs PH | 38.5 | 3700 | 120.2 | 95 | 62 | 92 | 61 | 91 | 61 | 87 | 59 | 66 | 64 | 27 | 19 | 25 | 28 | 3857 | 
| Salyer RS | 40.9 | 623 | 123.6 | 102 | 69 | 95 | 67 | 93 | 66 | 87 | 64 | 70 | 68 | 33 | 22 | 28 | 31 | 
 | 
| San Anselmo | 38 | 50 | 122 | 95 | 67 | 89 | 66 | 87 | 66 | 82 | 65 | 70 | 68 | 32 | 26 | 31 | 33 | 
 | 
| San Antonio Canyon | 34.2 | 2394 | 117.7 | 100 | 68 | 96 | 67 | 94 | 67 | 90 | 65 | 72 | 70 | 33 | 29 | 35 | 39 | 
 | 
| San Antonio Mission | 36 | 1060 | 117.7 | 99 | 69 | 94 | 68 | 92 | 68 | 88 | 67 | 71 | 69 | 28 | 19 | 25 | 28 | 
 | 
| San Bernardino | 34.1 | 1125 | 117.3 | 106 | 70 | 102 | 69 | 101 | 69 | 98 | 68 | 75 | 72 | 39 | 27 | 31 | 33 | 1777 | 
| San Bruno | 37.7 | 20 | 122.4 | 86 | 66 | 80 | 64 | 78 | 64 | 73 | 62 | 67 | 65 | 23 | 30 | 35 | 38 | 3042 | 
| San Carlos | 37.5 | 26 | 122.3 | 92 | 67 | 88 | 65 | 86 | 65 | 82 | 63 | 68 | 66 | 28 | 28 | 33 | 35 | 
 | 
| San Clemente | 33.4 | 208 | 118.6 | 91 | 68 | 85 | 67 | 84 | 67 | 80 | 66 | 71 | 69 | 12 | 31 | 35 | 37 | 
 | 
| San Diego AP | 32.7 | 13 | 117.2 | 88 | 70 | 83 | 69 | 82 | 69 | 78 | 68 | 72 | 70 | 13 | 38 | 42 | 44 | 1507 | 
| San Dimas | 34 | 955 | 118.4 | 102 | 70 | 98 | 69 | 96 | 69 | 92 | 67 | 74 | 72 | 35 | 30 | 35 | 37 | 
 | 
| San Fernando | 34.3 | 977 | 118.5 | 104 | 71 | 99 | 70 | 98 | 70 | 94 | 68 | 74 | 72 | 37 | 30 | 35 | 37 | 1800 | 
| San Francisco AP | 37.6 | 8 | 122.4 | 89 | 66 | 83 | 64 | 80 | 63 | 74 | 61 | 67 | 64 | 20 | 31 | 35 | 38 | 3042 | 
| San Francisco CO | 37.8 | 52 | 122.4 | 84 | 65 | 79 | 63 | 77 | 62 | 71 | 60 | 66 | 63 | 14 | 38 | 41 | 44 | 3080 | 
| San Gabriel FD | 34.1 | 450 | 118.1 | 99 | 70 | 94 | 69 | 92 | 69 | 88 | 68 | 73 | 71 | 30 | 30 | 35 | 37 | 1532 | 
| San Gregorio 2 SE | 37.3 | 275 | 122.4 | 87 | 66 | 81 | 63 | 79 | 63 | 74 | 61 | 68 | 65 | 30 | 27 | 32 | 35 | 
 | 
| San Jacinto | 33.8 | 1535 | 117 | 110 | 70 | 105 | 69 | 104 | 69 | 102 | 68 | 75 | 73 | 41 | 20 | 26 | 29 | 2376 | 
| San Jose | 37.4 | 67 | 121.9 | 94 | 68 | 86 | 66 | 84 | 66 | 78 | 64 | 70 | 68 | 26 | 29 | 34 | 36 | 2438 | 
| San Leandro | 37.7 | 45 | 122.2 | 89 | 67 | 83 | 64 | 81 | 64 | 76 | 62 | 69 | 66 | 22 | 28 | 33 | 35 | 
 | 
| San Lorenzo | 37.7 | 45 | 122.1 | 89 | 67 | 83 | 64 | 81 | 64 | 76 | 62 | 69 | 66 | 23 | 28 | 33 | 36 | 
 | 
| San Luis Dam | 37.1 | 277 | 121.1 | 97 | 68 | 91 | 66 | 90 | 66 | 86 | 64 | 70 | 68 | 32 | 25 | 30 | 33 | 
 | 
| San Luis Obispo | 35.3 | 320 | 120.7 | 94 | 63 | 87 | 63 | 85 | 63 | 81 | 62 | 67 | 65 | 26 | 30 | 33 | 35 | 2498 | 
| San Marcos | 33.1 | 567 | 117.2 | 97 | 69 | 98 | 68 | 94 | 68 | 84 | 67 | 72 | 70 | 29 | 26 | 31 | 34 | 662 | 
| San Marino | 34.2 | 300 | 118.1 | 100 | 69 | 95 | 68 | 93 | 68 | 88 | 66 | 73 | 71 | 28 | 30 | 35 | 37 | 
 | 
| San Mateo | 37.5 | 21 | 122.3 | 92 | 67 | 84 | 65 | 82 | 65 | 76 | 63 | 68 | 66 | 24 | 31 | 36 | 38 | 2655 | 
| San Nicholas Island | 33.2 | 504 | 119.5 | 85 | 66 | 78 | 65 | 76 | 65 | 70 | 64 | 69 | 67 | 11 | 39 | 43 | 45 | 2454 | 
| San Pablo | 37.6 | 30 | 122.3 | 90 | 65 | 84 | 63 | 82 | 63 | 77 | 61 | 69 | 66 | 17 | 29 | 34 | 37 | 
 | 
| San Pedro | 33.7 | 10 | 118.3 | 92 | 69 | 84 | 68 | 82 | 68 | 78 | 66 | 72 | 70 | 13 | 35 | 31 | 34 | 1819 | 
| San Rafael | 38 | 40 | 122.6 | 96 | 67 | 90 | 65 | 88 | 65 | 83 | 63 | 71 | 68 | 29 | 30 | 35 | 37 | 2440 | 
| San Ramon | 37.7 | 360 | 122 | 99 | 69 | 93 | 67 | 91 | 67 | 86 | 65 | 70 | 68 | 35 | 24 | 29 | 32 | 1369 | 
| Sandberg | 34.8 | 4517 | 118.7 | 95 | 63 | 91 | 61 | 90 | 61 | 87 | 59 | 67 | 65 | 32 | 17 | 21 | 24 | 4427 | 
| Sanger | 36.7 | 364 | 119.6 | 105 | 72 | 101 | 70 | 100 | 70 | 96 | 68 | 74 | 72 | 37 | 24 | 30 | 34 | 
 | 
| Santa Ana FS | 33.8 | 115 | 117.8 | 98 | 70 | 91 | 68 | 89 | 68 | 84 | 67 | 72 | 70 | 26 | 33 | 35 | 38 | 1430 | 
| Santa Barbara AP | 34.4 | 9 | 119.8 | 90 | 69 | 83 | 67 | 81 | 67 | 77 | 65 | 70 | 68 | 20 | 29 | 34 | 36 | 2487 | 
| Santa Barbara CO | 34.4 | 5 | 119.7 | 91 | 69 | 84 | 67 | 82 | 67 | 78 | 65 | 70 | 68 | 22 | 33 | 38 | 40 | 1994 | 
| Santa Clara Univ | 37.4 | 88 | 121.9 | 90 | 67 | 87 | 65 | 86 | 65 | 82 | 63 | 69 | 67 | 30 | 29 | 34 | 36 | 2566 | 
| Santa Clarita | 34.4 | 1300 | 118.5 | 103 | 71 | 98 | 70 | 97 | 70 | 93 | 68 | 74 | 72 | 36 | 30 | 35 | 37 | 
 | 
| Santa Cruz | 37 | 125 | 122 | 94 | 68 | 88 | 66 | 86 | 66 | 81 | 64 | 69 | 67 | 28 | 27 | 32 | 35 | 3136 | 
| Santa Fe Springs | 33.9 | 280 | 118.1 | 99 | 69 | 90 | 68 | 88 | 68 | 84 | 67 | 72 | 70 | 24 | 31 | 36 | 38 | 
 | 
| Santa Maria AP | 34.9 | 236 | 120.5 | 90 | 66 | 83 | 64 | 82 | 63 | 78 | 61 | 67 | 65 | 23 | 25 | 31 | 33 | 3053 | 
| Santa Monica | 34 | 15 | 118.5 | 85 | 67 | 78 | 66 | 76 | 66 | 72 | 64 | 69 | 67 | 15 | 39 | 44 | 46 | 1873 | 
| Santa Paula | 34.4 | 263 | 119.1 | 101 | 71 | 94 | 70 | 92 | 70 | 87 | 68 | 73 | 71 | 28 | 28 | 33 | 35 | 2030 | 
| Santa Rosa | 38.5 | 167 | 122.8 | 99 | 69 | 96 | 68 | 95 | 68 | 92 | 66 | 71 | 69 | 35 | 24 | 27 | 29 | 2980 | 
| Santee | 32.8 | 400 | 117 | 96 | 69 | 91 | 68 | 90 | 68 | 87 | 67 | 72 | 70 | 20 | 25 | 30 | 33 | 
 | 
| Saratoga | 37.3 | 500 | 122 | 96 | 67 | 88 | 66 | 86 | 66 | 80 | 65 | 70 | 68 | 31 | 27 | 32 | 35 | 
 | 
| Sausalito | 37.9 | 10 | 122.5 | 85 | 66 | 80 | 65 | 78 | 65 | 73 | 63 | 67 | 65 | 12 | 30 | 34 | 36 | 
 | 
| Sawyer's Bar RS | 41.3 | 2169 | 123.1 | 100 | 66 | 95 | 65 | 93 | 64 | 88 | 62 | 68 | 66 | 38 | 14 | 21 | 25 | 4102 | 
| Scotia | 40.5 | 139 | 124.4 | 78 | 61 | 74 | 60 | 73 | 60 | 69 | 58 | 63 | 61 | 19 | 28 | 33 | 35 | 3954 | 
| Scotts Valley | 37 | 400 | 122 | 94 | 68 | 88 | 66 | 86 | 66 | 81 | 64 | 69 | 67 | 28 | 27 | 32 | 35 | 1097 | 
| Seal Beach | 33.8 | 21 | 118.1 | 94 | 69 | 86 | 68 | 84 | 67 | 80 | 65 | 71 | 69 | 15 | 35 | 40 | 42 | 1519 | 
| Seaside | 36.6 | 17 | 122.9 | 85 | 66 | 79 | 64 | 77 | 64 | 73 | 62 | 67 | 65 | 20 | 30 | 35 | 37 | 
 | 
| Sebastapol | 38.4 | 102 | 122.8 | 99 | 69 | 96 | 68 | 95 | 68 | 92 | 66 | 71 | 69 | 35 | 24 | 27 | 29 | 1249 | 
| Selma | 36.6 | 305 | 119.6 | 104 | 73 | 101 | 71 | 100 | 70 | 97 | 68 | 75 | 73 | 38 | 24 | 30 | 34 | 
 | 
| Sepulveda | 34.2 | 818 | 118.5 | 103 | 71 | 98 | 69 | 96 | 69 | 92 | 67 | 74 | 71 | 32 | 28 | 33 | 36 | 664 | 
| Shafter | 35.5 | 345 | 119.2 | 106 | 71 | 102 | 70 | 101 | 70 | 98 | 68 | 74 | 72 | 28 | 24 | 29 | 32 | 2185 | 
| Shasta Dam | 40.7 | 1076 | 122.4 | 105 | 69 | 101 | 68 | 99 | 68 | 95 | 67 | 72 | 70 | 27 | 29 | 34 | 36 | 2943 | 
| Shelter Cove | 40 | 110 | 124.1 | 80 | 61 | 73 | 60 | 72 | 59 | 68 | 57 | 63 | 61 | 15 | 34 | 39 | 41 | 
 | 
| Sherman Oaks | 34.2 | 657 | 118.5 | 103 | 71 | 98 | 69 | 96 | 69 | 92 | 67 | 74 | 71 | 28 | 29 | 34 | 37 | 664 | 
| Sierra City | 39.6 | 4230 | 120.1 | 96 | 62 | 93 | 61 | 92 | 61 | 89 | 59 | 66 | 64 | 43 | 12 | 19 | 24 | 
 | 
| Sierra Madre | 34.2 | 1153 | 118.1 | 102 | 69 | 96 | 68 | 94 | 68 | 90 | 67 | 73 | 71 | 27 | 32 | 37 | 39 | 
 | 
| Sierraville RS | 39.6 | 4975 | 120.4 | 94 | 60 | 91 | 59 | 90 | 59 | 86 | 57 | 64 | 62 | 44 | -10 | -4 | 0 | 6893 | 
| Signal Hill | 33.5 | 100 | 118.2 | 99 | 70 | 90 | 69 | 88 | 68 | 84 | 66 | 72 | 70 | 19 | 35 | 39 | 42 | 
 | 
| Simi Valley | 34.4 | 500 | 118.8 | 98 | 70 | 93 | 68 | 91 | 68 | 87 | 66 | 73 | 71 | 30 | 28 | 33 | 35 | 
 | 
| Solana Beach | 33 | 15 | 117.3 | 87 | 68 | 83 | 67 | 81 | 67 | 77 | 65 | 70 | 68 | 10 | 35 | 39 | 41 | 
 | 
| Soledad | 36.4 | 200 | 121.3 | 90 | 67 | 87 | 65 | 86 | 65 | 82 | 64 | 70 | 67 | 23 | 24 | 29 | 32 | 1020 | 
| Sonoma | 38.3 | 70 | 122.5 | 101 | 70 | 96 | 69 | 94 | 69 | 90 | 67 | 72 | 70 | 40 | 22 | 28 | 31 | 2998 | 
| Sonora RS | 38 | 1749 | 120.4 | 103 | 68 | 100 | 67 | 99 | 67 | 95 | 66 | 72 | 70 | 34 | 20 | 26 | 29 | 3537 | 
| Soquel | 37 | 50 | 122 | 94 | 67 | 88 | 66 | 86 | 65 | 81 | 63 | 69 | 67 | 24 | 27 | 32 | 35 | 1097 | 
| South El Monte | 34 | 270 | 118.1 | 101 | 72 | 97 | 70 | 95 | 70 | 91 | 68 | 74 | 72 | 28 | 31 | 36 | 38 | 
 | 
| South Entr Yosemite | 37.5 | 5120 | 119.6 | 92 | 61 | 88 | 60 | 87 | 60 | 84 | 59 | 64 | 62 | 36 | 8 | 15 | 20 | 5789 | 
| South Gate | 33.9 | 120 | 118.2 | 97 | 70 | 90 | 69 | 88 | 69 | 84 | 67 | 72 | 70 | 21 | 32 | 37 | 39 | 
 | 
| South Laguna | 33.6 | 100 | 117.7 | 91 | 69 | 83 | 68 | 82 | 68 | 78 | 66 | 71 | 69 | 18 | 30 | 33 | 36 | 586 | 
| South Lake Tahoe | 38.9 | 6200 | 120 | 85 | 56 | 82 | 55 | 79 | 55 | 71 | 54 | 60 | 58 | 33 | -2 | 3 | 10 | 
 | 
| South Oroville | 39.5 | 174 | 121.6 | 106 | 71 | 104 | 70 | 102 | 70 | 98 | 69 | 74 | 72 | 37 | 25 | 30 | 33 | 1385 | 
| South Pasadena | 34 | 657 | 118.2 | 99 | 69 | 94 | 68 | 92 | 68 | 88 | 67 | 73 | 71 | 30 | 31 | 36 | 38 | 
 | 
| South San Francisco | 37.7 | 10 | 122.4 | 87 | 67 | 81 | 64 | 78 | 64 | 72 | 62 | 68 | 65 | 20 | 32 | 36 | 38 | 
 | 
| South San Gabriel | 34.1 | 450 | 118.1 | 99 | 70 | 94 | 69 | 92 | 69 | 88 | 68 | 73 | 71 | 73 | 30 | 35 | 37 | 431 | 
| South Whittier | 33.9 | 300 | 118 | 100 | 70 | 92 | 69 | 90 | 69 | 84 | 68 | 73 | 71 | 30 | 31 | 36 | 38 | 
 | 
| South Yuba City | 39.1 | 59 | 121.6 | 105 | 69 | 101 | 69 | 100 | 69 | 96 | 68 | 72 | 71 | 36 | 24 | 29 | 32 | 1160 | 
| Spring Valley | 32.7 | 300 | 117 | 94 | 69 | 86 | 68 | 85 | 68 | 82 | 66 | 71 | 69 | 30 | 34 | 38 | 41 | 
 | 
| Squaw Valley | 39.2 | 6235 | 120.2 | 88 | 57 | 85 | 56 | 84 | 56 | 80 | 54 | 61 | 59 | 40 | -10 | -4 | 0 | 
 | 
| Squirrel Inn | 34.2 | 5680 | 117.2 | 86 | 61 | 82 | 60 | 81 | 60 | 77 | 58 | 65 | 63 | 23 | 12 | 18 | 22 | 5175 | 
| Stanford | 37.5 | 23 | 122.1 | 93 | 66 | 85 | 64 | 83 | 64 | 77 | 62 | 68 | 66 | 25 | 26 | 31 | 34 | 1103 | 
| Stanton | 33.6 | 45 | 118 | 98 | 69 | 91 | 68 | 89 | 68 | 84 | 67 | 72 | 70 | 24 | 31 | 36 | 38 | 
 | 
| Stockton AP | 37.9 | 22 | 121.3 | 103 | 71 | 98 | 69 | 97 | 69 | 93 | 67 | 73 | 71 | 35 | 24 | 28 | 30 | 2806 | 
| Stockton FS 4 | 38 | 12 | 121.3 | 101 | 70 | 96 | 68 | 95 | 68 | 91 | 67 | 72 | 70 | 37 | 24 | 28 | 30 | 2846 | 
| Stony Gorge Res | 39.6 | 791 | 122.5 | 104 | 70 | 99 | 69 | 97 | 69 | 93 | 67 | 72 | 70 | 37 | 21 | 27 | 30 | 3149 | 
| Strawberry Valley | 39.6 | 3808 | 121.1 | 96 | 63 | 93 | 62 | 92 | 62 | 88 | 60 | 66 | 64 | 32 | 14 | 21 | 25 | 5120 | 
| Studio City | 34.3 | 620 | 118.4 | 102 | 70 | 97 | 69 | 95 | 69 | 91 | 67 | 73 | 71 | 31 | 28 | 33 | 36 | 664 | 
| Suisun City | 38.2 | 72 | 122 | 103 | 71 | 98 | 69 | 96 | 68 | 91 | 66 | 73 | 70 | 35 | 24 | 29 | 32 | 1299 | 
| Sun City | 33.7 | 1420 | 117.2 | 105 | 70 | 101 | 69 | 100 | 69 | 97 | 68 | 74 | 72 | 39 | 22 | 27 | 30 | 827 | 
| Sunland | 34.3 | 1460 | 118.3 | 107 | 71 | 102 | 70 | 100 | 70 | 96 | 68 | 74 | 72 | 36 | 28 | 33 | 36 | 
 | 
| Sunnyvale | 37.3 | 97 | 122 | 96 | 68 | 88 | 66 | 86 | 66 | 80 | 64 | 70 | 68 | 26 | 29 | 34 | 36 | 2511 | 
| Susanville AP | 40.4 | 4148 | 120.6 | 98 | 62 | 95 | 61 | 94 | 61 | 90 | 59 | 66 | 64 | 38 | -1 | 4 | 11 | 6233 | 
| Taft | 35.1 | 987 | 119.5 | 106 | 71 | 102 | 70 | 101 | 70 | 98 | 68 | 74 | 72 | 34 | 26 | 31 | 35 | 934 | 
| Tahoe City | 39.2 | 6230 | 120.1 | 84 | 56 | 81 | 55 | 80 | 55 | 76 | 53 | 60 | 58 | 36 | 2 | 7 | 14 | 8085 | 
| Tahoe Valley AP | 38.9 | 6254 | 120.0 | 85 | 56 | 82 | 55 | 81 | 55 | 77 | 53 | 60 | 58 | 38 | -5 | 2 | 6 | 
 | 
| Tamalpais-Homestead Valley | 37.9 | 25 | 122.5 | 97 | 68 | 91 | 66 | 89 | 66 | 84 | 64 | 70 | 68 | 28 | 28 | 33 | 35 | 874 | 
| Tarzana | 34.2 | 800 | 118.6 | 104 | 71 | 99 | 69 | 97 | 69 | 93 | 68 | 74 | 71 | 27 | 27 | 32 | 35 | 664 | 
| Tehachapi | 35.1 | 3975 | 118.5 | 97 | 66 | 93 | 65 | 92 | 65 | 89 | 64 | 69 | 67 | 33 | 13 | 20 | 24 | 4494 | 
| Tejon Rancho | 35 | 1425 | 118.8 | 107 | 71 | 103 | 70 | 102 | 70 | 99 | 68 | 74 | 72 | 27 | 24 | 29 | 32 | 2602 | 
| Temecula | 33.5 | 1006 | 117.2 | 101 | 69 | 96 | 68 | 95 | 68 | 91 | 67 | 73 | 71 | 34 | 24 | 29 | 32 | 
 | 
| Temple City | 34.1 | 403 | 118.1 | 101 | 70 | 95 | 69 | 93 | 69 | 89 | 68 | 73 | 71 | 27 | 30 | 35 | 37 | 
 | 
| Termo | 40.9 | 5300 | 120.5 | 95 | 60 | 92 | 59 | 91 | 59 | 87 | 57 | 64 | 62 | 37 | -17 | -11 | -4 | 
 | 
| Thermal AP | 33.6 | -112 | 116.1 | 114 | 74 | 110 | 74 | 109 | 74 | 106 | 74 | 80 | 79 | 29 | 26 | 31 | 35 | 1154 | 
| Thermalito | 37.9 | 25 | 121.6 | 106 | 71 | 104 | 70 | 102 | 70 | 98 | 69 | 74 | 72 | 37 | 25 | 30 | 33 | 
 | 
| Thousand Oaks | 34.2 | 810 | 118.8 | 98 | 69 | 93 | 68 | 92 | 68 | 88 | 67 | 72 | 70 | 30 | 27 | 32 | 35 | 
 | 
| Three Rivers PH 1 | 36.5 | 1140 | 118.9 | 105 | 70 | 102 | 69 | 101 | 69 | 98 | 67 | 73 | 71 | 38 | 24 | 30 | 32 | 2642 | 
| Tiburon | 37.9 | 90 | 122.5 | 85 | 66 | 80 | 65 | 78 | 65 | 73 | 63 | 67 | 65 | 12 | 30 | 34 | 36 | 
 | 
| Tiger Creek PH | 38.5 | 2355 | 120.5 | 100 | 66 | 96 | 65 | 95 | 65 | 92 | 63 | 69 | 67 | 36 | 20 | 26 | 29 | 3795 | 
| Torrance | 33.8 | 110 | 118.3 | 93 | 69 | 86 | 68 | 84 | 68 | 80 | 66 | 71 | 69 | 18 | 32 | 37 | 39 | 1859 | 
| Tracy Carbona | 37.7 | 140 | 121.4 | 102 | 70 | 97 | 68 | 95 | 68 | 90 | 67 | 72 | 70 | 38 | 24 | 29 | 32 | 2704 | 
| Tracy Pumps | 37.8 | 61 | 121.4 | 104 | 71 | 99 | 69 | 97 | 69 | 92 | 68 | 73 | 71 | 39 | 23 | 28 | 31 | 
 | 
| Travis AFB | 38.3 | 72 | 121.9 | 103 | 71 | 98 | 69 | 96 | 68 | 91 | 66 | 73 | 70 | 35 | 24 | 29 | 32 | 2725 | 
| Trinity Dam | 40.8 | 2500 | 122.8 | 99 | 65 | 94 | 64 | 92 | 64 | 88 | 62 | 68 | 66 | 37 | 17 | 24 | 28 | 
 | 
| Trona | 35.8 | 1695 | 117.4 | 113 | 72 | 109 | 70 | 108 | 70 | 105 | 68 | 76 | 73 | 35 | 18 | 24 | 27 | 2415 | 
| Truckee RS | 39.3 | 5995 | 120.2 | 90 | 58 | 87 | 57 | 86 | 57 | 82 | 55 | 62 | 60 | 40 | -10 | -4 | 0 | 8230 | 
| Tujunga | 34.3 | 1820 | 118.3 | 103 | 70 | 99 | 69 | 98 | 69 | 94 | 67 | 73 | 71 | 36 | 20 | 26 | 29 | 
 | 
| Tulare | 36.2 | 290 | 119.4 | 105 | 72 | 101 | 71 | 100 | 71 | 96 | 69 | 74 | 72 | 39 | 24 | 30 | 34 | 
 | 
| Tulelake | 42 | 4035 | 121.5 | 92 | 60 | 88 | 59 | 87 | 59 | 83 | 57 | 63 | 61 | 41 | -5 | 0 | 6 | 6854 | 
| Turlock | 37.5 | 100 | 120.9 | 104 | 72 | 100 | 70 | 99 | 70 | 95 | 68 | 74 | 72 | 40 | 24 | 30 | 34 | 
 | 
| Turntable Creek | 40.8 | 1067 | 120.9 | 105 | 69 | 101 | 68 | 99 | 68 | 95 | 66 | 72 | 70 | 28 | 24 | 29 | 32 | 
 | 
| Tustin Foothills | 33.8 | 500 | 117.8 | 99 | 71 | 92 | 69 | 90 | 69 | 85 | 68 | 73 | 71 | 27 | 28 | 31 | 34 | 550 | 
| Tustin Irvine Rch | 33.7 | 118 | 117.8 | 99 | 71 | 92 | 69 | 90 | 69 | 85 | 68 | 73 | 71 | 27 | 28 | 31 | 34 | 1856 | 
| Twentynine Palms | 34.1 | 1975 | 116.1 | 110 | 71 | 107 | 70 | 106 | 70 | 103 | 69 | 76 | 74 | 31 | 21 | 26 | 29 | 1973 | 
| Twin Lakes | 38.7 | 7829 | 119.1 | 73 | 49 | 64 | 47 | 62 | 47 | 57 | 46 | 53 | 50 | 30 | -7 | -2 | 4 | 9196 | 
| Twitchell Dam | 35 | 582 | 120.3 | 99 | 70 | 93 | 68 | 92 | 68 | 88 | 66 | 71 | 69 | 26 | 26 | 31 | 34 | 
 | 
| UCLA | 34.1 | 430 | 118.4 | 93 | 69 | 86 | 68 | 84 | 68 | 80 | 66 | 71 | 69 | 20 | 39 | 43 | 46 | 1509 | 
| Ukiah | 39.2 | 623 | 123.2 | 100 | 70 | 97 | 69 | 96 | 69 | 92 | 68 | 72 | 71 | 42 | 22 | 28 | 31 | 2958 | 
| Union City | 37.6 | 5 | 122.1 | 90 | 67 | 87 | 66 | 85 | 65 | 81 | 63 | 69 | 67 | 20 | 25 | 30 | 33 | 
 | 
| Upland | 34.1 | 1605 | 117.7 | 102 | 69 | 98 | 68 | 96 | 68 | 92 | 66 | 73 | 71 | 31 | 29 | 34 | 36 | 2175 | 
| Upper Lake RS | 39.2 | 1347 | 123 | 98 | 68 | 95 | 67 | 94 | 66 | 91 | 64 | 73 | 71 | 39 | 18 | 34 | 36 | 
 | 
| Upper San Leandro | 37.8 | 394 | 122.1 | 93 | 67 | 87 | 66 | 85 | 65 | 80 | 63 | 69 | 67 | 22 | 28 | 33 | 35 | 
 | 
| Vacaville | 38.4 | 105 | 122 | 103 | 71 | 100 | 70 | 98 | 70 | 94 | 68 | 73 | 71 | 40 | 23 | 28 | 31 | 2788 | 
| Valinda | 34 | 340 | 117.9 | 102 | 70 | 98 | 69 | 96 | 69 | 92 | 68 | 74 | 72 | 28 | 31 | 36 | 38 | 
 | 
| Valle Vista | 33.8 | 1655 | 116.9 | 109 | 70 | 104 | 69 | 103 | 69 | 101 | 67 | 74 | 72 | 40 | 20 | 25 | 28 | 
 | 
| Vallejo | 38.1 | 85 | 122.3 | 93 | 67 | 90 | 66 | 88 | 66 | 84 | 64 | 70 | 68 | 23 | 28 | 33 | 36 | 
 | 
| Valyermo RS | 34.5 | 3600 | 117.9 | 100 | 67 | 96 | 66 | 95 | 66 | 91 | 65 | 70 | 68 | 41 | 12 | 19 | 24 | 3870 | 
| Van Nuys | 34.2 | 708 | 118.5 | 103 | 71 | 98 | 69 | 96 | 69 | 92 | 67 | 74 | 71 | 30 | 28 | 33 | 39 | 664 | 
| Vandenburg AFB | 34.7 | 368 | 122.8 | 85 | 62 | 77 | 61 | 75 | 61 | 71 | 60 | 64 | 62 | 16 | 30 | 35 | 37 | 3451 | 
| Ventura | 34.3 | 341 | 119.3 | 89 | 68 | 82 | 67 | 80 | 67 | 76 | 66 | 70 | 68 | 15 | 29 | 34 | 36 | 
 | 
| Victorville Pumps | 34.5 | 2858 | 117.3 | 105 | 67 | 101 | 65 | 100 | 64 | 97 | 62 | 70 | 68 | 39 | 14 | 24 | 27 | 3191 | 
| View Park | 34 | 300 | 118.3 | 95 | 69 | 88 | 68 | 85 | 68 | 78 | 66 | 71 | 69 | 18 | 36 | 40 | 43 | 
 | 
| Villa Park | 33.8 | 300 | 117.8 | 99 | 70 | 92 | 68 | 90 | 68 | 85 | 67 | 72 | 70 | 27 | 33 | 37 | 40 | 550 | 
| Vincent | 34.5 | 3135 | 118.1 | 105 | 67 | 101 | 65 | 100 | 65 | 96 | 64 | 71 | 69 | 33 | 10 | 18 | 22 | 1455 | 
| Visalia | 36.3 | 325 | 119.3 | 103 | 71 | 100 | 70 | 99 | 70 | 96 | 69 | 73 | 72 | 38 | 25 | 30 | 33 | 2459 | 
| Vista | 33.2 | 510 | 117.2 | 96 | 69 | 90 | 68 | 89 | 68 | 85 | 67 | 72 | 70 | 16 | 30 | 35 | 37 | 
 | 
| Volta PH | 40.5 | 2220 | 120.9 | 101 | 66 | 98 | 65 | 97 | 65 | 93 | 63 | 69 | 67 | 33 | 21 | 27 | 30 | 
 | 
| Walnut | 34 | 550 | 117.9 | 101 | 70 | 97 | 69 | 96 | 69 | 92 | 69 | 74 | 72 | 30 | 28 | 33 | 35 | 
 | 
| Walnut Creek | 37.9 | 245 | 122.1 | 100 | 69 | 94 | 67 | 92 | 67 | 87 | 66 | 71 | 69 | 32 | 23 | 29 | 31 | 
 | 
| Walnut Grove | 38.2 | 23 | 121.5 | 102 | 70 | 98 | 69 | 96 | 69 | 92 | 68 | 72 | 71 | 37 | 24 | 30 | 32 | 
 | 
| Walnut Park | 33.9 | 45 | 118.2 | 92 | 69 | 84 | 68 | 82 | 68 | 78 | 66 | 71 | 69 | 12 | 37 | 42 | 44 | 450 | 
| Warner Springs | 33.3 | 3180 | 116.6 | 100 | 67 | 95 | 66 | 94 | 66 | 91 | 65 | 71 | 69 | 40 | 15 | 22 | 26 | 3591 | 
| Wasco | 35.6 | 333 | 119.3 | 105 | 71 | 101 | 70 | 100 | 70 | 97 | 68 | 74 | 72 | 36 | 23 | 28 | 31 | 2466 | 
| Watsonville | 36.9 | 95 | 121.8 | 86 | 66 | 82 | 64 | 81 | 63 | 79 | 61 | 68 | 65 | 22 | 28 | 33 | 35 | 3418 | 
| Weaverville RS | 40.7 | 2050 | 122.9 | 100 | 67 | 95 | 66 | 93 | 65 | 89 | 63 | 69 | 67 | 46 | 10 | 17 | 22 | 4992 | 
| Weed FD | 41.4 | 3590 | 122.4 | 92 | 63 | 89 | 62 | 88 | 61 | 84 | 59 | 65 | 63 | 35 | 4 | 12 | 17 | 
 | 
| West Athens | 33.9 | 25 | 118.3 | 92 | 69 | 85 | 68 | 84 | 68 | 80 | 66 | 71 | 69 | 18 | 32 | 37 | 39 | 450 | 
| West Carson | 33.8 | 100 | 118.3 | 92 | 69 | 87 | 68 | 85 | 68 | 81 | 66 | 71 | 69 | 18 | 32 | 37 | 39 | 
 | 
| West Compton | 33.9 | 71 | 118.3 | 97 | 69 | 90 | 68 | 88 | 68 | 83 | 67 | 72 | 70 | 21 | 33 | 37 | 39 | 450 | 
| West Covina | 34 | 365 | 117.9 | 102 | 70 | 98 | 69 | 96 | 69 | 92 | 68 | 74 | 72 | 34 | 29 | 34 | 36 | 
 | 
| West Hollywood | 34 | 290 | 118.4 | 95 | 70 | 89 | 69 | 87 | 69 | 82 | 67 | 72 | 70 | 20 | 38 | 42 | 45 | 
 | 
| West Pittsburg | 38 | 12 | 121.9 | 102 | 70 | 97 | 68 | 95 | 68 | 90 | 67 | 72 | 70 | 34 | 26 | 32 | 35 | 
 | 
| West Puente Valley | 34 | 500 | 117.9 | 101 | 71 | 97 | 70 | 95 | 70 | 91 | 68 | 73 | 71 | 26 | 31 | 36 | 39 | 
 | 
| West Sacramento | 38.6 | 19 | 121.5 | 104 | 72 | 100 | 70 | 98 | 70 | 94 | 68 | 74 | 71 | 35 | 26 | 31 | 33 | 1290 | 
| West Whittier-Los Nietos | 34 | 320 | 118.1 | 99 | 69 | 90 | 68 | 88 | 68 | 84 | 67 | 72 | 70 | 24 | 31 | 35 | 38 | 
 | 
| Westlake Village | 34.2 | 750 | 118.8 | 103 | 71 | 99 | 70 | 98 | 70 | 94 | 69 | 73 | 71 | 26 | 26 | 30 | 33 | 
 | 
| Westminster | 33.8 | 38 | 118 | 95 | 70 | 88 | 68 | 86 | 68 | 81 | 67 | 72 | 70 | 23 | 33 | 38 | 41 | 
 | 
| Westmont | 33.9 | 110 | 118.3 | 96 | 70 | 89 | 69 | 87 | 69 | 83 | 67 | 72 | 70 | 20 | 36 | 41 | 44 | 400 | 
| Whiskeytown Res | 40.6 | 1295 | 122.6 | 105 | 69 | 101 | 68 | 100 | 68 | 96 | 67 | 72 | 70 | 31 | 25 | 30 | 33 | 
 | 
| White Mtn 1 | 37.5 | 10150 | 119.3 | 73 | 49 | 69 | 47 | 68 | 47 | 65 | 45 | 53 | 50 | 37 | -15 | -9 | -6 | 
 | 
| White Mtn 2 | 37.6 | 12470 | 119.3 | 61 | 42 | 58 | 41 | 57 | 41 | 54 | 40 | 46 | 43 | 38 | -20 | -15 | -12 | 
 | 
| Whittier | 34 | 320 | 118 | 99 | 69 | 90 | 68 | 88 | 68 | 84 | 67 | 72 | 70 | 24 | 31 | 35 | 38 | 
 | 
| Wildomar | 33.6 | 1255 | 117.3 | 103 | 70 | 99 | 69 | 98 | 69 | 94 | 68 | 74 | 72 | 36 | 23 | 28 | 30 | 827 | 
| Wildrose RS | 36.3 | 4100 | 
 | 100 | 64 | 97 | 63 | 96 | 63 | 93 | 61 | 68 | 66 | 33 | 13 | 20 | 24 | 
 | 
| Williams | 39.2 | 85 | 122.2 | 104 | 71 | 100 | 70 | 98 | 70 | 94 | 68 | 73 | 71 | 36 | 24 | 29 | 32 | 
 | 
| Willits | 39.4 | 1350 | 123.3 | 95 | 66 | 89 | 65 | 87 | 64 | 82 | 62 | 68 | 66 | 38 | 18 | 24 | 27 | 
 | 
| Willow Brook | 33.9 | 60 | 118.2 | 97 | 70 | 90 | 69 | 88 | 69 | 83 | 67 | 72 | 70 | 21 | 35 | 39 | 42 | 
 | 
| Willow Creek | 41 | 461 | 123 | 104 | 70 | 98 | 68 | 96 | 68 | 92 | 66 | 71 | 69 | 35 | 22 | 28 | 31 | 
 | 
| Willows | 39.5 | 140 | 122.2 | 104 | 71 | 100 | 70 | 98 | 70 | 94 | 68 | 73 | 71 | 36 | 22 | 28 | 31 | 2836 | 
| Windsor | 38.5 | 130 | 122.8 | 99 | 69 | 96 | 68 | 95 | 68 | 92 | 66 | 71 | 69 | 35 | 24 | 27 | 29 | 1249 | 
| Winters | 38.5 | 135 | 122 | 104 | 71 | 99 | 70 | 97 | 70 | 93 | 68 | 73 | 71 | 38 | 24 | 29 | 32 | 2593 | 
| Winton | 37.4 | 168 | 120.6 | 103 | 71 | 100 | 69 | 99 | 69 | 95 | 67 | 73 | 71 | 36 | 21 | 27 | 30 | 1244 | 
| Woodcrest | 33.9 | 1500 | 117.4 | 104 | 70 | 100 | 69 | 99 | 68 | 95 | 65 | 74 | 72 | 37 | 27 | 32 | 35 | 611 | 
| Woodfords | 38.8 | 5671 | 119.8 | 92 | 59 | 89 | 58 | 88 | 58 | 84 | 56 | 63 | 61 | 32 | 0 | 5 | 12 | 6047 | 
| Woodlake | 36.3 | 500 | 119.1 | 103 | 71 | 100 | 70 | 99 | 70 | 96 | 69 | 73 | 72 | 38 | 25 | 30 | 33 | 1130 | 
| Woodland | 38.7 | 69 | 121.8 | 106 | 72 | 101 | 71 | 100 | 71 | 96 | 69 | 74 | 72 | 40 | 25 | 30 | 33 | 2708 | 
| Woodland Hills | 34.2 | 944 | 118.6 | 104 | 71 | 99 | 70 | 97 | 70 | 93 | 68 | 74 | 72 | 32 | 26 | 31 | 34 | 664 | 
| Woodside | 37.5 | 75 | 122.3 | 92 | 67 | 84 | 66 | 82 | 65 | 76 | 63 | 69 | 67 | 24 | 22 | 28 | 31 | 
 | 
| Yorba Linda | 33.9 | 350 | 117.8 | 102 | 70 | 94 | 69 | 92 | 69 | 88 | 68 | 73 | 71 | 31 | 30 | 35 | 37 | 1643 | 
| Yosemite Park Hq | 37.7 | 3970 | 119.6 | 97 | 63 | 94 | 62 | 93 | 62 | 90 | 60 | 67 | 65 | 38 | 11 | 18 | 23 | 4785 | 
| Yreka | 41.7 | 2625 | 122.6 | 99 | 66 | 95 | 65 | 94 | 65 | 90 | 64 | 69 | 67 | 39 | 8 | 15 | 20 | 5395 | 
| Yuba City | 39.1 | 70 | 121.6 | 105 | 69 | 101 | 69 | 100 | 69 | 96 | 68 | 72 | 71 | 36 | 24 | 29 | 32 | 
 | 
| Yucaipa | 34 | 2600 | 117 | 106 | 68 | 102 | 67 | 101 | 67 | 98 | 65 | 73 | 71 | 35 | 27 | 32 | 35 | 
 | 
| Yucca Valley | 34.2 | 2600 | 116.4 | 108 | 71 | 105 | 70 | 104 | 70 | 101 | 69 | 75 | 73 | 32 | 19 | 24 | 27 | 862 |